ID-range 260000-260249

260001

AT-telegram was missing two times.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Logical axis number [-]

 

%3:

Actual value [-]

 

%4:

Actual value [-]

 

Error type

-

 

260002

MST telegram was missing two times, signal MSTMISS, MSTEARLY, MSTLATE.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Ring number [-]

 

%2:

Incorrect value [-]

 

%3:

Incorrect value [-]

 

%4:

Actual value [-]

 

Error type

-

 

260003

Physical transmission is disturbed.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Ring number [-]

 

%2:

Incorrect value [-]

 

%3:

Actual value [-]

 

Error type

-

 

260004

Programming error or transmission error.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Incorrect value [-]

 

%3:

Incorrect value [-]

 

%4:

Actual value [-]

 

%5:

Incorrect value [-]

 

Error type

-

 

260005

HS time-out error occurred.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Logical axis number [-]

 

%3:

Status [-]

 

Error type

-

 

260007

General time-out occurred.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Actual value [-]

 

%3:

Logical axis number [-]

 

%4:

Limit value [-]

 

%5:

Actual value [-]

 

Error type

-

 

260008

Selected phase is wrong, phase 1 after 0 not possible.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

State [-]

 

%3:

Incorrect value [-]

 

Error type

-

 

260009

Selected phase is wrong, phase 2 after 1 not possible.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

State [-]

 

%3:

Incorrect value [-]

 

Error type

-

 

260010

Selected phase is wrong, phase 3 after 2 not possible.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

State [-]

 

%3:

Incorrect value [-]

 

Error type

-

 

260011

Selected phase is wrong, phase 4 after 3 not possible.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

State [-]

 

%3:

Incorrect value [-]

 

Error type

-

 

260012

Selected phase does not exist.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

State [-]

 

%3:

Incorrect value [-]

 

Error type

-

 

260013

Phase switch exceeds time-out.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Actual value [-]

 

%3:

Limit value [-]

 

Error type

-

 

260016

Checked address could not be found.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Incorrect value [-]

 

Error type

-

 

260017

Phase switch to CP1 not possible (HS-TIMEOUT). Check drive addresses.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Incorrect value [-]

 

%3:

Incorrect value [-]

 

%4:

Incorrect value [-]

 

Error type

-

 

260018

Received telegram wrong in CP1.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Actual value [-]

 

%3:

Incorrect value [-]

 

%4:

Logical axis number [-]

 

Error type

-

 

260019

Switch back from phase 1 to phase 0 not possible.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Incorrect value [-]

 

%3:

Incorrect value [-]

 

%4:

Limit value [-]

 

Error type

-

 

260020

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

1

 

Solution

Class

8

Restart of NC-control necessary.

260021

Received phase is wrong <value 1..3> equal to err / back / phase.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Incorrect value [-]

 

%3:

Expected value [-]

 

Error type

-

 

260022

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

1

 

Solution

Class

8

Restart of NC-control necessary.

260023

Time slot parameter error <value 1..3> equal to ident / axis / ring.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Incorrect value [-]

 

%2:

Logical axis number [-]

 

%3:

Actual value [-]

 

Error type

-

 

260025

Calculation of T1.m not possible (TATAT time slot missing).

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Actual value [-]

 

%3:

Logical axis number [-]

 

Error type

-

 

260026

MDT cannot be sent in permitted time (T2 too big).

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Actual value [-]

 

%3:

Limit value [-]

 

%4:

Incorrect value [-]

 

Error type

-

 

260027 - 260030

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

1

 

Solution

Class

8

Restart of NC-control necessary.

260031

Identification 0002 in SERCON 410B not found.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Incorrect value [-]

 

%2:

Expected value [-]

 

%3:

Expected value [-]

 

Error type

-

 

260032

Sercon 410B cannot be reset.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Incorrect value [-]

 

%2:

Expected value [-]

 

Error type

-

 

260033

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

1

 

Solution

Class

8

Restart of NC-control necessary.

260034

Read data are longer than commanded data length.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Incorrect value [-]

 

%2:

State [-]

 

%3:

Expected value [-]

 

%4:

Incorrect value [-]

 

Error type

-

 

260035

Received HS-bit is wrong.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Actual value [-]

 

Error type

-

 

260036

In this moment the service channel are not open.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

[-]

 

%2:

Ident number [-]

 

%3:

Incorrect value [-]

 

%4:

Status [-]

 

Error type

-

 

260037

Wrong access of element 0.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260038

IDENT number not exist.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260039

Wrong access of element 1.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260040

Element of the name from IDENT does not exist.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260041

The transfer of the name is too short.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260042

The transfer of the name is too long.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260043

The name cannot be changed.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260044

In this time the name is write protect.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260045

The transfer of the attribute is too short.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260046

The transfer of the attribute is too long.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260047

It is impossible to change the attribute.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260048

In this time the attribute is write protect.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260049

The unit element of IDENT not exist.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260050

The transfer of the unit is too short.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260051

The transfer of the unit is too long.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260052

It is impossible to change the unit.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260053

In this time the unit is write protect.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260054

Minimum value element from IDENT does not exist.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260055

The transfer of the minimum value is too short.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260056

The transfer of the minimum value is too long.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260057

It is impossible to change the minimum value.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260058

In this time the minimum value is write protect.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260059

Maximum value element from IDENT does not exist.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260060

The transfer of the maximum value is too short.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260062

It is impossible to change the maximum value.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260063

In this time the maximum value is write protect.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260064

The transfer of the date is too short.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260065

It is impossible to change the date.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260066

It is impossible to change the date.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260067

In this time the date is write protect.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260068

The date is under the minimum value.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260069

The date is greater than the max. value.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260070

Incorrect data value.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260071

The error in service data is not code.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260074

Bad reception by transfer of date-data, signal RDIST.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Ring number [-]

 

%2:

Incorrect value [-]

 

%3:

Actual value [-]

 

Error type

-

 

260075

Transfer of MST comes be early back, signal MSTEARLY.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Ring number [-]

 

%2:

Incorrect value [-]

 

%3:

Incorrect value [-]

 

%4:

Actual value [-]

 

Error type

-

 

260076

Transfer of MST comes be late back, signal MSTLATE.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Ring number [-]

 

%2:

Incorrect value [-]

 

%3:

Incorrect value [-]

 

%4:

Actual value [-]

 

Error type

-

 

260077

Requested address too big.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Incorrect value [-]

 

%2:

Actual value [-]

 

Error type

-

 

260078

A - parameter too big.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Incorrect value [-]

 

%2:

Limit value [-]

 

Error type

-

 

260079

Y - Parameter too big.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260080

Index from a searching IDENT too big.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Incorrect value [-]

 

%2:

Limit value [-]

 

Error type

-

 

260081

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

1

 

Solution

Class

8

Restart of NC-control necessary.

260082

Wrong element instructed.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Incorrect value [-]

 

%2:

State [-]

 

%3:

Ring number [-]

 

Error type

-

 

260083

Impossible to initialize SERCOS-master.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Incorrect value [-]

 

%2:

Limit value [-]

 

Error type

-

 

260084

Order from service channel by SERCOS CP under 2.

 

Description

 

Reaction

Class

1

 

Solution

Class

6

 

Parameter

%1:

Incorrect value [-]

 

%2:

Incorrect value [-]

 

%3:

Limit value [-]

 

Error type

-

 

260085

Time slot parameter information.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Actual value [1 µsec]

 

Error type

-

 

260086

 

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

1

 

Solution

Class

8

Restart of NC-control necessary.

260089

MDT-Configuration of SERCOS telegram 7 wrong.

 

Description

At least one element of the configured master data telegram (MDT) for SERCOS is not known. All configured telegram entries must be known by the CNC to be linked to the corresponding CNC element.

If you want to configure elements in the drive telegram, which are not commanded by the CNC, just add this additional elements after linkage of CNC axis to physical axis.

Example:

  1. Telegram configuration MDT = S-0-0047, AT = S-0-0051 in the physical axis
  2. Link logical CNC axis with physical axis
  3. insert additional SI-control word P-0-3210 in drive telegram

Reaction

Class

3

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

s. P-AXIS-00016

Error type

-

 

260090

AT-Configuration of SERCOS telegram 7 wrong.

 

Description

At least one element of the configured drive telegram (AT) for SERCOS is not known. All configured telegram entries must be known by the CNC to be linked to the corresponding CNC element.

If you want to configure elements in the drive telegram, which are not linked to the CNC, just add this additional elements after linkage of CNC axis to physical axis.

Example:

  1. Telegram configuration MDT = S-0-0047, AT = S-0-0051 in the physical axis
  2. Link logical CNC axis with physical axis
  3. insert additional SI-status word P-0-3215 in drive telegram

Reaction

Class

3

 

Solution

Class

7

 

Parameter

%1:

Logical axis number [-]

s. P-AXIS-00016

%2:

Actual value [-]

s. P-AXIS-00131

Error type

-

 

260091

SERCOS, calculation of total MDT-length failed.

 

Description

 

Reaction

Class

3

 

Solution

Class

7

 

Error type

-

 

260092

Operation data write protected by a password

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260093

Operation data is write protected, it is configured cyclically.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260094

Invalid indirect addressing: (e.g., data container, list handling)

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260095

Operation data is write protected, due to other settings.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260096

Procedure command is already active.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260097

Procedure command not interruptible.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260098

Procedure command in current state not executable.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260099

Procedure command not executable (invalid / false parameters).

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Error type

-

 

260100

Invalid slave arrangement.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Actual value [-]

 

%2:

Actual value [-]

 

%3:

Logical axis number [-]

 

Error type

-