ID-range 110250-110499

110250

Revolution limit N1 greater N2.

 

Description

The revolution N1 P-AXIS-00241 is bigger than N2 P-AXIS-00242. this is not possible.

Reaction

Class

1

N1 is limited by N2

Solution

Class

1

Correct specified revolution the parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Incorrect value [1µm/sec or 0,001°/sec]

P-AXIS-00241

%3:

Limit value [1µm/sec or 0,001°/sec]

P-AXIS-00242

%4:

Corrected value [1µm/sec or 0,001°/sec]

P-AXIS-00241

Error type

2, Error message by data transfer from parameter list into control device.

 

110251

Acceleration limit greater than permitted value.

 

Description

Maximum acceleration P-AXIS-00240 of acceleration characteristic curve was specified too big. This value must not be above the maximum acceleration P-AXIS-00008.

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1µm/sec or 0,001°/sec]

P-AXIS-00240

%3:

Limit value [1µm/sec or 0,001°/sec]

P-AXIS-00008

%4:

Corrected value [1µm/sec or 0,001°/sec]

P-AXIS-00240

Error type

2, Error message by data transfer from parameter list into control device.

 

110253

System error

 

Description

This error message informs about internal states, error solutions and the place of error in the source.Please give the complete error message data to the CNC manufacturer.

Reaction

Class

2

 

Solution

Class

8

Restart of NC-control necessary.

110254

Master-spindle not found.

 

Description

The master axis, on which the slave should be synchronized, is not available.

Reaction

Class

6

Axis is stopped at once.

Solution

Class

6

Correction of command for camming or gearing.

 

%2:

Incorrect value [-]

 

Error type

1, Error message from NC-program.

 

110264

Unknown entry in configuration list for PROFIBUS telegram

 

Description

The Number of increments per revolution is given by 0.

Reaction

Class

3

Parameter is set to 1.

Solution

Class

6

Set correct parameter, check configuration of telegram.

Parameter

%1:

Logical axis number [-]

s. P-AXIS-00016

%2:

Incorrect value [-]

 

%3:

Actual value [-]

 

%4:

Actual value [-]

 

Error type

-

 

110267

Min position lag is greater than max. position lag.

 

Description

The minimum position lag limit P-AXIS-00169 is bigger than the maximum limit P-AXIS-00168.

Reaction

Class

1

The minimal position lag is limited by the maximum value.

Solution

Class

1

Decrease of value in parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [0.1 µm or 0,0001°]

P-AXIS-00169

%3:

Limit value [0.1 µm or 0,0001°]

P-AXIS-00168

%4:

Corrected value [0.1 µm or 0,0001°]

P-AXIS-00169

Error type

2, Error message by data transfer from parameter list into control device.

 

110268

Inadmissible value for time basis of velocity.

 

Description

The specified time base for the velocity calculation is out of range.

Reaction

Class

3

Break

Solution

Class

7

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Incorrect value [-]

P-AXIS-00207

%3:

Limit value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110269

Inadmissible value for time basis of velocity.

 

Description

The specified time velocity resolution (numerator) is out of range.

Reaction

Class

3

Break

Solution

Class

7

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00206

Error type

2, Error message by data transfer from parameter list into control device.

 

110270

Inadmissible value for velocity resolution (denominator).

 

Description

The specified time velocity resolution (denominator) is out of range.

Reaction

Class

3

Break

Solution

Class

7

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00205

Error type

2, Error message by data transfer from parameter list into control device.

 

110271

Inadmissible mode for output position setpoint.

 

Description

The Mode (drive dependent, linear, modulo), how the command position shall be used, is specified wrong.

Reaction

Class

3

Break

Solution

Class

7

Correct element in axis parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Incorrect value [-]

P-AXIS-00123

%3:

Limit value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110272

Inadmissible mode for input position actual value.

 

Description

The Mode (drive dependent, linear, modulo), how the actual position shall be used, is specified wrong.

Reaction

Class

3

Break

Solution

Class

1

Correct element in axis parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00122

%3:

Limit value [-]

 

%4:

Limit value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110273

Invalid value for incr_per_rev, value corrected.

 

Description

The Number of increments per revolution is given by 0.

Reaction

Class

1

Parameter is set to 1.

Solution

Class

1

Set correct parameter.

Parameter

%1:

Logical axis number [-]

s. P-AXIS-00016

%2:

Incorrect value [Increment/Revolution]

s. P-AXIS-00092

%3:

Corrected value [Increment/Revolution]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110274

Value for parameter feinaufloesung too big.

 

Description

Element specifies the resolution of the measurement system for PROFIBUS- drives.

Reaction

Class

1

Element is limited by maximum value.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Incorrect value [-]

P-AXIS-00065

%3:

Limit value [-]

 

%4:

Corrected value [-]

P-AXIS-00065

Error type

2, Error message by data transfer from parameter list into control device.

 

110275

Number of delay cycles is over limit.

 

Description

The number of delay cycles between actual position and commanded position because of the runtime of the digital drive is specified to high.

Reaction

Class

3

Break

Solution

Class

7

Correct element in axis parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00191

%3:

Limit value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110276

Illegal geometry ramp time.

 

Description

Geometry ramp time P-AXIS-00199 is given smaller than minimal ramp time P-AXIS-00201.

Reaction

Class

1

Geometry ramp time is limited by minimal value.

Solution

Class

1

Correct values in parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1 µsec]

P-AXIS-00199

%3:

Limit value [1 µsec]

P-AXIS-00201

%4:

Corrected value [1 µsec]

P-AXIS-00199

Error type

2, Error message by data transfer from parameter list into control device.

 

110277

After initialization of one axis, it is not allow to work with default axis MDS.

 

Description

The CNC got an order to take the axis parameter data set from the standard configuration.

The message appears if the order takes place at a moment the CNC already has overtaken the axis specific axis parameter data set. At that moment it’s not allowed to overwrite the actual data set by the standard data set.

Reaction

Class

3

Order is rejected.

Solution

Class

7

You have to check if it’s necessary to interpret and take over the standard axis parameter data set at the chosen moment.

Parameter

%1:

Actual value [-]

Number of the logical axis for which the order was received to interpret and use the standard axis parameter data set.

Error type

-

 

110278

Changing of digital drive type necessary, then new start.

 

Description

It was tried to change the node type of a SERCOS bus node by actualizing the axis parameter list.

Changing the node type of a SERCOS node requires a restart of the control.

Reaction

Class

1

Output of a error message, old value stays unchanged.

Solution

Class

1

Restart control to change node type.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110281

Changing of GANTRY master axis necessary, then new start.

 

Description

The parameter P-AXIS-00070 for logical axis number of leading master axis in gantry link cannot be changed while CNC kernel is running. The new logical axis number for gantry master is not transferred, the previous active logical axis number remains valid.

Reaction

Class

1

None.

Solution

Class

1

Only change logical axis number P-AXIS-00070 in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00070.

%3:

Corrected value [-]

Corrected value of P-AXIS-00070.

Error type

2, Error message by data transfer from parameter list into control device.

 

110282

Changing the direct access of cam necessary, then new start.

 

Description

The parameter P-AXIS-00036 for direct access to cam switch signal via hardware driver function cannot be changed while CNC kernel is running. The new parameter value is not transferred, the previous active parameter value remains valid.

Reaction

Class

1

None.

Solution

Class

1

Only change P-AXIS-00036 in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00036.

%3:

Corrected value [-]

Corrected value of P-AXIS-00036.

Error type

2, Error message by data transfer from parameter list into control device.

 

110283

Changing of hardware sign cam necessary, then new start.

 

Description

The parameter P-AXIS-00037 for straightforward identification of hardware in system cannot be changed while CNC kernel is running. The new hardware identification is not transferred, the previous active hardware identification remains valid.

Reaction

Class

1

None.

Solution

Class

1

Only change hardware identification in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00037.

%3:

Corrected value [-]

Corrected value of P-AXIS-00037.

Error type

2, Error message by data transfer from parameter list into control device.

 

110286

Changing of counter channel, then new start.

 

Description

The parameter P-AXIS-00041 for physical counter channel on I/0 hardware cannot be changed while CNC kernel is running. The new parameter value is not transferred, the previous active parameter value remains valid.

Reaction

Class

1

None.

Solution

Class

1

Only change P-AXIS-00041 in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00041.

%3:

Corrected value [-]

Corrected value of P-AXIS-00041.

Error type

2, Error message by data transfer from parameter list into control device.

 

110288

Changing of hardware sign counter necessary, then new start.

 

Description

The parameter P-AXIS-00042 for straightforward identification of counter hardware in system cannot be changed while CNC kernel is running. The new counter hardware identification is not transferred, the previous active counter hardware identification remains valid.

Reaction

Class

1

None.

Solution

Class

1

Only change hardware identification P-AXIS-00042 in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00042.

%3:

Corrected value [-]

Corrected value of P-AXIS-00042.

Error type

2, Error message by data transfer from parameter list into control device.

 

110292

Changing the D/A-Channel necessary, then new start.

 

Description

The parameter P-AXIS-00048 for D/A-channel on I/0 hardware cannot be changed while CNC kernel is running. The new parameter value is not transferred, the previous active parameter value remains valid.

Reaction

Class

1

None.

Solution

Class

1

Only change P-AXIS-00048 in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00048.

%3:

Corrected value [-]

Corrected value of P-AXIS-00048.

Error type

2, Error message by data transfer from parameter list into control device.

 

110294

Changing the D/A-hardware sign necessary, then new start.

 

Description

The parameter P-AXIS-00049 for straightforward identification of D/A hardware in system cannot be changed while CNC kernel is running. The new D/A hardware identification is not transferred, the previous active D/A hardware identification remains valid.

Reaction

Class

1

None.

Solution

Class

1

Only change hardware identification P-AXIS-00049 in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00049.

%3:

Corrected value [-]

Corrected value of P-AXIS-00049.

Error type

2, Error message by data transfer from parameter list into control device.

 

110297

Changing the hardware number necessary, then new start.

 

Description

The parameter P-AXIS-00136 for number of hardware specific parameter set cannot be changed while CNC kernel is running. The modified number is not transferred, the previous number remains valid.

Reaction

Class

1

None.

Solution

Class

1

Only change number P-AXIS-00136 in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00136.

%3:

Corrected value [-]

Corrected value of P-AXIS-00136.

Error type

2, Error message by data transfer from parameter list into control device.

 

110298

Changing the first sign of actual value necessary, then new start.

 

Description

The parameter P-AXIS-00230 for sign of actual value cannot be changed while CNC kernel is running. The modified sign value is not transferred, the previous sign value remains valid.

Reaction

Class

1

None.

Solution

Class

1

Only change sign of actual value P-AXIS-00230 in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00230.

%3:

Corrected value [-]

Corrected value of P-AXIS-00230.

Error type

2, Error message by data transfer from parameter list into control device.

 

110299

Changing the first sign necessary, then new start.

 

Description

The parameter P-AXIS-00231 for sign of command value cannot be changed while CNC kernel is running. The modified sign value is not transferred, the previous sign value remains valid.

Reaction

Class

1

None.

Solution

Class

1

Only change sign of command value P-AXIS-00231 in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00231.

%3:

Corrected value [-]

Corrected value of P-AXIS-00231.

Error type

2, Error message by data transfer from parameter list into control device.

 

110300

Logical axis number of default-MDS must be 0.

 

Description

The logical number of the default axis parameter list must be zero.

Reaction

Class

3

 

Solution

Class

7

 

Parameter

%1:

Incorrect value [-]

P-AXIS-00016

Error type

2, Error message by data transfer from parameter list into control device.

 

110301

Changing of numerator of resolution necessary, then new start.

 

Description

The parameter P-AXIS-00234 for numerator of resolution of axis cannot be changed while CNC kernel is running. The new numerator value is not transferred, the previous numerator value remains valid.

Reaction

Class

1

None.

Solution

Class

1

Only change numerator P-AXIS-00234 in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00234.

%3:

Corrected value [-]

Corrected value of P-AXIS-00234.

Error type

2, Error message by data transfer from parameter list into control device.

 

110302

Changing of denominator of resolution necessary, then new start.

 

Description

The parameter P-AXIS-00233 for denominator of resolution of axis cannot be changed while CNC kernel is running. The new denominator value is not transferred, the previous denominator value remains valid.

Reaction

Class

1

None.

Solution

Class

1

Only change numerator P-AXIS-00233 in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00233.

%3:

Corrected value [-]

Corrected value of P-AXIS-00233.

Error type

2, Error message by data transfer from parameter list into control device.

 

110303

The list contains an unknown list element.

 

Description

During interpretation of a list an unknown list element is detected.

More information about type of list, unknown element etc. you can get inspecting the additional data in the message.

Reaction

Class

1

Interpretation of list is continued.

Solution

Class

1

Remove or modify the unknown list element in the corresponding list.

Error type

-

 

110304

Ask for spindle interface, but axis is no spindle.

 

Description

A spindle is defined in channel parameter list (SDA para) and a logical axis number is parametrized by parameter P-CHAN-00036.

In the axis configuration list with the corresponding logical axis number (P-AXIS-00016) no spindle (0x0004) is defined as axis type in parameter P-AXIS-00018.

Reaction

Class

2

Startup of CNC is continued, but no axis is available in the channel where the spindle was parametrized.

Solution

Class

7

 

Parameter

%1:

Expected value [-]

Parameter P-AXIS-00018 of an axis configuration list should have this value, if the axis should be a spindle.

%2:

Incorrect value [-]

Actual value of parameter P-AXIS-00018 in an axis configuration list.

%3:

Logical axis number [-]

Parameter P-AXIS-00016 of an axis configuration list, within that parameter P-AXIS-00018 is incorrect

Error type

3, Error message from communication.

 

110305

Modification of parameter feinaufloesung needs reboot.

 

Description

The parameter P-AXIS-00065 for factor between Profibus interface and CNC internal resolution cannot be changed while CNC kernel is running. The new resolution factor is not transferred, the previous active factor remains valid.

Reaction

Class

1

None.

Solution

Class

1

Only change parameter P-AXIS-00065 in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00065.

%3:

Corrected value [-]

Corrected value of P-AXIS-00065.

Error type

2, Error message by data transfer from parameter list into control device.

 

110306

System error

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

2

 

Solution

Class

8

Restart of NC-control necessary.

110307

Hardware description with that index not present.

 

Description

The specified Hardware description P-AXIS-00054 is not known.

Reaction

Class

3

Hardware number is set to the highest known hardware description.

Solution

Class

7

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

Gear Stepp

%3:

Actual value [-]

P-AXIS-00054

%4:

Limit value [-]

Highest known hardware description

%5:

Corrected value [-]

P-AXIS-00054

Error type

2, Error message by data transfer from parameter list into control device.

 

110308

Modulo difference over limit.

 

Description

The difference between upper P-AXIS-00126 and lower modulo limit P-AXIS-00127 exceeds the maximum 32 bit range. The modulo range for rotatory axis or spindles at least must be smaller the maximum 32 bit range (2147483647).

Reaction

Class

1

The upper and lower modulo limit is initialized by a default value.

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Incorrect value [0.1 µm or 0,0001°]

P-AXIS-00126 - P-AXIS-00127

%3:

Limit value [0.1 µm or 0,0001°]

 

%4:

Corrected value [0.1 µm or 0,0001°]

P-AXIS-00126

%5:

Corrected value [0.1 µm or 0,0001°]

P-AXIS-00127

Error type

2, Error message by data transfer from parameter list into control device.

 

110309

Factor for speed monitoring over limit.

 

Description

The given factor for the monitoring of the spindle revolution P-AXIS-00217 exceeds maximum.

Reaction

Class

1

Value is initialized with a default.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Incorrect value [-]

P-AXIS-00217

%3:

Limit value [-]

 

%4:

Corrected value [-]

P-AXIS-00217

Error type

2, Error message by data transfer from parameter list into control device.

 

110310

Modulo difference weight with path resolution less than or equal to 0.

 

Description

The distance between upper and lower modulo limit weighted by the resolution is to small.

Reaction

Class

1

Parameter is limited to maximum range.

Solution

Class

1

Correct modulo limits or check actual resolution.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

Difference between upper and lower modulo limit weighted with resolution (P-AXIS-00233, P-AXIS-00234)

%3:

Corrected value [-]

Corrected to minimal difference between upper and lower modulo limit

%4:

Lower limit value [0.1 µm or 0,0001°]

lower modulo limit P-AXIS-00127

%5:

Upper limit value [0.1 µm or 0,0001°]

Upper modulo limit P-AXIS-00126

Error type

-

 

110311

vb_max_red exceeds maximum axis velocity

 

Description

The safety G01-feedrate P-AXIS-00214 lies above the maximum velocity of the axis.

Reaction

Class

1

Initialization of parameter with maximum velocity of axis.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1µm/sec or 0,001°/sec]

P-AXIS-00214

%3:

Limit value [1µm/sec or 0,001°/sec]

P-AXIS-00212

%4:

Corrected value [1µm/sec or 0,001°/sec]

P-AXIS-00214

Error type

2, Error message by data transfer from parameter list into control device.

 

110312

Invalid type for position lag monitoring selected.

 

Description

The selected type of the position lag monitoring P-AXIS-00172 is unknown.

Reaction

Class

1

The position lag monitoring is turned off (type = 0)

Solution

Class

1

Set correct type of position lag monitoring in parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00172

%3:

Corrected value [-]

P-AXIS-00172

%4:

Actual value [-]

Gear Stepp

Error type

2, Error message by data transfer from parameter list into control device.

 

110316

rapid_speed_red exceeds maximum axis velocity

 

Description

The safety G00-feedrate P-AXIS-00155 lies above the maximum velocity of the axis.

Reaction

Class

1

Initialization of parameter with maximum velocity of axis.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1µm/sec or 0,001°/sec]

P-AXIS-00155

%3:

Limit value [1µm/sec or 0,001°/sec]

P-AXIS-00212

%4:

Corrected value [1µm/sec or 0,001°/sec]

P-AXIS-00155

Error type

2, Error message by data transfer from parameter list into control device.

 

110317

SGN32 Underflow: negative software limit switch - Tolerance less than MIN_SGN32.

 

Description

The negative software limit switch P-AXIS-00177 is out of range. The limit switch inclusive the tolerance band P-AXIS-00179 must be bigger then

–2147483648 (minimum signed 4byte number).

Reaction

Class

1

Value is set to minimum value.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [0.1 µm or 0,0001°]

Limit switch P-AXIS-00177

%3:

Actual value [0.1 µm or 0,0001°]

Tolerance P-AXIS-00179

%4:

Corrected value [0.1 µm or 0,0001°]

P-AXIS-00177

Error type

2, Error message by data transfer from parameter list into control device.

 

110318

SGN32 Overflow: positive software limit switch + Tolerance greater than MAX_SGN32.

 

Description

The positive software limit switch P-AXIS-00178 is out of range. The limit switch inclusive the tolerance band P-AXIS-00179 must be smaller then

2147483647 (maximum signed 4byte number).

Reaction

Class

1

Value is set to minimum value.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [0.1 µm or 0,0001°]

P-AXIS-00016

%2:

Actual value [0.1 µm or 0,0001°]

Limit switch P-AXIS-00178

%3:

Actual value [0.1 µm or 0,0001°]

Tolerance P-AXIS-00179

%4:

Corrected value [0.1 µm or 0,0001°]

P-AXIS-00178

Error type

2, Error message by data transfer from parameter list into control device.

 

110319

Unknown entry in configuration of input telegram.

 

Description

At startup of the control the mapping between the values transmitted cyclically to resp. from the drive and the internal working data of the control is defined by entries in the axis parameter list. In one of these entries an unknown value was detected.

In the following example either value 99999 in entry antr.terminal.in[1].signal_nr or value XXXXXX in entry antr.terminal.in[1].nc_ref is invalid.

Reaction

Class

3

Output of error message, erroneous entry is ignored.

Solution

Class

6

Correct entry in parameter list.

Parameter

%1:

Actual value [-]

P-AXIS-00020.

%2:

Logical axis number [-]

P-AXIS-00016

%3:

Actual value [-]

Index of erroneous entry, in the example above value 1.

%4:

Actual value [-]

Signal number of erroneous entry, in the example above 99999.

%5:

Actual value [-]

Signal name of erroneous entry, in the example above XXXXXX.

Error type

-

 

110320

Unknown entry in configuration of output telegram.

 

Description

At startup of the control the mapping between the values transmitted cyclically to resp. from the drive and the internal working data of the control is defined by entries in the axis parameter list. In one of these entries an unknown value was detected.

In the following example either value 99999 in entry antr.terminal.out[1].signal_nr or value XXXXXX in entry antr.terminal.out[1].nc_ref is invalid.

Reaction

Class

3

Output of error message, erroneous entry is ignored.

Solution

Class

6

Correct entry in parameter list.

Parameter

%1:

Actual value [-]

P-AXIS-00020.

%2:

Actual value [-]

P-AXIS-00016

%3:

Logical axis number [-]

 

%4:

Actual value [-]

 

%5:

Actual value [-]

 

Error type

-

 

110321

emergency deceleration must not be 0.

 

Description

The emergency deceleration P-AXIS-00003 of the axis is given by 0. The emergency deceleration must be greater 0.

Reaction

Class

1

Initialization of parameter with maximal acceleration of the axis value.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1µm/sec or 0,001°/sec]

P-AXIS-00003

%3:

Corrected value [1µm/sec or 0,001°/sec]

P-AXIS-00003

Error type

2, Error message by data transfer from parameter list into control device.

 

110322

emergency deceleration is greater than max. deceleration.

 

Description

The emergency deceleration P-AXIS-00003 of the axis exceeds the maximum acceleration of the axis.

Reaction

Class

1

Limitation of parameter with maximum acceleration of axis.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00003

%3:

Limit value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00008

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00003

Error type

2, Error message by data transfer from parameter list into control device.

 

110323

Terminal KL5111 cannot be used for probing.

Description

For a terminal axis with the KL5111 encoder terminal, the parameter

P-AXIS-00118 was set to 1.

It is not possible to measure with the terminal since it has no measuring input.

Response

Class

1

Error message output, P-AXIS-00118 is set to zero

Solution

Class

1

Parameter P-AXIS-00118 at zero

Parameter

%1

Logical axis number [-]

 

%2

Current value [-]

Value of P-AXIS-00118

%3

Corrected value [-]

Corrected value of P-AXIS-00118

Error type

2, Error message by data transfer from parameter list into control device.

110324

System error

 

Description

This error message informs about internal states, error solutions and the place of error in the source.Please give the complete error message data to the CNC manufacturer.

Reaction

Class

2

 

Solution

Class

8

Restart of NC-control necessary.

110326

Axis for duplication (Clone) is intern unknown.

 

Description

For easier configuration an axis could be cloned based on the axis parameters of another axis. This means, during initialization of the axis the clone just uses the data of its master as template. The clone just has to specify the differences to its master in the parameter list.

Reaction

Class

3

Abort of the instruction management

Solution

Class

1

The value of axis parameter P-AXIS-00040 needs to be checked.

Parameter

%1:

Logical axis number [-]

The logical axis that has that axis number should be the result of the clone process (P-AXIS-00016) .

%2:

Incorrect value [-]

That’s the number of the logical axis which axis parameters are used as template, but there is no axis with such a number (P-AXIS-00040).

Error type

-

 

110327

Invalid number for SERCOS-real time bit [1 ... 2].

 

Description

An invalid value for P-AXIS-00060 was entered in the axis parameter list.

Reaction

Class

1

Output of warning, value is corrected automatically.

Solution

Class

1

Enter a valid value for P-AXIS-00060 in the axis parameter list.

Parameter

%1:

Logical axis number [-]

Logical axis number.

%2:

Incorrect value [-]

Erroneous value for P-AXIS-00060.

%3:

Upper limit value [-]

Maximum allowable value for P-AXIS-00060.

%4:

Corrected value [-]

Corrected value for P-AXIS-00060.

Error type

2, Error message by data transfer from parameter list into control device.

 

110328

Percentage value Vdiff for cam-/gearing is greater than 100%

 

Description

The value for the permissible velocity difference for considering the axes as synchronous in velocity P-AXIS-00289 for cam-/gearing is greater than 100%.

The Dimension for this parameter is 0.1%.

Reaction

Class

1

Output of a warning message. Value of P-AXIS-00289 is automatically set to 100%.

Solution

Class

1

Choose value for P-AXIS-00289 less or equal than 100%

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Actual value of P-AXIS-00289.

%3:

Corrected value [-]

Corrected value of P-AXIS-00289.

Error type

2, Error message by data transfer from parameter list into control device.

 

110329

cam_gear: time_in_window timeout value is smaller than time_in_window para

 

Description

The value of P-AXIS-00291 is smaller than the value of P-AXIS-00290.

For the “velocity reached” confirmation the axis has to be within the percental windows P-AXIS-00289 for the time P-AXIS-00290.

P-AXIS-00291 is the time out value for the „velocity reached“ confirmation.

Reaction

Class

1

Output of warning. Value of P-AXIS-00290 is set to P-AXIS-00291 automatically.

Solution

Class

1

Choose value of P-AXIS-00290 less than P-AXIS-00291.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Actual value of P-AXIS-00290.

%3:

Corrected value [-]

Corrected value of P-AXIS-00290.

Error type

2, Error message by data transfer from parameter list into control device.

 

110330

Deceleration step 1 greater than maximum axis acceleration.

 

Description

The deceleration P-AXIS-00282 of the first step of the linear slope (not jerk limited) is bigger than the maximum acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

Limitation of deceleration with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00282

%3:

Upper limit value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00008

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00282

Error type

2, Error message by data transfer from parameter list into control device.

 

110331

Deceleration step 2 greater than maximum axis acceleration.

 

Description

The deceleration P-AXIS-00283 of the second step of the linear slope (not jerk limited) is bigger than the maximum acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

Limitation of deceleration with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00283

%3:

Upper limit value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00008

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00283

Error type

2, Error message by data transfer from parameter list into control device.

 

110332

Feedhold acceleration is greater than max. permissible axis acceleration

 

Description

The feedhold acceleration P-AXIS-00024 of linear slope is bigger than the maximum acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

Limitation of acceleration with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00024

%3:

Upper limit value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00008

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00024

Error type

2, Error message by data transfer from parameter list into control device.

 

110333

Ramp time for feedhold acceleration to small

 

Description

The time P-AXIS-00081 (ramp time) for in-/decreasing the maximum feedhold acceleration P-AXIS-00053 of the jerk limited slope is smaller than the minimal ramp time P-AXIS-00201 of the axis.

Reaction

Class

1

Limitation of ramp time with minimal value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1 µsec]

P-AXIS-00081

%3:

Lower limit value [1 µsec]

P-AXIS-00201

%4:

Corrected value [1 µsec]

P-AXIS-00081

Error type

2, Error message by data transfer from parameter list into control device.

 

110334

Reduced speed zone limit pos. greater than pos. software limit switch.

 

Description

The upper zone limit for reduced velocity in safety zone P-AXIS-00085, P-AXIS-00097 is greater than the upper software limit. The upper zone limit is shifted to upper software limit.

Reaction

Class

1

None.

Solution

Class

1

Upper zone limit smaller than upper software limit.

Parameter

%1:

Logical axis number [0.1 µm or 0,0001°]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0.1 µm or 0,0001°]

Current upper zone limit.

%3:

Upper limit value [0.1 µm or 0,0001°]

Upper software limit P-AXIS-00178 .

%4:

Corrected value [0.1 µm or 0,0001°]

Corrected upper zone limit.

Error type

2, Error message by data transfer from parameter list into control device.

 

110335

Reduced speed zone limit negative less than negative software limit switch.

 

Description

The lower zone limit for reduced velocity in safety zone P-AXIS-00093, P-AXIS-00105 is smaller than the lower software limit. The lower zone limit is shifted to lower software limit.

Reaction

Class

1

None.

Solution

Class

1

Lower zone limit greater than lower software limit.

Parameter

%1:

Logical axis number [0.1 µm or 0,0001°]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0.1 µm or 0,0001°]

Current lower zone limit.

%3:

Actual value [0.1 µm or 0,0001°]

Lower software limit P-AXIS-00177.

%4:

Lower limit value [0.1 µm or 0,0001°]

Corrected lower zone limit.

Error type

2, Error message by data transfer from parameter list into control device.

 

110336

Limit-deceleration step 1 greater than maximum axis acceleration.

 

Description

The current limit deceleration P-AXIS-00280 of the first step of the linear slope (not jerk limited) is bigger than the maximum acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

Limitation of deceleration with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00280

%3:

Upper limit value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00008

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00280

Error type

2, Error message by data transfer from parameter list into control device.

 

110337

Limit-deceleration step 2 greater than maximum axis acceleration.

 

Description

The current limit deceleration P-AXIS-00281 of the second step of the linear slope (not jerk limited) is bigger than the maximum acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

Limitation of deceleration with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00281

%3:

Upper limit value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00008

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00281

Error type

2, Error message by data transfer from parameter list into control device.

 

110339

Terminal KL5001 can not be used for probing.

 

Description

A terminal of type KL5001 cannot be used for probing (s. [FCT-C4]), since it does not possess an external latch input. Probing is deactivated for this axis (s. P-AXIS-00118).

Reaction

Class

1

Correction of parameter P-AXIS-00118

Solution

Class

1

Correct parameter P-AXIS-00118 or use a different terminal type.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Actual value [-]

Given value of parameter P-AXIS-00118

%3:

Corrected value [-]

Corrected value of parameter P-AXIS-00118

Error type

2, Error message by data transfer from parameter list into control device.

 

110340

Velocity dependent position loop gain for SERCOS OR CANOPEN drives not possible.

 

Description

For SERCOS and CANOpen drives the position loop is calculated in the drive. Therefore the functionality „dynamical position loop gain in dependency of velocity“ of the numerical control is not usable. For this axis the functionality is deactivated.

Reaction

Class

1

Correction of parameter P-AXIS-00244

Solution

Class

1

Correct parameter P-AXIS-00244

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Corrected value [-]

Corrected value of parameter P-AXIS-00244

Error type

2, Error message by data transfer from parameter list into control device.

 

110341

Velocity dependent kv: v2 must be greater than v1.

 

Description

The second velocity limit P-AXIS-00248 of the dynamic gain adaption is initialized smaller than the first velocity limit P-AXIS-00246.

Reaction

Class

1

Element is initialized slightly bigger than the first limit.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1µm/sec or 0,001°/sec]

P-AXIS-00248

%3:

Corrected value [1µm/sec or 0,001°/sec]

P-AXIS-00248

Error type

2, Error message by data transfer from parameter list into control device.

 

110342

Value for GANTRY master 'axis must be 0.

 

Description

The axis is marked as master axis of a gantry link with P-AXIS-00015 but the correct master axis entry P-AXIS-00070 is missing.

Reaction

Class

3

None.

Solution

Class

7

Use correct entry 0 for logical axis number P-AXIS-00070 in master axis.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Logical axis number [-]

Current logical axis number P-AXIS-00070.

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110343

If global feedforward is switched off, the value of list parameter 'vorsteuerung' must be 0.

 

Description

If feedforward control was disabled by P-AXIS-00256, e.g. in the default axis parameter list, feedforward control must also be disabled in the individual setting of the axis P-AXIS-00223.

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00223

%3:

Limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110344

Drive controlled measuring only possible with digital drives.

 

Description

Use of parameter P-AXIS-00269 only with digital drives allowed.

The parameter P-AXIS-00269 is set to default value.

Reaction

Class

1

None.

Solution

Class

1

Use of parameter P-AXIS-00269 only with digital drive corresponding to drive type setting of P-AXIS-00020.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis P-AXIS-00016.

%2:

Actual value [-]

Current parameter P-AXIS-00269.

%3:

Drive type [-]

Current drive type P-AXIS-00020.

%4:

Corrected value [-]

Corrected parameter P-AXIS-00269.

Error type

2, Error message by data transfer from parameter list into control device.

 

110345 - 110347

System error

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

2

 

Solution

Class

8

Restart of NC-control necessary.

110348

Terminal KL2521 can not be used for probing.

 

Description

A terminal of type KL2521 cannot be used for probing (s. [FCT-C4]), since it does not possess an external latch input. Probing is deactivated for this axis (s. P-AXIS-00118).

Reaction

Class

1

Correction of parameter P-AXIS-00118

Solution

Class

1

Correct parameter P-AXIS-00118 or use a different terminal type.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Actual value [-]

Given value of parameter P-AXIS-00118

%3:

Corrected value [-]

Corrected value of parameter P-AXIS-00118

Error type

2, Error message by data transfer from parameter list into control device.

 

110349

Terminal KL2521 can not home with zero pulse.

 

Description

A homing with zero pulse search (s. [FCT-M1]) cannot be performed with a terminal of type KL2521, since it does not possess an external latch input. Therefore, during homing no zero pulse search is performed for this axis (s. P-AXIS-00084).

Reaction

Class

1

Correction of parameter P-AXIS-00084

Solution

Class

1

Correct parameter P-AXIS-00084 or use a different terminal type.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Actual value [-]

Given value of parameter P-AXIS-00084

%3:

Corrected value [-]

Corrected value of parameter P-AXIS-00084

Error type

2, Error message by data transfer from parameter list into control device.

 

110350

Maximum of velocity for axis, which is not referenced, was set to 0.

 

Description

The maximum velocity for not homed axis P-AXIS-00268 is initialized with 0.

Reaction

Class

1

Parameter is initialized with default value.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1µm/sec or 0,001°/sec]

P-AXIS-00268

%3:

Corrected value [1µm/sec or 0,001°/sec]

P-AXIS-00268

Error type

2, Error message by data transfer from parameter list into control device.

 

110351

Max. of vel. for axis, which is not referenced, greater than max. vel.

 

Description

The maximum velocity for not homed axis P-AXIS-00268 is above the maximum axis velocity.

Reaction

Class

1

Value is limited by maximum velocity.

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1µm/sec or 0,001°/sec]

P-AXIS-00268

%3:

Limit value [1µm/sec or 0,001°/sec]

P-AXIS-00212

%4:

Corrected value [1µm/sec or 0,001°/sec]

P-AXIS-00268

Error type

2, Error message by data transfer from parameter list into control device.

 

110352

Axis mode not permitted for spindle.

 

Description

The axis mode P-AXIS-00015 for the spindle is not set to MODULO (= 4), even though this is required.

Reaction

Class

1

Value is set to MODULO

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00015

%3:

Corrected value [-]

P-AXIS-00015

Error type

2, Error message by data transfer from parameter list into control device.

 

110353

Unknown axis mode corrected.

 

Description

The axis mode P-AXIS-00015 is not known. Following values are possible:

1 : LINEAR

2 : optimized positioning

4 : MODULO.

Reaction

Class

1

Value is set to MODULO for spindle or rotatory axis. For translatory axis the value is set to LINEAR

Solution

Class

1

Correct value in parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00015

%3:

Corrected value [-]

P-AXIS-00015

Error type

2, Error message by data transfer from parameter list into control device.

 

110354

Global_enable and global_disable activated at the same time for this axis.

 

Description

In the parameter list the feed forward control is permanent enabled (P-AXIS-00255) and disable (P-AXIS-00256). This is setting is contra dictional.

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00255

%3:

Actual value [-]

P-AXIS-00256

%4:

Corrected value [-]

P-AXIS-00255

Error type

2, Error message by data transfer from parameter list into control device.

The feed forward control is permanent disabled by default.

110355

Feedforward can not be activated because of to few buffer places.

 

Description

You tried to enable (P-AXIS-00255) the feed forward control permanently, even though the functionality is not available in the actual version.

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00255

%3:

Limit value [-]

Maximum available numbers of samples for calculation of feed forward control.

%4:

Expected value [-]

Necessary number of samples for calculation of feed forward control.

%5:

Corrected value [-]

P-AXIS-00255

Error type

2, Error message by data transfer from parameter list into control device.

The feed forward control is not permanently enabled.

110356

Feedforward permanently enabled but no mode selected.

 

Description

The feed forward control is permanent enable without specifying the mode. At least velocity of acceleration feed forward control must be given in the mode P-AXIS-00233.

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00255

%3:

Actual value [-]

Mode of feed forward control P-AXIS-00233

%4:

Corrected value [-]

P-AXIS-00255

Error type

2, Error message by data transfer from parameter list into control device.

The feed forward control is not permanently enabled.

110357 / 110358

System error

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

2

 

Solution

Class

8

Restart of NC-control necessary.

110359

Feedhold acceleration is greater than max. permissible axis acceleration

 

Description

The feedhold acceleration P-AXIS-00259 for active manual mode operation is bigger than the maximum acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

None.

Solution

Class

1

Use feedhold acceleration setting smaller than P-AXIS-00008.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

Current setting of P-AXIS-00259.

%3:

Upper limit value [1mm/sec^2 or 1°/sec^2]

Upper limit value for acceleration P-AXIS-00008.

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

Limited feedhold acceleration P-AXIS-00259.

Error type

2, Error message by data transfer from parameter list into control device.

 

110360

The value of the parameter 'op_mode_for_velocity_control' is invalid.

 

Description

The operation mode for automatic change to velocity control mode is not valid.

Reaction

Class

1

 

Solution

Class

1

Check P-AXIS-00264

Parameter

%1:

Logical axis number [-]

s. P-AXIS-00016

%2:

Incorrect value [-]

s. P-AXIS-00264

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110361

Minimum cut-off/center frequency of filter is to low.

 

Description

The characteristic frequency (s. P-AXIS-00067) of the given axis filter is too low. The interpretation of the characteristic frequency is dependent of the filter type:

- Low pass filter: Start of cut-off region (ideal filter)

Reaction

Class

1

Correction of parameter P-AXIS-00067 to the lowest, permissible frequency.

Solution

Class

1

Increase the characteristic frequency P-AXIS-00067 of the axis filter.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Actual value [-]

Number of affected filter

%3:

Actual value [-]

Given value for the characteristic filter frequency P-AXIS-00067 in hertz.

%4:

Corrected value [-]

Corrected value for the characteristic filter frequency P-AXIS-00067 in hertz.

Error type

2, Error message by data transfer from parameter list into control device.

 

110362

Number of cycles for in-/out coupling by temperature compensation are over size.

 

Description

The specified number of cycles for activation/deactivation of the compensation values exceeds the maximum.

Reaction

Class

1

Parameter is limited to maximum range.

Solution

Class

1

Correct parameter.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Incorrect value [-]

 

%3:

Upper limit value [-]

 

%4:

Corrected value [-]

 

Error type

-

 

110363

Unknown mode for set reference position.

 

Description

Invalid parameter setting for P-AXIS-00278 is used.

The default mode is set to parameter P-AXIS-00278.

Reaction

Class

3

None.

Solution

Class

1

Only use valid mode for P-AXIS-00278.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis P-AXIS-00016.

%2:

Actual value [-]

Current parameter P-AXIS-00278.

%3:

Corrected value [-]

Corrected parameter P-AXIS-00278.

Error type

2, Error message by data transfer from parameter list into control device.

 

110364

torq_max_distance less than torq_min_distance.

 

Description

The value of torq_max_distance must not be less than the value of torq_min_distance.

Reaction

Class

1

Output of a warning message.

Solution

Class

1

Choose value of torq_max_distance greater than the value of torq_min_distance.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0.1 µm or 0,0001°]

Actual value of torq_max_distance.

%3:

Actual value [0.1 µm or 0,0001°]

Actual value of torq_min_distance.

Error type

2, Error message by data transfer from parameter list into control device.

 

110365

torq_min_distance less than 0.

 

Description

Value for torq_min_distance must not be less than zero.

Reaction

Class

1

Output of a warning message. Value of torq_min_distance is set to zero automatically.

Solution

Class

1

Choose value of torq_min_distance greater than zero.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0.1 µm or 0,0001°]

Actual value of torq_min_distance.

%3:

Corrected value [0.1 µm or 0,0001°]

Corrected value of torq_min_distance.

Error type

2, Error message by data transfer from parameter list into control device.

 

110366

torq_max_distance less than 0.

 

Description

Value for torq_max_distance must not be less than zero.

Reaction

Class

1

Output of warning. Value of torq_max_distance is set to zero automatically.

Solution

Class

1

Choose value of torq_max_distance greater than zero.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0.1 µm or 0,0001°]

Actual value of torq_max_distance.

%3:

Corrected value [0.1 µm or 0,0001°]

Corrected value of torq_max_distance.

Error type

2, Error message by data transfer from parameter list into control device.

 

110367

torq_detect_velocity_limit less than 0.

 

Description

Value for torq_detect_velocity_limit must not be less than zero.

Reaction

Class

1

Output of warning. Value of torq_detect_velocity_limit is set to zero automatically.

Solution

Class

1

Choose value of torq_detect_velocity_limit greater than zero.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0.1 µm or 0,0001°]

Actual value of torq_detect_velocity_limit.

%3:

Corrected value [0.1 µm or 0,0001°]

Corrected value of torq_detect_velocity_limit.

Error type

2, Error message by data transfer from parameter list into control device.

 

110368

retraction_distance less than 0.

 

Description

Value for retraction_distance must not be less than zero.

Reaction

Class

1

Output of warning. Value of retraction_distance is set to zero automatically.

Solution

Class

1

Choose value of retraction_distance greater than zero.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0.1 µm or 0,0001°]

Actual value of retraction_distance.

%3:

Corrected value [0.1 µm or 0,0001°]

Corrected value of retraction_distance.

Error type

2, Error message by data transfer from parameter list into control device.

 

110369 / 110370

System error

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

3

 

Solution

Class

8

Restart of NC-control necessary.

110372

Parameter mod_komp ineffective, because set internally.

 

Description

Setting the parameter P-AXIS-00120 for activating the modulo compensation has no effect because it is set internally.

Reaction

Class

1

-

Solution

Class

1

-

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

Error type

-

 

110373

Admissible value range exceeded.

 

Description

During conversion of position to increments with actual resolution of measurement system the maximum range is exceeded.

Reaction

Class

1

Parameter is limited to maximum range.

Solution

Class

1

Correct parameter of check actual resolution.

 

%5:

Logical axis number [-]

Actual resolution, s. P-AXIS-00233, P-AXIS-00234

Error type

2, Error message by data transfer from parameter list into control device.

 

110374

Command position for DSE corrected to MODE_ACC_LINEAR.

 

Description

P-AXIS-00122 and P-AXIS-00123 for normalization actual and commanded position have to be set to MODE_ACC_LINEAR (linear processing of values) for DSE for showing correct data of actual and commanded position and position lag.

Reaction

Class

1

Output of warning. P-AXIS-00123 is set to MODE_ACC_LINEAR.

Solution

Class

1

Set value of P-AXIS-00123 to MODE_ACC_LINEAR.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Actual value of P-AXIS-00123.

%3:

Corrected value [-]

Corrected value of P-AXIS-00123.

Error type

-

 

110375

Current position from DSE corrected to MODE_ACC_LINEAR.

 

Description

P-AXIS-00122 and P-AXIS-00123 for normalization actual and commanded position must be set to MODE_ACC_LINEAR (linear processing of values) for DSE for showing correct data of actual and commanded position and position lag.

Reaction

Class

1

Output of warning. P-AXIS-00122 is set to MODE_ACC_LINEAR.

Solution

Class

1

Set value of P-AXIS-00122 to MODE_ACC_LINEAR.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Actual value of P-AXIS-00122.

%3:

Corrected value [-]

Corrected value of P-AXIS-00122.

Error type

-

 

110376

torq_move_acceleration greater than dynamik.a_max.

 

Description

torq_move_acceleration is greater than the maximum permissible axis acceleration P-AXIS-00008.

Reaction

Class

1

Output of warning. Value of torq_move_acceleration is set to P-AXIS-00008 automatically.

Solution

Class

1

Choose value of torq_move_acceleration less than P-AXIS-00008.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

Actual value of torq_move_acceleration.

%3:

Limit value [1mm/sec^2 or 1°/sec^2]

Maximum permissible axis acceleration P-AXIS-00008.

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

Corrected value of torq_move_acceleration.

Error type

2, Error message by data transfer from parameter list into control device.

 

110378

torq_move_torque_limit greater than 1000.

 

Description

The value of torq_move_torque_limit for the maximum torque is greater than 1000, i.e. it is greater than 100%.

Reaction

Class

1

Output of a warning message. The value of torq_move_torque_limit is set to 1000 (100%) automatically.

Solution

Class

1

Choose value of torq_move_torque_limit less or equal than 1000 (100%).

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0,1%]

Current value of torq_move_torque_limit.

%3:

Limit value [0,1%]

1000 (100%)

%4:

Corrected value [0,1%]

Corrected value of torq_move_torque_limit.

Error type

2, Error message by data transfer from parameter list into control device.

 

110379

torq_detect_torque_limit greater than 1000.

 

Description

The value of torq_detect_torque_limit is greater than 1000, i.e. it is greater than 100%.

Reaction

Class

1

Output of a warning message. The value of torq_detect_torque_limit is set to 1000 (100%) automatically.

Solution

Class

1

Choose value of torq_detect_torque_limit less or equal than 1000 (100%).

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [0,1%]

Current value of torq_detect_torque_limit.

%3:

Limit value [0,1%]

1000 (100%)

%4:

Corrected value [0,1%]

Corrected value of torq_detect_torque_limit.

Error type

2, Error message by data transfer from parameter list into control device.

 

110380

Numerator of acceleration feed forward factor is 0.

 

Description

The numerator of the factor for normalization of the acceleration feed forward control P-AXIS-00225 was given with zero.

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00225

%3:

Corrected value [-]

P-AXIS-00225

Error type

2, Error message by data transfer from parameter list into control device.

Numerator is initialized with default value.

110381

Denominator of acceleration forward factor is 0.

 

Description

The denominator of the factor for normalization of the acceleration feed forward control P-AXIS-00226 was given with zero.

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00226

%3:

Corrected value [-]

P-AXIS-00226

Error type

2, Error message by data transfer from parameter list into control device.

Denominator is initialized with default value.

110382

D/A converter resolution (numerator) is 0.

 

Description

The resolution for the digital/analog converter (numerator) is specified with zero. This value is illegal.

Reaction

Class

1

Element is initialized by default value.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00129

%3:

Corrected value [-]

P-AXIS-00129

Error type

2, Error message by data transfer from parameter list into control device.

 

110384

This drive type does not support the parametrized homing type.

 

Description

The homing type (e.g. drive-controlled homing) which is used for the axis is specified in the parameter P-AXIS-00299. The actual drive type however does not support the given type of homing.

Reaction

Class

1

Use of default homing type (s. P-AXIS-00299)

Solution

Class

1

Change the homing type P-AXIS-00299

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Drive type [-]

Drive type of affected axis s. P-AXIS-00020

%3:

Actual value [-]

Operation mode of the axis s. P-AXIS-00320

%4:

Incorrect value [-]

Given homing type s. P-AXIS-00299

%5:

Corrected value [-]

Corrected homing type s. P-AXIS-00299

Error type

2, Error message by data transfer from parameter list into control device.

 

110385

The value of a_min is smaller as the lower limit value.

 

Description

Minimum acceleration P-AXIS-00010 of acceleration characteristic curve was specified to big. This value must not be above the minimum acceleration.

Reaction

Class

1

Limitation of value

Solution

Class

1

Correct specified acceleration in the parameter list.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1µm/sec or 0,001°/sec]

P-AXIS-00010

%3:

Limit value [1µm/sec or 0,001°/sec]

 

%4:

Incorrect value [1µm/sec or 0,001°/sec]

P-AXIS-00010

Error type

2, Error message by data transfer from parameter list into control device.

 

110386

Adjusted resolution is 0.

 

Description

The numerator of the resolution P-AXIS-00234 of the measurement system is given with zero. This value must be initialized bigger zero. The resolution of the measurement system is given as factor between P-AXIS-00234 / P-AXIS-00233 in increments per 0,1 µm or per 0,0001°.

Reaction

Class

1

Initialization of numerator with default value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00234

%3:

Corrected value [-]

P-AXIS-00234

Error type

2, Error message by data transfer from parameter list into control device.

 

110388

Max. path of referencing GANTRY slave is less than 0.

 

Description

A negative value for P-AXIS-00284 was entered in the axis parameter list. The value is corrected automatically by take in the absolute value.

Reaction

Class

1

Closed-loop controlled halt of axis

Solution

Class

1

Consult the documentation of the drive manufacturer

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016.

%2:

Actual value [0.1 µm or 0,0001°]

Actual value of P-AXIS-00284.

%3:

Limit value [0.1 µm or 0,0001°]

Lower Limit for P-AXIS-00284.

%4:

Corrected value [-]

Corrected value for P-AXIS- 00284 .

Error type

2, Error message by data transfer from parameter list into control device.

 

110389

Feedhold acc. jerk limiting SLOPE is greater than max. permissible axis acc.

 

Description

The feedhold acceleration P-AXIS-00053 of jerk limit slope is bigger than the maximum acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

Limitation of acceleration with maximum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00053

%3:

Upper limit value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00008

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

P-AXIS-00053

Error type

2, Error message by data transfer from parameter list into control device.

 

110390

1st proportional gain of the dynamic gain adaption is initialized with 0.

 

Description

The first proportional gain P-AXIS-00245 of the dynamic gain adaption was set to zero. This is an illegal value.

Reaction

Class

1

Element is initialized by default value.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00245

%3:

Corrected value [-]

P-AXIS-00245

Error type

2, Error message by data transfer from parameter list into control device.

 

110391

2nd proportional gain of the dynamic gain adaption is initialized with 0.

 

Description

The second proportional gain P-AXIS-00247 of the dynamic gain adaption was set to zero. This is an illegal value.

Reaction

Class

1

Element is initialized by default value.

Solution

Class

1

Correct parameter list of axis.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

P-AXIS-00247

%3:

Corrected value [-]

P-AXIS-00247

Error type

2, Error message by data transfer from parameter list into control device.

 

110392

Number of cycles for driving out backlash at inversion of direction too great.

 

Description

The bilateral leadscrew error compensation (s. [FCT-C5 - Leadscrew error compensation]) uses two different compensation tables for the two movement directions of the axis. The difference between the correction tables (backlash) is driven out when the movement direction of the axis changes. The backlash is distributed on several position controller cycles with the help of a filter. The number of cycles is specified in the parameter P-AXIS-00243. The given value is however greater than the permissible maximum value.

Reaction

Class

1

Reduction of the filter cycles to permissible maximum value

Solution

Class

1

Correct the value of parameter P-AXIS-00243

Parameter

%1:

Logical axis number [-]

Logical axis number of affected slave axis s. P-AXIS-00016

%2:

Incorrect value [-]

Given number of filter cycles s. P-AXIS-00243

%3:

Limit value [-]

Maximum permissible number of filter cycles s. P-AXIS-00243

%4:

Corrected value [-]

Corrected number of filter cycles s. P-AXIS-00243

Error type

-

 

110393

acceleration for homing greater than maximum permissible value.

 

Description

The acceleration for homing P-AXIS-00285 of jerk limited slope is bigger than maximum permissible acceleration P-AXIS-00008 of the axis.

Reaction

Class

1

Limitation of acceleration with maximum value

Solution

Class

1

Setting of acceleration for homing smaller than maximum value.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis P-AXIS-00016.

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

Current acceleration P-AXIS-00285.

%3:

Upper limit value [1mm/sec^2 or 1°/sec^2]

Upper limit of acceleration P-AXIS-00008.

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

Corrected acceleration P-AXIS-00285.

Error type

2, Error message by data transfer from parameter list into control device.

 

110394

ramp time smaller than minimum value.

 

Description

The slope time P-AXIS-00286 of jerk limited slope is smaller than the minimum permissible ramp time P-AXIS-00201 of the axis.

Reaction

Class

1

Limitation of ramp time with minimum value

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis P-AXIS-00016.

%2:

Actual value [1 µsec]

Current slope time P-AXIS-00286.

%3:

Lower limit value [1 µsec]

Lower limit of slope time P-AXIS-00201.

%4:

Corrected value [1 µsec]

Corrected slope time P-AXIS-00286.

Error type

2, Error message by data transfer from parameter list into control device.

 

110395

Parametrized greatest index at cross compensation exceeds limits.

 

Description

By parameter P-COMP-00004 (see [COMP]) the user specifies the index (starting at index 0) of the last entry for cross compensation in the list with correction values.

During interpretation of that list by the CNC it is checked if the specified index is between the limits that are provided for cross compensation.

Reaction

Class

1

The reaction of the CNC depends whether the number given by P-COMP-00004 exceeds the lower or upper limit for the index of the last list entries.

If the value of P-COMP-00004 is

  • > 0 Die CNC verwendet intern den Index 0.
  • > Upper limit
    The CNC limits the index to the upper limit ( see %3).

Solution

Class

1

Check the value given by parameter P-COMP-00004.

The value must be ≥ 0 and < the value that is displayed as parameter 3 of this message.

Parameter

%1:

Actual value [-]

From user by parameter P-COMP-00004 specified index of the last valid entry in the list of correction values used for cross compensation.

%2:

Corrected value [-]

Shows which value the CNC uses after sending this message.

%3:

Limit value [-]

The value of parameter P-COMP-00004 must be < as this value.

Error type

-

 

110396

Parametrized greatest index at plane compensation exceeds limits.

 

Description

By parameters P-COMP-00010, P-COMP-00011 (see [COMP]) the user specifies the indexes (starting at index 0) of the last entries for plane compensation in the list with correction values.

During interpretation of that list by the CNC it is checked if the specified indexes are between the limits that are provided for plane compensation.

Reaction

Class

3

no reaction of the CNC

Solution

Class

7

Check the value given by parameter P-COMP-00010, P-COMP-00010.

The value must be ≥ 0 and < the value that is displayed as parameter 3 of this message.

Parameter

%1:

Actual value [-]

From user by parameter P-COMP-00010 specified index of the last valid entry in the list of correction values used for plane compensation for the first axis.

%2:

Actual value [-]

From user by parameter P-COMP-00011 specified index of the last valid entry in the list of correction values used for plane compensation for the first axis.

%3:

Limit value [-]

The value of parameter P-COMP-00010, P-COMP-00010 must be < as this value.

Error type

-

 

110397

cam_gear: unknown type for mean value calculation.

 

Description

The type for P-AXIS-00300 for mean value calculation is unknown.

Reaction

Class

1

Output of warning. The value for P-AXIS-00300 is corrected to MV_NONE.

Solution

Class

1

Choose suitable type for P-AXIS-00300.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Actual value of P-AXIS-00300.

%3:

Corrected value [-]

Corrected value of P-AXIS-00300.

Error type

2, Error message by data transfer from parameter list into control device.

 

110398

cam_gear: Number of values for means value calculation not allowed.

 

Description

The number of values P-AXIS-00301, that should be used for mean value calculation in order to filter the master current values, is not allowed.

Reaction

Class

1

Output of warning. The value of P-AXIS-00301 is corrected automatically.

Solution

Class

1

Choose suitable value for P-AXIS-00301.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Actual value of P-AXIS-00301.

%3:

Corrected value [-]

Corrected value of P-AXIS-00301.

Error type

2, Error message by data transfer from parameter list into control device.

 

110399

Illegal measuring method. Only one method may be selected.

 

Description

Invalid parameter setting for P-AXIS-00117 for measurement is used.

The parameter P-AXIS-00117 is set to default value.

Reaction

Class

1

None.

Solution

Class

1

Only use parameter P-AXIS-00117 if P-AXIS-00115 is inactive.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis P-AXIS-00016.

%2:

Actual value [-]

Current parameter P-AXIS-00117.

%3:

Actual value [-]

Current parameter P-AXIS-00115.

%4:

Actual value [-]

Corrected parameter P-AXIS-00117.

%5:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110400

Illegal measuring method. Only one method may be selected.

 

Description

Invalid parameter setting for P-AXIS-00117 for measurement is used.

The parameter P-AXIS-00117 is set to default value.

Reaction

Class

1

None.

Solution

Class

1

Only use parameter P-AXIS-00117 if P-AXIS-00115 is inactive.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis P-AXIS-00016.

%2:

Actual value [-]

Current parameter P-AXIS-00117.

%3:

Actual value [-]

Current parameter P-AXIS-00115.

%4:

Corrected value [-]

Corrected parameter P-AXIS-00117.

Error type

2, Error message by data transfer from parameter list into control device.

 

110401

Illegal measuring method. Only one method may be selected.

 

Description

Invalid parameter setting for P-AXIS-00117 for measurement is used.

The parameter P-AXIS-00117 is set to default value.

Reaction

Class

1

None.

Solution

Class

1

Only use parameter P-AXIS-00117 if P-AXIS-00115 is inactive.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis P-AXIS-00016.

%2:

Actual value [-]

Current parameter P-AXIS-00269.

%3:

Actual value [-]

Current parameter P-AXIS-00117.

%4:

Corrected value [-]

Corrected parameter P-AXIS-00117.

Error type

2, Error message by data transfer from parameter list into control device.

 

110402

Illegal measuring method. Only one method may be selected.

 

Description

Invalid parameter setting for P-AXIS-00115 for measurement is used.

The parameter P-AXIS-00115 is set to default value.

Reaction

Class

1

None.

Solution

Class

1

Only use parameter P-AXIS-00115 if P-AXIS-00269 is inactive.

 

%3:

Actual value [-]

Current parameter P-AXIS-00115.

%4:

Corrected value [-]

Corrected parameter P-AXIS-00115.

Error type

2, Error message by data transfer from parameter list into control device.

 

110403

The value of max. slave velocity is 0.

 

Description

During the velocity synchronization (camming and gearing) and during synchronous camming, the maximum slave velocity P-AXIS-00302 must not be zero.

Reaction

Class

1

Output of a warning message. Value of P-AXIS-00302 is automatically set to the maximum permissible axis velocity P-AXIS-00212.

Solution

Class

1

Choose value of P-AXIS-00302 greater than zero.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1µm/sec or 0,001°/sec]

Actual value of P-AXIS-00302.

%3:

Corrected value [1µm/sec or 0,001°/sec]

Corrected value of P-AXIS-00302.

Error type

2, Error message by data transfer from parameter list into control device.

 

110404

The value of max. slave acceleration is 0.

 

Description

During the synchronization (camming and gearing) and during synchronous camming, the maximum slave acceleration P-AXIS-00303 must not be zero.

Reaction

Class

1

Output of a warning message. Value of P-AXIS-00303 is automatically set to the maximum permissible axis acceleration P-AXIS-00008.

Solution

Class

1

Choose value of P-AXIS-00303 greater than zero.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

Actual value of P-AXIS-00303.

%3:

Corrected value [1mm/sec^2 or 1°/sec^2]

Corrected value of P-AXIS-00303.

Error type

2, Error message by data transfer from parameter list into control device.

 

110405

Maximum for weighted acceleration time is to big.

 

Description

The maximum acceleration with weighting G130/G131 (s. P-AXIS-00292) is greater than the maximum permissible axis acceleration (s. P-AXIS-00008).

Reaction

Class

1

Reduction of the acceleration P-AXIS-00292 to the maximum axis acceleration

Solution

Class

1

Correct parameter P-AXIS-00292

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

Given maximum for weighted acceleration s. P-AXIS-00292

%3:

Limit value [1mm/sec^2 or 1°/sec^2]

Maximum axis acceleration s. P-AXIS-00008

%4:

Corrected value [1mm/sec^2 or 1°/sec^2]

Corrected maximum for weighted acceleration s. P-AXIS-00292

Error type

2, Error message by data transfer from parameter list into control device.

 

110406

Minimum for weighted ramp time is to small.

 

Description

The minimum for the ramp time P-AXIS-00293 with weighting G132/G133 is smaller than the minimum permissible ramp time P-AXIS-00201.

Reaction

Class

1

Increase of ramp time P-AXIS-00293 to minimum permissible ramp time

Solution

Class

1

Increase the ramp time P-AXIS-00293

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Actual value [1 µsec]

Given minimum for weighted ramp time s. P-AXIS-00293

%3:

Limit value [1 µsec]

Minimum permissible ramp time s. P-AXIS-00201

%4:

Corrected value [1 µsec]

Corrected minimum for weighted ramp time s. P-AXIS-00293

Error type

2, Error message by data transfer from parameter list into control device.

 

110409

Phasing-velocity is inadmissible.

 

Description

The phasing velocity P-AXIS-00305 for the synchronization at camming must not be zero or greater than the half of the maximum permissible axis velocity P-AXIS-00212.

Reaction

Class

1

Output of a warning message. The value of P-AXIS-00305 is automatically set to the half of the maximum permissible axis velocity P-AXIS-00212.

Solution

Class

1

Choose value of P-AXIS-00305 greater than zero and less than the half of the maximum permissible axis velocity P-AXIS-00212.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1µm/sec or 0,001°/sec]

Actual value of P-AXIS-00305.

%3:

Corrected value [1µm/sec or 0,001°/sec]

Corrected value of P-AXIS-00305.

Error type

2, Error message by data transfer from parameter list into control device.

 

110410

Phasing-acceleration is inadmissible.

 

Description

The acceleration P-AXIS-00306 for phase synchronization at camming must not be zero or greater than the half of the maximum permissible axis acceleration P-AXIS-00008.

Reaction

Class

1

Output of warning. The value of P-AXIS-00306 is automatically set to the half of the maximum permissible axis acceleration P-AXIS-00008.

Solution

Class

1

Choose value of P-AXIS-00306 greater than zero and less than the half of the maximum permissible axis acceleration P-AXIS-00008/2.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

Actual value of P-AXIS-00306.

%3:

Corrected value [1mm/sec^2 or 1°/sec^2]

Corrected value of P-AXIS-00306.

Error type

2, Error message by data transfer from parameter list into control device.

 

110411

Phasing-deceleration is inadmissible.

 

Description

The deceleration P-AXIS-00307 for the phase synchronization at camming must not be zero or greater than the half of the maximum permissible axis acceleration P-AXIS-00008.

Reaction

Class

1

Output of warning. The value of P-AXIS-00307 is automatically set to the half of the maximum permissible axis acceleration P-AXIS-00008.

Solution

Class

1

Choose value of P-AXIS-00307 greater than zero and less than the half of the maximum permissible axis acceleration P-AXIS-00008.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1mm/sec^2 or 1°/sec^2]

Actual value of P-AXIS-00307.

%3:

Corrected value [1mm/sec^2 or 1°/sec^2]

Corrected value of P-AXIS-00307.

Error type

2, Error message by data transfer from parameter list into control device.

 

110412

Coefficient (gradient) of temperature compensation exceeds valid range.

 

Description

The temperature compensation (s. [FCT-C5]) uses a linear straight line to approximate the correction values. The gradient of the straight line is given in the parameter P-AXIS-00274 in dependency of temperature. However, the actual value specified in the axis parameters list [AXIS] is not within valid range.

Reaction

Class

1

Warning, automatic correction of parameter P-AXIS-00274 to maximum or minimum permissible value.

Solution

Class

1

Correct value of P-AXIS-00274 in axis parameter list.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis (s. P-AXIS-00016)

%2:

Incorrect value [-]

Incorrect value of P-AXIS-00274

%3:

Limit value [-]

Maximum permissible value for gradient P-AXIS-00274

%4:

Limit value [-]

Minimum permissible value for gradient P-AXIS-00274

%5:

Corrected value [-]

Corrected value for parameter P-AXIS-00274

Error type

-

 

110413

torq_move_velocity > dynamik.vb_not_referenced.

 

Description

torq_move_velocity must not be greater than the maximum permissible velocity P-AXIS-00268 for unreferenced axes.

Reaction

Class

1

Output of a warning message. The value of torq_move_velocity is automatically set to the maximum permissible velocity P-AXIS-00268 for unreferenced axes.

Solution

Class

1

Choose value of torq_move_velocity less than the maximum permissible velocity P-AXIS-00268 for unreferenced axes.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1µm/sec or 0,001°/sec]

Actual value of torq_move_velocity.

%3:

Limit value [1µm/sec or 0,001°/sec]

Maximum velocity P-AXIS-00268 for unreferenced axes.

%4:

Corrected value [1µm/sec or 0,001°/sec]

Corrected value of torq_move_velocity.

Error type

2, Error message by data transfer from parameter list into control device.

 

110414

This terminal can not be used for probing.

 

Description

The axis was set up as probing axis by assigning axis parameter P-AXIS-00118 the value 1, although the unused terminal does not support this functionality.

Reaction

Class

1

Output of a warning, automatic correction of P-AXIS-00118 to zero.

Solution

Class

1

Set P-AXIS-00118 in axis parameter list to zero.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis (s. P-AXIS-00016).

%2:

Actual value [-]

Incorrect value of P-AXIS-00118.

%3:

Corrected value [-]

Corrected value P-AXIS-00118.

%4:

Actual value [-]

String containing the terminal type.

Error type

2, Error message by data transfer from parameter list into control device.

 

110415

This Terminal can not be used for homing with zero pulse.

 

Description

The homing type for the axis was set up as homing with zero pulse by assigning axis parameter P-AXIS-00084 the value 0, although the used terminal does not support this functionality.

Reaction

Class

1

Output of a warning, automatic correction of P-AXIS-00084 to 1.

Solution

Class

1

Set P-AXIS-00084 in axis parameter list to 1.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis (s. P-AXIS-00016).

%2:

Actual value [-]

Incorrect value of P-AXIS-00084.

%3:

Corrected value [-]

Corrected value P-AXIS-00084.

%4:

Actual value [-]

String containing the terminal type.

Error type

2, Error message by data transfer from parameter list into control device.

 

110416

Homing with evaluation of encoder overflow is not supported.

 

Description

For the axis homing type ‘evaluation of encoder overflow’ was parametrized by setting parameter P-AXIS-00294 to 1, although the used drive type does not support this functionality.

Reaction

Class

3

Output of a warning, automatic correction of P-AXIS-00294 to 0.

Solution

Class

7

Set P-AXIS-00084 in axis parameter list to 0.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis (s. P-AXIS-00016).

%2:

Drive type [-]

Drive type (s. P-AXIS-00020).

%3:

Actual value [-]

Incorrect value of P-AXIS-00084.

%4:

Corrected value [-]

Corrected value P-AXIS-00084.

Error type

2, Error message by data transfer from parameter list into control device.

 

110417

Fixing invalid value of parameter probing_input_number.

 

Description

The axis was set up as probing axis (P-AXIS-00118) and for the number of the drive probing input (parameter P-AXIS-00295) an invalid value was assigned.

Reaction

Class

1

Output of a warning, automatic correction of P-AXIS-00295 to 1.

Solution

Class

1

Set P-AXIS-00295 in axis parameter list to a valid value (either 1 or 2). In the drive the according digital input must be set up as probing input by assigning the drive variable IN1MODE resp. IN2MODE the value 26.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis (s. P-AXIS-00016).

%2:

Incorrect value [-]

 

%3:

Lower limit value [-]

 

%4:

Upper limit value [-]

 

%5:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110418

Value of encoder_range exceeds the permissible range

 

Description

The parameter P-AXIS-00296 is outside its permissible range.

Reaction

Class

1

Output of a warning, automatic correction of P-AXIS-00296. If P-AXIS-00296 was configured below minimum value it is set to the minimum value, otherwise, if P-AXIS-00296 was set to an value above the maximum value it is limited to the maximum value.

Solution

Class

1

Set P-AXIS-00296 to a valid value in the axis parameter list.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis (s. P-AXIS-00016).

%2:

Actual value [-]

Index of erroneous entry in the lr_hw[] array. A value of 0 means lr_hw[0].encoder_range is erroneous.

%3:

Lower limit value [-]

 

%4:

Upper limit value [-]

 

%5:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110419

Changing of encoder_range necessary, then new start.

 

Description

The parameter P-AXIS-00296 for the range of the position encoder cannot be changed while CNC kernel is running. The modified sign value is not transferred, the previous value remains valid.

Reaction

Class

0

None.

Solution

Class

0

Only change sign of command value P-AXIS-00296 in configuration mode or if CNC kernel does not run respectively.

Error type

-

 

110420

Invalid value for parameter max_reference_position_offset entered.

 

Description

The value of parameter P-AXIS-00298 (permissible distance to reference position for the suppression of an gantry error) is outside its valid range.

Reaction

Class

1

Output of warning, P-AXIS-00298 is corrected to 0.

Solution

Class

1

Only change sign of command value P-AXIS-00296 in configuration mode or if CNC kernel does not run respectively.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Lower limit value [0.1 µm or 0,0001°]

Permissible minimum value of P-AXIS-00298.

%3:

Upper limit value [0.1 µm or 0,0001°]

Permissible maximum value of P-AXIS-00298.

%4:

Incorrect value [0.1 µm or 0,0001°]

Current value of P-AXIS-00298.

%5:

Corrected value [0.1 µm or 0,0001°]

Corrected value of P-AXIS-00298.

Error type

2, Error message by data transfer from parameter list into control device.

 

110421

vb_refmax > vb_not_referenced.

 

Description

The fast homing velocity P-AXIS-00219 must not be greater than the maximum permissible velocity P-AXIS-00268 for unreferenced axes.

Reaction

Class

1

Output of a warning message. The value of P-AXIS-00219 is automatically set to the maximum permissible velocity P-AXIS-00268 for unreferenced axes.

Solution

Class

1

Choose value of P-AXIS-00219 less than the maximum permissible velocity P-AXIS-00268 for unreferenced axes.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1µm/sec or 0,001°/sec]

Actual value of P-AXIS-00219.

%3:

Limit value [1µm/sec or 0,001°/sec]

Maximum velocity P-AXIS-00268 for unreferenced axes.

%4:

Corrected value [1µm/sec or 0,001°/sec]

Corrected speed value to P-AXIS-00268.

Error type

2, Error message by data transfer from parameter list into control device.

 

110422

vb_reflow > vb_not_referenced.

 

Description

The slow homing velocity P-AXIS-00218 must not be greater than the maximum permissible velocity P-AXIS-00268 for unreferenced axes.

Reaction

Class

1

Output of a warning message. The value of P-AXIS-00218 is automatically set to the maximum permissible velocity P-AXIS-00268 for unreferenced axes.

Solution

Class

1

Choose value of P-AXIS-00218 less than the maximum permissible velocity P-AXIS-00268 for unreferenced axes.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1µm/sec or 0,001°/sec]

Actual value of P-AXIS-00218.

%3:

Limit value [1µm/sec or 0,001°/sec]

Maximum velocity P-AXIS-00268 for unreferenced axes.

%4:

Corrected value [1µm/sec or 0,001°/sec]

Corrected speed value to P-AXIS-00268.

Error type

2, Error message by data transfer from parameter list into control device.

 

110423

Line could not be written to file.

 

Description

The line with changes axis parameters could not be written to the file.

Possible reasons are:

  • The file is read only
  • The file is blocked by another process.
  • Insufficient access rights.

Reaction

Class

3

Job processing aborted.

Solution

Class

6

Remedy possible problems and process reset after that.

Problem remedials:

  • Remove write protection.
  • Wait until the blocking process releases the file or ends the blocking process
  • Check access rights.

Check access rights.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current parameter set number.

Error type

5, Error message by access on files.

 

110424

Could not delete file.

 

Description

The file could not be deleted. Possible reasons are:

  • The file is read only
  • The file is blocked by another process.
  • Insufficient access rights.

Reaction

Class

3

Job processing aborted.

Solution

Class

6

Remedy possible problems and process reset after that.

Problem remedials:

  • Remove write protection.
  • Wait until the blocking process releases the file or ends the blocking process
  • Check access rights.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current parameter set number.

Error type

5, Error message by access on files.

 

110425

Could not change file name, check file properties and access rights.

 

Description

The file could not be renamed. Possible reasons are:

  • The fie is read only
  • The file is used by another process
  • Insufficient access rights

Reaction

Class

3

Job processing aborted.

Solution

Class

6

Remedy possible problems and process reset after that.

Problem remedials:

  • Remove the read only flag
  • Terminate the process
  • Gain sufficient access rights

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current parameter set number.

Error type

5, Error message by access on files.

 

110426

The given parameter set number is invalid.

 

Description

The given parameter set number is too large. Check for maximum number of alternative parameters set ids.

Reaction

Class

3

Job processing aborted.

Solution

Class

3

Correct value of parameter set number.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Incorrect value [-]

Invalid parameter set number.

Error type

-

 

110427

There are no changed parameter values available.

 

Description

There are no changed parameter values available.

Reaction

Class

3

Job processing aborted.

Solution

Class

3

-

Parameter

%1:

Logical axis number [-]

Logische Achsnummer P-AXIS-00016 der betroffenen Achse

%2:

Actual value [-]

 

Error type

-

 

110428

Saving not possible, since parameter set is not activated.

 

Description

The change parameter values cannot be saved because the current parameter set has not been activated.

Reaction

Class

3

Job processing aborted.

Solution

Class

3

Activate current parameter set for saving.

Parameter

%1:

Logical axis number [-]

Logische Achsnummer P-AXIS-00016 der betroffenen Achse

%2:

Actual value [-]

Parameter set number.

Error type

-

 

110429

File name is too long.

 

Description

The file name of the backup list file, including the path, is too long.

Reaction

Class

3

Job processing aborted.

Solution

Class

6

Adapt length of filename resp. path.

Parameter

%1:

Logical axis number [-]

Logische Achsnummer P-AXIS-00016 der betroffenen Achse

%2:

Actual value [-]

Value of the actual parameter set id.

%3:

Limit value [-]

Maximum length of the file name, including path.

%4:

Incorrect value [-]

Current length of the file name, including path.

Error type

5, Error message by access on files.

 

110430

Activation of parameter set not possible, since there are no changed values available.

 

Description

The current parameter set cannot be activated because there are no changed parameter values.

Reaction

Class

3

Job processing aborted.

Solution

Class

3

Activation of parameter set is not possible until there are any changed values available.

Parameter

%1:

Logical axis number [-]

Logische Achsnummer P-AXIS-00016 der betroffenen Achse

%2:

Actual value [-]

Current parameter set number.

Error type

-

 

110431

Saving not possible, since there are no changed parameter values available.

 

Description

Saving is not possible because no parameter values has been changed.

Reaction

Class

1

-

Solution

Class

1

-

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Actual parameter set number.

Error type

-

 

110432

The string of the read parameter value is too long.

 

Description

The string of the read parameter value is too long.

Reaction

Class

3

Job processing aborted.

Solution

Class

6

Adapt length of parameter value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current parameter set number.

%3:

Incorrect value [-]

Length of the read parameter value.

%4:

Limit value [-]

Maximum permissible length of the parameter value.

Error type

-

 

110433

The parameter identifier could not be found.

 

Description

The entered parameter identifier is not valid.

Reaction

Class

3

Job processing aborted.

Solution

Class

3

Enter valid parameter identifier.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current parameter set number.

Error type

-

 

110434

Inconsistent axis parameters due to errors during updating process.

 

Description

Inconsistent axis parameters due to errors during updating process.

Reaction

Class

3

Job processing aborted.

Solution

Class

7

Correct axis parameters.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

Error type

-

 

110435 / 110436

System error

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

3

 

Solution

Class

8

Restart of NC-control necessary.

110437

Speed monitoring parameter was corrected from zero to vb_not_referenced.

 

Description

The limit of the monitoring velocity P-AXIS-00311 must not be zero and is corrected to P-AXIS-00268.

Reaction

Class

1

Output of Warning. Value is set to P-AXIS-00268 automatically.

Solution

Class

1

Choose value for P-AXIS-00311 must be greater than zero.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1µm/sec or 0,001°/sec]

Actual value of P-AXIS-00311.

%3:

Corrected value [1µm/sec or 0,001°/sec]

Corrected valued of P-AXIS-00311.

Error type

2, Error message by data transfer from parameter list into control device.

 

110438

Changed parameter values are already activated.

 

Description

The changed parameter values have already been activated.

Reaction

Class

1

-

Solution

Class

1

-

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Actual parameter set number.

Error type

-

 

110439

The given parameter type is invalid.

 

Description

The given parameter resp. list type is invalid.

Reaction

Class

3

Job processing aborted.

Solution

Class

3

Correct parameter resp. list type.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

Error type

-

 

110440

No parameter identifier specified.

 

Description

No parameter identifier has been specified.

Reaction

Class

3

Job processing aborted.

Solution

Class

3

Use valid parameter identifier.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current parameter set number.

Error type

-

 

110441

No parameter value specified.

 

Description

No parameter value has been specified.

Reaction

Class

3

Job processing aborted.

Solution

Class

3

Use valid parameter value.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current parameter set number.

Error type

-

 

110442

Line for parameter configuration list too long or end of line token missing.

 

Description

The line for the parameter configuration is too long or the end of line token is missing.

Reaction

Class

3

Job processing aborted.

Solution

Class

6

Adjust line length or insert end of line token.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current parameter set number.

%3:

Incorrect value [-]

Current line length.

%4:

Limit value [-]

Maximum line length.

Error type

-

 

110443

The axis management could not open the file.

 

Description

The axis management could not open the file. Possible reasons are:

  • The file is write-protected.
  • The file is blocked by another process.
  • Insufficient access rights.
  • The file does not exist.

Reaction

Class

3

Job processing aborted.

Solution

Class

6

Remedy possible problems and process reset after that.

Problem remedials:

  • Remove write protection.
  • Wait until the blocking process releases the file or end the blocking process.
  • Check access rights.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current parameter set number.

Error type

5, Error message by access on files.

 

110444

Line could not be read from file.

 

Description

A line could not be read from file. Possible reasons are:

  • The file is write-protected.
  • The file is blocked by another process.
  • Insufficient access rights.
  • The file does not exist.

Reaction

Class

3

Job processing aborted.

Solution

Class

6

Remedy possible problems and process reset after that.

Problem remedials:

  • Remove write protection.
  • Wait until the blocking process releases the file or end the blocking process.
  • Check access rights.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current parameter set number.

Error type

5, Error message by access on files.

 

110445

Phasing jerk inadmissible.

 

Description

The value for the phasing jerk j_phasing must not be zero or greater than the maximum jerk.

For this the maximum jerk is half the value of the maximum acceleration divided by the minimum permissible ramp time.

Reaction

Class

1

Output of a warning message. The value of j_phasing is automatically set to the maximum jerk.

Solution

Class

1

Set value of j_phasing greater than zero and less than the maximum jerk.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1mm/2^3 or 1°/sec^3]

Actual value of j_phasing.

%3:

Corrected value [1mm/2^3 or 1°/sec^3]

To the maximum jerk corrected value of j_phasing.

Error type

2, Error message by data transfer from parameter list into control device.

 

110446

Jerk for velocity synchronization inadmissible.

 

Description

The value of the jerk j_vel_sync for velocity synchronization must not be zero or greater than the maximum jerk.

For this the maximum jerk is half the value of the maximum acceleration divided by the minimum permissible ramp time.

Reaction

Class

1

Output of a warning message. The value of j_vel_sync is automatically set to the maximum jerk.

Solution

Class

1

Set value of j_vel_sync greater than zero and less than the maximum jerk.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [1mm/2^3 or 1°/sec^3]

Actual value of j_vel_sync.

%3:

Corrected value [1mm/2^3 or 1°/sec^3]

To the maximum jerk corrected value of j_vel_sync.

Error type

2, Error message by data transfer from parameter list into control device.

 

110447

Invalid value for parameter P979_3 was corrected.

 

Description

In the axis parameter list the functionality ‘read absolute position from drive’ was activated (see P-AXIS-00315) and P-AXIS-00316 was assigned no respectively an invalid value.

This parameter is by default initialized with -1, so if there is no entry for this parameter in the Parameter list this warning is issued.

Reaction

Class

1

P-AXIS-00316 is automatically corrected.

Solution

Class

1

Change value of P-AXIS-00316 or enter an entry in the axis parameter list.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Incorrect value [-]

Current value of P-AXIS-00316.

%3:

Lower limit value [-]

Permissible minimum value of P-AXIS-00316.

%4:

Upper limit value [-]

Permissible maximum value of P-AXIS-00316.

%5:

Corrected value [-]

Corrected value of P-AXIS-00316.

Error type

2, Error message by data transfer from parameter list into control device.

 

110448

Invalid value for parameter P979_4 was corrected.

 

Description

In the axis parameter list the functionality ‘read absolute position from drive’ was activated (see P-AXIS-00315) and P-AXIS-00317 was assigned not respectively an invalid value.

This parameter is by default initialized with –1, so if there is no entry for this parameter in the Parameter list this warning is issued.

Reaction

Class

1

P-AXIS-00317 is automatically corrected.

Solution

Class

1

Change value of P-AXIS-00317 or enter an entry in the axis parameter list.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Incorrect value [-]

Current value of P-AXIS-00317.

%3:

Lower limit value [-]

Permissible minimum value of P-AXIS-00317.

%4:

Upper limit value [-]

Permissible maximum value of P-AXIS-00317.

%5:

Corrected value [-]

Corrected value of P-AXIS-00317.

Error type

2, Error message by data transfer from parameter list into control device.

 

110449

Invalid value for parameter read_abs_pos_mode was corrected.

 

Description

In the axis parameter list the functionality ‘read absolute position from drive’ was activated (see P-AXIS-00315) and P-AXIS-00318 was assigned no respectively an invalid value.

This parameter is by default initialized with –1, so if there is no entry for this parameter in the Parameter list this warning is issued.

Reaction

Class

1

P-AXIS-00318 is automatically corrected.

Solution

Class

1

Change value of P-AXIS-00318 or enter an entry in the axis parameter list.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Incorrect value [-]

Current value of P-AXIS-00318.

%3:

Upper limit value [-]

Permissible maximum value of P-AXIS-00318.

%4:

Corrected value [-]

Corrected value of P-AXIS-00318.

Error type

2, Error message by data transfer from parameter list into control device.

 

110450

Modification of parameter p1042 needs reboot.

 

Description

Parameter P-AXIS-00316 cannot be changed while CNC kernel is running. The new value is not taken over, the previous active value remains valid.

Reaction

Class

1

None.

Solution

Class

1

Restart control after changing P-AXIS-00316.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00316.

%3:

Corrected value [-]

Corrected value of P-AXIS-00316.

Error type

2, Error message by data transfer from parameter list into control device.

 

110451

Modification of parameter p1043 needs reboot.

 

Description

Parameter P-AXIS-00317 cannot be changed while CNC kernel is running. The new value is not taken over, the previous active value remains valid.

Reaction

Class

1

None.

Solution

Class

1

Restart control after changing P-AXIS-00317.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00317.

%3:

Corrected value [-]

Corrected value of P-AXIS-00317.

Error type

2, Error message by data transfer from parameter list into control device.

 

110452

Modification of parameter read_abs_pos_mode needs reboot.

 

Description

Parameter P-AXIS-00318 cannot be changed while CNC kernel is running. The new value is not taken over, the previous active value remains valid.

Reaction

Class

1

None.

Solution

Class

1

Restart control after changing P-AXIS-00318.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00318.

%3:

Corrected value [-]

Corrected value of P-AXIS-00318.

Error type

2, Error message by data transfer from parameter list into control device.

 

110453

Modification of parameter read_abs_pos_from_drive needs reboot.

 

Description

Parameter P-AXIS-00315 cannot be changed while CNC kernel is running. The new value is not taken over, the previous active value remains valid.

Reaction

Class

1

None.

Solution

Class

1

Restart control after changing P-AXIS-00315.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Current value of P-AXIS-00315.

%3:

Corrected value [-]

Corrected value of P-AXIS-00315.

Error type

2, Error message by data transfer from parameter list into control device.

 

110454

Value for quantization of the measuring system increments is zero.

 

Description

The value for the quantization of the measuring system increments is zero. It must be greater zero. The default value is one increment.

The speed monitoring function for spindles (s. [FCT-S1 - Spindle monitoring] and the function accuracy stop of axes check, if the actual values are within a tolerance window. The parameter P-AXIS-00323 is the minimum size of the tolerance window after the conversion of the tolerance bounds into the resolution of the measuring system (default setting: one increment).

Reaction

Class

1

Correction of the parameter P-AXIS-00323 to the default value 1

Solution

Class

1

Correct parameter P-AXIS-00323

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Incorrect value [-]

Given value s. P-AXIS-00323

%3:

Corrected value [-]

Corrected value s. P-AXIS-00323

Error type

-

 

110455

A specification for a link is not allowed for GANTRY slave axis.

 

Description

The parameter P-AXIS-00101 connects a logical axis in the interpolator to a physical axis in the position controller. This is not allowed for a gantry slave axis (s. [FCT-C11]) since it may not be moved independently from the gantry master axis and is therefore not available in the interpolator.

Reaction

Class

3

Abortion of start-up

Solution

Class

7

Set parameter P-AXIS-00101 to zero

Parameter

%1:

Incorrect value [-]

Given value for parameter P-AXIS-00101

Error type

2, Error message by data transfer from parameter list into control device.

 

110456

Changing the operation mode requires a restart.

 

Description

The operation mode (s. P-AXIS-00320) of an axis cannot be changed (e.g. by updating a parameter list) while the numerical control is running. It has to be stopped and restarted in order to change the operation mode.

Reaction

Class

1

Warning, operation mode is corrected to the old value

Solution

Class

1

Stop and restart the numerical control

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Drive type [-]

Drive type of affected axis s. P-AXIS-00020

%3:

Incorrect value [-]

New operation mode for axis s. P-AXIS-00320

%4:

Corrected value [-]

Actual used operation mode for axis s. P-AXIS-00320

Error type

2, Error message by data transfer from parameter list into control device.

 

110457

This drive type does not support the parameterized operation mode.

 

Description

The configured operation mode (s. P-AXIS-00320) is not supported for the used drive type.

Reaction

Class

1

Warning and correction of the operation mode

Solution

Class

1

Select an operation mode, which is supported for the drive type

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Drive type [-]

Drive type of affected axis s. P-AXIS-00020

%3:

Incorrect value [-]

Parameterized operation mode for axis s. P-AXIS-00320

%4:

Corrected value [-]

Corrected operation mode for axis s. P-AXIS-00320

Error type

2, Error message by data transfer from parameter list into control device.

 

110459

Conventional and adaptive feedforward activated at the same time.

 

Description

In parameter P-AXIS-00223 adaptive feedforward (bits 4 … 6) and conventional (bits 0 … 3) feedforward are activated at the same time.

Reaction

Class

1

Output of warning, correction of P-AXIS-00223 to 0.

Solution

Class

1

Correct value of P-AXIS-00223.

Parameter

%1:

Logical axis number [-]

P-AXIS-00016

%2:

Actual value [-]

Actual value of P-AXIS-00223.

%3:

Corrected value [-]

Corrected value of P-AXIS-00223.

Error type

2, Error message by data transfer from parameter list into control device.

 

110460

Limiting velocity of regulation (vb_regelgrenze) equal zero expected for spindles without sensor.

 

Description

Parameter P-AXIS-00220 describes the limiting speed, starting from which the measuring system supplies invalid values (e.g. spindles at higher rotational speeds). When this speed is exceeded, the position controller of the axis is switched to open-loop controlled operation mode, since without actual values the axis cannot be regulated any longer.

For a spindle without a sensor therefore the limiting speed must be set to zero.

Possible solutions:

  • Spindle without sensor: Set the limiting speed P-AXIS-00220 to zero.

Actual values must be included in the cyclic telegram for this axis.

Reaction

Class

1

Warning and correction of parameter P-AXIS-00220

Solution

Class

1

Correct parameter P-AXIS-00220

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Drive type [-]

Drive type of affected axis s. P-AXIS-00020

%3:

Incorrect value [-]

Specified limiting velocity for this axis s. P-AXIS-00220

%4:

Expected value [-]

Expected limiting velocity for this axis s. P-AXIS-00220

%5:

Corrected value [-]

Corrected value for limiting velocity s. P-AXIS-00220

Error type

2, Error message by data transfer from parameter list into control device.

 

110461

Number of configured user idents exceeds limit.

 

Description

During the configuration of drive functions (see [FCT-A10]) the number of configured elements in the cyclic process data that shall be written, exceeded the maximum limit

Reaction

Class

3

Abortion of program.

Solution

Class

6

Adjust value of VAL in the NC-program.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Actual value [-]

Drive type (P-AXIS-00020).

%3:

Actual value [-]

Actual value.

%4:

Limit value [-]

Maximum admissible value.

%5:

Actual value [-]

 

Error type

-

 

110462

User ident with zero length configured.

 

Description

In the output telegram of the drive a telegram element with data length zero was configured.

Reaction

Class

3

Abortion of program.

Solution

Class

6

Change signal length of telegram element.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Actual value [-]

Drive type, see P-AXIS-00020.

%3:

Actual value [-]

Index of erroneous telegram element.

%4:

Actual value [-]

Name of erroneous telegram element.

%5:

Actual value [-]

Signal number of erroneous telegram element.

Error type

-

 

110463

Additive torque command is greater than nominal torque.

 

Description

The additive torque command (see. P-AXIS-00324) configured in the axis parameter list is greater than 1000. So the additional torque would be greater than the nominal torque of the motor.

Reaction

Class

1

Output of a warning, P-AXIS-00324 is limited automatically to 0.

Solution

Class

1

Assign P-AXIS-00324 a value less than zero.

Parameter

%1:

Logical axis number [-]

Logical axis number (s. P-AXIS-00016).

%2:

Lower limit value [0.1 µm or 0,0001°]

 

%3:

Upper limit value [0.1 µm or 0,0001°]

 

%4:

Incorrect value [0.1 µm or 0,0001°]

 

%5:

Corrected value [0.1 µm or 0,0001°]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110464

Additive torque command is not supported by this drive type.

 

Description

Output of an additive torque command value (see P-AXIS-00324) was configured in the axis parameter list, although the set up drive type (see P-AXIS-00020) does not support this.

Reaction

Class

1

Output of a warning, output of an additive torque command value is deactivated by setting P-AXIS-00324 to zero.

Solution

Class

1

Remove P-AXIS-00324 from the axis parameter list or set it to zero.

Parameter

%1:

Logical axis number [-]

Logical axis number (s. P-AXIS-00016).

%2:

Actual value [-]

Drive type (s. P-AXIS-00020).

%3:

Incorrect value [-]

Parametrized value of P-AXIS-00324.

%4:

Corrected value [-]

Corrected value of P-AXIS-00324.

Error type

2, Error message by data transfer from parameter list into control device.

 

110465

Denominator for torque scaling must not be zero.

 

Description

The denominator of the torque scaling factor (s. P-AXIS-00326) was assigned the value 0.

Reaction

Class

1

Output of warning, torque scaling factor is set internally to zero.

Solution

Class

1

Assign P-AXIS-00326 a value which is not zero.

Parameter

%1:

Logical axis number [-]

Logical axis number (s. P-AXIS-00016).

%2:

Incorrect value [-]

Erroneous value of P-AXIS-00326.

%3:

Corrected value [-]

Corrected value of P-AXIS-00326.

%4:

Corrected value [-]

Corrected value of P-AXIS-00325.

Error type

2, Error message by data transfer from parameter list into control device.

 

110466

Illegal measuring method. Only one method may be selected.

 

Description

P-AXIS-00330 was set and additionally one of the parameters P-AXIS-00269, P-AXIS-00269, P-AXIS-00269, P-AXIS-00269 or P-AXIS-00257 was also set.

If P-AXIS-00330 is not other measurement method can be active.

Reaction

Class

1

Output of an error message, P-AXIS-00269, P-AXIS-00269, P-AXIS-00269, P-AXIS-00269 and P-AXIS-00257 are set to zero.

Solution

Class

1

Configure measurement method correctly.

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

Value of P-AXIS-00330.

Error type

2, Error message by data transfer from parameter list into control device.

 

110467

Invalid value for ref_cam_input.

 

Description

In P-AXIS-00321 a digital input for the reference cam signal was configured which does not fit to the drive type used (see also P-AXIS-00321).

Reaction

Class

1

Output of warning, P-AXIS-00321 is set to “PLC”.

Solution

Class

1

Assign P-AXIS-00321 a value which is supported by the drive.

Parameter

%1:

Logical axis number [-]

Logical axis number (s. P-AXIS-00016).

%2:

Drive type [-]

Drive type (s. P-AXIS-00020).

%3:

Incorrect value [-]

Erroneous value of P-AXIS-00321.

%4:

Corrected value [-]

Corrected value of P-AXIS-00321.

Error type

2, Error message by data transfer from parameter list into control device.

 

110468

Homing on hardware limit switch without reversing is not possible.

 

Description

P-AXIS-00329 and P-AXIS-00157 are set simultaneously. This is not possible because homing on hardware limit switches is done in principle with reversing.

Reaction

Class

3

Output of warning, P-AXIS-00157 is set to 0.

Solution

Class

1

Assign either P-AXIS-00329 or P-AXIS-00157 the value 0.

Parameter

%1:

Logical axis number [-]

Logical axis number (s. P-AXIS-00016).

%2:

Drive type [-]

Drive type (s. P-AXIS-00020).

%3:

Actual value [-]

Erroneous value of P-AXIS-00157.

%4:

Corrected value [-]

Corrected value of P-AXIS-00157.

Error type

2, Error message by data transfer from parameter list into control device.

 

110469

Homing on hardware limit switch without cam is not possible.

 

Description

P-AXIS-00329 and P-AXIS-00156 are set simultaneously. This is not possible.

Reaction

Class

3

Output of warning, P-AXIS-00156 is set to 0.

Solution

Class

1

Assign either P-AXIS-00329 or P-AXIS-00156 the value 0.

Parameter

%1:

Logical axis number [-]

Logical axis number (s. P-AXIS-00016).

%2:

Drive type [-]

Drive type (s. P-AXIS-00020).

%3:

Actual value [-]

Erroneous value of P-AXIS-00156.

%4:

Corrected value [-]

Corrected value of P-AXIS-00156.

Error type

2, Error message by data transfer from parameter list into control device.

 

110470

Homing on hardware limit switch is only with CNC controlled homing possible.

 

Description

Homing on hardware limit (P-AXIS-00329) switches and a homing type different to “CNC_CONTROLLED” was set up.

Reaction

Class

3

Output of warning, P-AXIS-00329 is set to 0.

Solution

Class

1

Set up either cnc controlled homing (P-AXIS-00299 = CNC_CONTROLLED ) or set P-AXIS-00329 to .

Parameter

%1:

Logical axis number [-]

Logical axis number (s. P-AXIS-00016).

%2:

Actual value [-]

Drive type (s. P-AXIS-00020).

%3:

Actual value [-]

Erroneous value of P-AXIS-00329.

%4:

Corrected value [-]

Corrected value of P-AXIS-00329.

Error type

2, Error message by data transfer from parameter list into control device.

 

110471

Invalid value for feed constant nominator.

 

Description

Axis parameter P-AXIS-00362 was set to zero.

Reaction

Class

3

Output of this error message, P-AXIS-00362 is set to 1.

Solution

Class

7

Set P-AXIS-00362 to a valid value. Valid range is 1 .. MAX_UNS32.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Lower limit value [-]

 

%4:

Upper limit value [-]

 

%5:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110472

Invalid value for feed constant denominator.

 

Description

Axis parameter P-AXIS-00363 was set to zero.

Reaction

Class

3

Output of this error message, P-AXIS-00363 is set to 1.

Solution

Class

7

Set P-AXIS-00363 to a valid value. Valid range is 1 .. MAX_UNS32.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Lower limit value [-]

 

%4:

Upper limit value [-]

 

%5:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110473

Denominator of scaling factor for jerk feedforward must not be zero.

 

Description

The denominator of the scaling factor for jerk feedforward (P-AXIS-00338) was set to zero.

Reaction

Class

1

Output of warning, P-AXIS-00338 is set to 100.

Solution

Class

1

Set P-AXIS-00338 to a value other than zero.

Parameter

%1:

Logical axis number [-]

Logical axis number (s. P-AXIS-00016).

%2:

Incorrect value [-]

Erroneous value of P-AXIS-00338.

%3:

Corrected value [-]

Corrected value of P-AXIS-00338.

Error type

2, Error message by data transfer from parameter list into control device.

 

110474

Backlash in leadscrew error compensation exceeds range of values.

 

Description

The bilateral leadscrew error compensation (s. [FCT-C5], P-COMP-00021) must drive out the difference (backlash) between correction value in positive direction (s. P-COMP-00023) and negative direction (s. P-COMP-00024) at reversal of movement direction. However, the specified backlash in the compensation table (s. [COMP]) exceeds the permissible range.

Reaction

Class

3

The transfer of the compensation table into the control is stopped.

Solution

Class

7

Correct the compensation table (s. [COMP])

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis (s. P-AXIS-00016).

%2:

Actual value [-]

Index in the compensation table of the affected compensation value pair.

%3:

Actual value [Increment]

Compensation value in positive direction (s. P-COMP-00023)

%4:

Actual value [Increment]

Compensation in negative direction (s. P-COMP-00023)

%5:

Incorrect value [Increment]

 

Error type

-

 

110475

Signal length configured in user ident is not supported.

 

Description

The length of the configured telegram element is not supported by the NC-kernel.

Reaction

Class

3

Abortion of program.

Solution

Class

6

Change signal length of telegram element.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Actual value [-]

Drive type, see P-AXIS-00020.

%3:

Actual value [-]

Index of erroneous telegram element.

%4:

Actual value [-]

Name of erroneous telegram element.

%5:

Incorrect value [-]

Signal number of erroneous telegram element.

Error type

-

 

110476

Compensation value change in leadscrew error compensation exceeds range of values.

 

Description

The difference of two following compensation values (s. P-COMP-00023, P-COMP-00024) in the compensation table (s. [COMP]) of the leadscrew error compensation (s. [FCT-C5 - Leadscrew error compensation]) exceeds range of values. If metrical input in 0.1 µm is used, the compensation values are multiplied with the resolution of the axis (s. P-AXIS-00234/P-AXIS-00233).

Solution:

Reduce spacing between interpolation points (s. P-COMP-00017) or insert additional intermediate points in the compensation table to reduce the compensation value change per interval.

Reaction

Class

3

The leadscrew error compensation (s. [FCT-C5]) is not activated.

Solution

Class

7

Correct the compensation table of the leadscrew error compensation (s. [COMP]).

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Table index of affected compensation value

%3:

Actual value [Increment]

Actual compensation value in increments (s. P-COMP-00023/P-COMP-00024)

%4:

Actual value [Increment]

Next compensation value in increments (s. P-COMP-00023/P-COMP-00024)

%5:

Incorrect value [Increment]

Difference between both compensation values in increments

Error type

-

 

110477

Position of interpolation point in leadscrew error compensation exceeds range of values.

 

Description

The interpolation points in the compensation table of the equidistant leadscrew error compensation (s. [FCT-C5 - Leadscrew error compensation]) are defined with the start point (s. P-COMP-00019), the spacing between the interpolation points (s. P-COMP-00020) and the number of entries (s. P-COMP-00020). The out of these data computed end position (P-COMP-00019 + P-COMP-00020 * P-COMP-00018) is however larger than permissible.

Possible solutions:

- Reduce the number of entries P-COMP-00020 in compensation table

Reaction

Class

3

The leadscrew error compensation (s. [FCT-C5]) is not activated.

Solution

Class

7

Correct the compensation table (s. [COMP]) of the leadscrew error compensation.

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis

%2:

Incorrect value [Increment]

Computed end position of compensation table

%3:

Upper limit value [Increment]

Largest, permissible position of an interpolation point

Error type

2, Error message by data transfer from parameter list into control device.

 

110478

Compensation value in leadscrew error compensation exceeds range of values.

 

Description

If the compensation values are entered metrically in 0,1 µm (s. P-COMP-00017), the control converts the values into increments by multiplying them with the resolution of the axis (s. P-AXIS-00234/P-AXIS-00233). The resulting value exceeds the range of values.

Reaction

Class

3

The leadscrew error compensation (s. [FCT-C5]) is not activated.

Solution

Class

7

Correct the compensation table of the leadscrew error compensation (s. [COMP]).

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Incorrect value [Increment]

Compensation value in increments (s. P-COMP-00023/P-COMP-00024)

%3:

Lower limit value [Increment]

Minimum permissible value

%4:

Upper limit value [Increment]

Maximum permissible value

%5:

Actual value [-]

Table index of affected compensation value

Error type

2, Error message by data transfer from parameter list into control device.

 

110479

Distance of interpolation points in leadscrew error compensation exceeds range of values.

 

Description

If the distance between the interpolation points for the leadscrew error compensation (s. [FCT-C5]) is entered metrically in 0,1 µm (s. P-COMP-00017), the control converts the value into increments by multiplying it with the resolution of the axis (s. P-AXIS-00234/P-AXIS-00233). The resulting value exceeds the range of values.

Solution:

Reduce the distance between the interpolation points (s. P-COMP-00018) in the compensation table (s. [COMP]).

Reaction

Class

3

The leadscrew error compensation (s. [FCT-C5]) is not activated.

Solution

Class

7

Correct the compensation table of the leadscrew error compensation (s. [COMP]).

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Incorrect value [Increment]

Spacing of interpolation points in increments.

%3:

Lower limit value [Increment]

Minimum permissible spacing of interpolation points in increments.

%4:

Upper limit value [Increment]

Maximum permissible spacing of interpolation points in increments.

%5:

Actual value [0.1 µm or 0,0001°]

Spacing of interpolation points P-COMP-00018 from compensation table.

Error type

2, Error message by data transfer from parameter list into control device.

 

110480

Distance of interpolation points in leadscrew error compensation exceeds range of values.

 

Description

If the interpolation points P-COMP-00025 of the compensation table for the leadscrew error compensation (s. [FCT-C5]) are entered metrically in 0,1 µm (s. P-COMP-00017), the control converts the positions into increments by multiplying them with the resolution of the axis (s. P-AXIS-00234/P-AXIS-00233). The resulting spacing between two interpolation points exceeds however the range of values.

Solution:

Insert additional intermediate points P-COMP-00025 in the compensation table to reduce the spacing between the interpolation points.

Reaction

Class

3

The leadscrew error compensation (s. [FCT-C5]) is not activated.

Solution

Class

7

Correct the compensation table of the leadscrew error compensation (s. [COMP]).

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis.

%2:

Actual value [-]

Table index of affected interpolation point

%3:

Actual value [Increment]

Position of affected interpolation point in increments

%4:

Actual value [Increment]

Position of next interpolation point in increments

%5:

Incorrect value [Increment]

Spacing between both interpolation points in increments.

Error type

-

 

110481

Modification of parameter abs_pos_revolutions needs reboot.

 

Description

It was tried to change P-AXIS-00326 due to a list download. A reboot of the control is necessary to change P-AXIS-00326.

Reaction

Class

1

Reboot control after changing P-AXIS-00326.

Solution

Class

1

Change signal length of telegram element.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00326.

%2:

Actual value [-]

Value of P-AXIS-00326 entered ion the axis parameter list (new value).

%3:

Corrected value [-]

Old value of P-AXIS-00326.

Error type

2, Error message by data transfer from parameter list into control device.

 

110482

Invalid range of values for homing with encoder overflow evaluation.

 

Description

Parameter P-AXIS-00355 is set to a value outside its valid range.

Reaction

Class

1

Output of this warning, correction of this parameter to 0, this causes a drive dependent default initialization.

Solution

Class

1

Insert correct value for P-AXIS-00355.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Lower limit value [-]

 

%4:

Upper limit value [-]

 

%5:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110483

Different latch methods for probing/zero pulse search in telegram configured.

 

Description

The combination of two touch-probing methods (e.g. manufacturer specific or probing according to CiA402) for measuring or zero pulse search is not possible. The control selects the touch probing method in dependency of the configured cyclic command and actual values telegram. Objects belonging to different latch methods cannot be combined.

Example for a configuration of the cyclic telegram for probing according CANopen CiA402 profile:

Command values telegram:

- Touch probe status (0x60B9)

Actual values telegram:

Reaction

Class

3

 

Solution

Class

6

Correct the configuration of the cyclic telegram

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis

%3:

Incorrect value [-]

Object of first touch probe method

Error type

2, Error message by data transfer from parameter list into control device.

 

110484

System error

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

3

 

Solution

Class

8

Restart of NC-control necessary.

110485

Invalid value for latch input used in zero pulse search is corrected.

 

Description

Parameter P-AXIS-00364 was assigned an invalid value.

Reaction

Class

1

Output of this error message correction of the parameter to 1.

Solution

Class

1

Enter a valid value for P-AXIS-00364 (value range 1..2).

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Lower limit value [-]

 

%4:

Upper limit value [-]

 

%5:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110486

This drive type does not support feedforward balancing.

 

Description

Feedforward balancing was activated (P-AXIS-00361 ≠ 0) although it is not implemented for this drive type.

Reaction

Class

1

Output of a warning and deactivation of feedforwad balancing.

Solution

Class

1

Deactivate feedforward balancing (set P-AXIS-00261 to zero).

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [1 µsec]

 

%3:

Corrected value [1 µsec]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110487

Changing the operation mode "Gantry master axis" requires a restart.

 

Description

The operation of an axis as „master axis of a gantry link“ (s. P-AXIS-00015, [FCT-C11]) may not be changed while the CNC is running. The new value is not used; the old setting remains further valid.

Reaction

Class

0

Warning and correction of parameter P-AXIS-00015

Solution

Class

0

Only change the operation mode “master axis of gantry link” in configuration mode or if the CNC does not run.

Error type

-

 

110488

Changing the operation mode "Gantry slave axis" requires a restart.

 

Description

The operation of an axis as „slave axis of a gantry link“ (s. P-AXIS-00015, [FCT-C11]) may not be changed while the CNC is running. The new value is not used; the old setting remains further valid.

Reaction

Class

0

Warning and correction of parameter P-AXIS-00015

Solution

Class

0

Only change the operation mode „slave axis of gantry link“ in configuration mode or if the CNC does not run.

Error type

-

 

110489

Invalid value for parameter edge_bending_input_number corrected.

 

Description

The axis was set up as edge bending axis (P-AXIS-00098) and for the number of the drives edge bending input (parameter P-AXIS-00353) an invalid value was assigned.

Reaction

Class

1

Output of a warning, automatic correction of P-AXIS-00353 to 1.

Solution

Class

1

Set P-AXIS-00353 in axis parameter list to a valid value for the drive type (P-AXIS-00020) used. In the drive the according digital input must be set up as probing input.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis (s. P-AXIS-00016).

%2:

Incorrect value [-]

 

%3:

Lower limit value [-]

 

%4:

Upper limit value [-]

 

%5:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110490

Reciprocal of filter bandwidth below minimum.

 

Description

The reciprocal bandwidth P-AXIS-00080 of the given axis filter is too low. The reciprocal filter bandwidth is used width band-stop and band-pass filters.

Reaction

Class

1

Correction of reciprocal filter bandwidth P-AXIS-00080 value 1.

Solution

Class

1

Increase the reciprocal bandwidth P-AXIS-00080 of the filter.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Actual value [-]

Number of affected filters

%3:

Actual value [-]

Invalid reciprocal bandwidth P-AXIS-00080 of the filter.

%4:

Incorrect value [-]

Corrected value for reciprocal filter bandwidth P-AXIS-00080

%5:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

110491

Value of filter time constant invalid.

 

Description

The time constant P-AXIS-00357 of the PT1 axis filter is zero.

Reaction

Class

1

Correction of the time constant P-AXIS-00357 to 10 milliseconds.

Solution

Class

1

Increase the time constant P-AXIS-00357 of the filter.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis s. P-AXIS-00016

%2:

Actual value [-]

Number of affected filters

%3:

Actual value [-]

Type of filter P-AXIS-00204

%4:

Incorrect value [1 µsec]

Invalid value of time constant P-AXIS-00357

%5:

Corrected value [1 µsec]

Corrected value of time constant P-AXIS-00357

Error type

2, Error message by data transfer from parameter list into control device.

 

110496

Position window of axis filter too small.

 

Description

The tolerance window P-AXIS-00351 specified for the axis filters is too small. During reset, axis position request or exact stop the CNC waits for the axis filters to reach the position window (|unfiltered command value – filtered command value| < P-AXIS-00351). Due to the limited computational accuracy the tolerance window may not be specified arbitrarily small.

Reaction

Class

1

Output of a warning, P-AXIS-00351 is automatically corrected.

Solution

Class

1

Correct value in parameter list

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis

%2:

Incorrect value [0.1 µm or 0,0001°]

Incorrect value for tolerance window P-AXIS-00351

%3:

Lower limit value [0.1 µm or 0,0001°]

Minimum permissible value for tolerance window P-AXIS-00351

%4:

Corrected value [0.1 µm or 0,0001°]

Corrected value of P-AXIS-00351

Error type

2, Error message by data transfer from parameter list into control device.

 

110497

Velocity monitoring: factor for warning greater than for error.

Description

Tolerance factor for excessive velocity warning is set higher than for an error.

Response

Class

1

Value for warning is set to value for error. If velocity limit is exceeded, no warning is generated before an error occurs

Solution

Class

1

Set smaller value.

Parameter

%1

Logical axis number [-]

 

%2

Current value [0.1%]

 

%3

Limit value [0.1%]

 

%4

Corrected value [0.1%]

 

Error type

2, Error message on data transfer of parameter lists to controller.

110498

Acceleration monitoring: factor for warning greater than for error.

Description

Tolerance factor for excessive acceleration warning is set higher than for an error.

Response

Class

1

Value for warning is set to value for error. If acceleration limit is exceeded, no warning is generated before an error occurs

Solution

Class

1

Set smaller value.

Parameter

%1

Logical axis number [-]

 

%2

Current value [0.1%]

 

%3

Limit value [0.1%]

 

%4

Corrected value [0.1%]

 

Error type

2, Error message on data transfer of parameter lists to controller.

110499

Jerk monitoring: factor for warning greater than for error.

Description

Tolerance factor for excessive jerk warning is set higher than for an error.

Response

Class

1

Value for warning is set to value for error. If jerk limit is exceeded, no warning is issued before an error occurs.

Solution

Class

1

Set smaller value.

Parameter

%1

Logical axis number [-]

 

%2

Current value [0.1%]

 

%3

Limit value [0.1%]

 

%4

Corrected value [0.1%]

 

Error type

2, Error message on data transfer of parameter lists to controller.