ID-range 130000-130249
130000 - 130006 |
| |||
| Description | This error message informs about internal states, error solutions and the place of error in the source.Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
130007 | Internal participant engaged maximum number of buffer locations. | ||||
| Description | While sending a PDU the system participant cannot get any PDU-buffer anymore. | |||
Reaction | Class | 3 | Output of a warning. | ||
Solution | Class | 1 | Wait, because later there may be any PDU-buffer again and then repeat instruction. | ||
Parameter | %1: | Actual value [-] | |||
Current number of PDU buffers. | |||||
%2: | Expected value [-] | ||||
Maximum number of PDU buffers for this system participant. | |||||
Error type | - | ||||
| |||||
130008 - 130104 |
| |||
| Description | This error message informs about internal states, error solutions and the place of error in the source.Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
130105 | Timeout for writing PDU to receiver. | ||||
| Description | The receiver doesn’t answers and doesn’t take the message. Possible cause of this error is a PLC which runs to slow., but has enabled the message unit in the HLI. | |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
Error type | 3, Error message from communication. | ||||
| |||||
130106 | Timeout for writing PDU to receiver. | ||||
| Description | The receiver doesn’t answers and doesn’t take the message. Possible cause of this error is a PLC which runs to slow., but has enabled the message unit in the HLI. | |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
Error type | 3, Error message from communication. | ||||
| |||||
130107 - 130119 |
| |||
| Description | This error message informs about internal states, error solutions and the place of error in the source.Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
130120 | Invalid receiver of PDU-message. | ||||
| Description | The message cannot be delivered to the receiver. Check the programmed receiver ID in the #MSG order, possible use the documented [PROG] key words. | |||
Reaction | Class | 3 |
| ||
Solution | Class | 3 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
Error type | 1, Error message from NC-program. | ||||
| |||||
130121 | Message can not be handled by receiver. | ||||
| Description | The programmed receiver doesn’t understand the message. The message will be ignored. | |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
Error type | 3, Error message from communication. | ||||
| |||||
130122 - 130124 |
| |||
| Description | This error message informs about internal states, error solutions and the place of error in the source.Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
130125 | PDU-receiver not announced or unknown. | ||||
| Description | The receiver of thios message isn’t announced until now or is unknown. The message is undeliverable and igrnored. Possible cause of this error is an unknown receiver programmed in the #MSG-report. | |||
Reaction | Class | 3 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
%2: | Incorrect value [-] | ||||
| |||||
%3: | Actual value [-] | ||||
| |||||
%4: | Actual value [-] | ||||
| |||||
%5: | Actual value [-] | ||||
| |||||
Error type | 3, Error message from communication. | ||||
| |||||
130126 | PDU not deliverable. PDU dismissed. | |||
| Description | The specified receiver doesn’t understand the message. He has sent the message back to the sender, who notices the message undeliverable. Possible cause of the error is a wrong programmed receiver. The receiver didn’t understand the message | ||
Reaction | Class | 3 |
| |
Solution | Class | 3 |
| |
Error type | 3, Error message from communication. | |||
| ||||
130127 | Participant already announced. | ||||
| Description | Every communication participant has to announce after startup of the control. Then he can sent or receive messages. A double announcement isn’t allowed, after next startup of the control the participant must register again. | |||
Reaction | Class | 1 |
| ||
Solution | Class | 1 |
| ||
Parameter | %1: | Actual value [-] | |||
| |||||
Error type | - | ||||
| |||||
130128 - 130133 |
| |||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |
130134 | New SIGNAL/WAIT-event could not be saved. | ||||
| Description | There are to much open signal- and wait-events. The control memory is full. Depending on the configuration 50 / 100 open signal- and wait- events are possible [SYSP]. | |||
Reaction | Class | 3 |
| ||
Solution | Class | 7 | Modify the cnc program and use less of synchronization events. Delete open synchronization events which are no longer used. | ||
Parameter | %1: | Actual value [-] | |||
| |||||
Error type | 3, Error message from communication. | ||||
| |||||
130135 |
| |||
| Description | This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer. | ||
Reaction | Class | 3 |
| |
Solution | Class | 8 | Restart of NC-control necessary. | |