ID-range 50500-50749

50500

Maximum permissible number of PLC spindle links exceeded

 

Description

The number of active links of PLC spindles with synchronous mode is limited (#SET AX LINK, #ENABLE AX LINK).

Further information to synchronous mode see .

Reaction

Class

6

Movement stop of axis.

Solution

Class

6

Check setting in channel machine parameters (P-CHAN-00037, P-CHAN-00038) or check number of programmed spindle links in #SET AX LINK command.

Parameter

%1:

Limit value [-]

Maximum number of links of PLC spindles.

%2:

Actual value [-]

Current defined number of links of PLC spindles.

%3:

Logical axis number [-]

Logical axis number(P-AXIS-00016)of affected master spindle axis.

%4:

Logical axis number [-]

Logical axis number(P-AXIS-00016)of slave axis which is linked to master axis and which leads to exceeding of maximum link number.

Error type

1, Error message from NC-program.

 

50501 / 50502

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

6

 

Solution

Class

8

Restart of NC-control necessary.

50503

Before deactivation of trafo tool geometry compensation has to be disabled.

 

Description

Before deselection of transformation with #TRAFO OFF while tool geometry compensation (TGC) is active TGC must be deactivate with #TGC OFF.

Reaction

Class

6

 

Solution

Class

6

Modification of NC program.

Error type

1, Error message from NC-program.

 

50504

Before deactivation of transformation.manual mode has to be disabled.

 

Description

Before deselection of active transformation (#CS ON, #TRAFO ON) and manual operation with parallel interpolation (G201) deactivation of manual mode via G202 is required.

Program example

wrong:

N10 #TRAFO ON
N20 G201
N30 G02 I200 F2000
N40 M30 #TRAFO OFF

correct:

N10 #TRAFO ON
N20 G201
N30 G02 I200 F2000
N40 G202
N50 M30 #TRAFO OFF

Reaction

Class

6

Movement stop of axes.

Solution

Class

6

Deselection of manual operation via G202 before command #CS OFF, #TRAFO OFF

Error type

1, Error message from NC-program.

 

50505

Deviation of orthogonal ori vector to path tangent vector exceeds limit.

 

Description

The deviation of the programmed orientation vector of the tool to the orthogonal to tangent vector of path exceeds limit.

Reaction

Class

6

 

Solution

Class

6

Modification of the orientation vector of tool in the NC program.

Parameter

%1:

Incorrect value [0.1 µm or 0,0001°]

Deviation of the orientation vector to the orthogonal to path tangent.

%2:

Lower limit value [0.1 µm or 0,0001°]

Maximal permitted deviation.

Error type

1, Error message from NC-program.

 

50506

Invalid orientation vector.

 

Description

The programmed orientation vector is invalid.

Error example: u=0 v=0 w=0

Corrected example: u=0 v=0 w=1

Reaction

Class

6

 

Solution

Class

6

Modification of orientation vector in NC program.

Error type

1, Error message from NC-program.

 

50507

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

6

 

Solution

Class

8

Restart of NC-control necessary.

50508

Torque homing: Reference position not detected.

 

Description

Homing can be done with different variants parameterized via machine data setting.

The torque homing process was terminated because of missing following error limit signal or torque limit signal.

Reaction

Class

6

Movement stop of axis.

Solution

Class

6

Check homing process, if necessary adjust parameter 2

Parameter

%1:

Logical axis number [-]

Logical axis number (P-AXIS-00016) of affected axis

%2:

Actual value [-]

Name of parameter

%3:

Limit value [0.1 µm or 0,0001°]

Path for torque homing

Error type

1, Error message from NC-program.

 

50509 / 50511

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

4

 

Solution

Class

8

Restart of NC-control necessary.

50512

Transition impossible, because of active position offset

 

Description

For activation of backward movement there is no position offset caused by additional manual mode movement or block search allowed.

Further information: Backward movement see [FCT-C7, Forward And Backward On Path].

Block Search see [FCT-C6].

Reaction

Class

4

Program execution stop.

Solution

Class

6

No position offset should be active before activation of backward movement. Position offset is cleared by CNC reset or restart of program.

Error type

-

 

50513

Position offset is still active

 

Description

After activation of backward movement restriction for position shift must be taken into consideration. There is no position offset caused by additional manual mode movement or block search mode allowed.

If additional offset is generated by manual mode while backward movement and movement is done until program start is reached or if selection of kinematic or cartesian transformation caused by commands #CS ON[], #TRAFO ON is done backward movement is stopped with error.

Further information: Backward movement see [FCT-C7]

Block search see [FCT-C6]

Transformation see [PROG],.

Reaction

Class

6

Program execution stop.

Solution

Class

6

No position offset should be active before activation of backward movement and no position offset should be generated while backward movement. Position offset is cleared by CNC reset or restart of program.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis.

%2:

Actual value [0.1 µm or 0,0001°]

Current active position offset caused by additional manual mode

%3:

Actual value [0.1 µm or 0,0001°]

Current PCS position offset caused by block search.

Error type

1, Error message from NC-program.

 

50515

Maximal number of unacknowledged SIGNAL exceeds the limit.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Limit value [-]

 

Error type

1, Error message from NC-program.

 

50516

Maximal number of unacknowledged WAIT exceeds the limit.

 

Description

The number of active #SIGNAL,#WAIT synchronizations is limited.

Further information to multi channel synchronization see [PROG].

Reaction

Class

4

Movement stop.

Solution

Class

6

Check NC program and reduce #SIGNAL, #WAIT synchronizations active at the same time.

Parameter

%1:

Actual value [-]

Identifier of signal

%2:

Limit value [-]

Maximum number of active signals

Error type

1, Error message from NC-program.

 

50517

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

4

 

Solution

Class

8

Restart of NC-control necessary.

50519

Cancellation of request without axis registration.

 

Description

This error message (warning) output is done for purpose of diagnosis only. The error message appears in diagnosis protocol.

Reaction

Class

1

None

Solution

Class

1

Diagnosis

Parameter

%1:

Logical axis number [-]

Logical axis number(P-AXIS-00016) of affected axis

Error type

3, Error message from communication.

 

50520 - 50528

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

3

 

Solution

Class

8

Restart of NC-control necessary.

50529

Incorrect parameter setting for touch probing.

 

Description

Different measurement types can be used in combination with probing functionality. These types can be selected via MDS or CNC program. Touch probing measurement type has wrong parameter setting.

Further information about measurement functionality G100 see [FCT-C4], [PROG].

Reaction

Class

4

Movement stop.

Solution

Class

6

Correct measurement type or parameter value 2

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis

%2:

Actual value [-]

Name of machine parameter

%3:

Actual value [-]

Machine parameter value

%4:

Actual value [-]

Selected measurement type

%5:

Actual value [-]

Moved probing axes

Error type

1, Error message from NC-program.

 

50533

Axis jerk exceeds maximum limit (Slope).

 

Description

This error message (warning) output is done depending on environment variable for purpose of diagnosis only. The error message appears in diagnosis protocol.

Reaction

Class

1

None

Solution

Class

1

None

Parameter

%1:

Actual value [-]

Actual jerk factor.

%2:

Limit value [-]

Jerk factor limit value.

Error type

1, Error message from NC-program.

 

50534 - 50539

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

3

 

Solution

Class

8

Restart of NC-control necessary.

50540

Angle of inclination of grinding disc exceeds limit.

 

Description

The angle of inclination of the grinding disc is outside of the permitted range.

The angle of inclination is adjustable via the parameter

grinding_disc_tilt_angle in the tool list for the appropriate tool.

Reaction

Class

3

 

Solution

Class

6

Correction of the parameter grinding_disc_tilt_angle in the tool list for the appropriate tool.

Parameter

%1:

Incorrect value [-]

 

%2:

Upper limit value [-]

 

%3:

Lower limit value [-]

 

Error type

-

 

50541

Maximal permissible discrete offset exceeds limit.

 

Description

The discrete offset of an axis via PLC exceeds the permitted range.

Reaction

Class

1

 

Solution

Class

1

Reduce the discrete offset of the axis via PLC.

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Lower limit value [-]

 

%4:

Upper limit value [-]

 

%5:

Corrected value [-]

 

Error type

1, Error message from NC-program.

 

50542

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

3

 

Solution

Class

8

Restart of NC-control necessary.

50543

Maximal permissible discrete radius offset exceeds limit.

 

Description

The discrete offset of the radius offset via PLC exceeds the permitted range.

Reaction

Class

1

 

Solution

Class

1

Reduce the discrete radius offset

Parameter

%1:

Incorrect value [Increment/0.1µm]

 

%2:

Lower limit value [-]

 

%3:

Upper limit value [-]

 

%4:

Corrected value [-]

 

Error type

1, Error message from NC-program.

 

50544

Axis velocity exceeds maximum limit.

 

Description

This error message (warning) output is done depending on environment variable for purpose of diagnosis only. The error message appears in diagnosis protocol.

Reaction

Class

4

Movement stop of axes.

Solution

Class

1

Diagnosis.

Parameter

%1:

Limit value [1µm/sec or 0,001°/sec]

Maximum permissible path velocity.

%2:

Actual value [1µm/sec or 0,001°/sec]

Actual path velocity.

Error type

1, Error message from NC-program.

 

50545

Axis acceleration exceeds maximum limit.

 

Description

This error message (warning) output is done depending on environment variable for purpose of diagnosis only. The error message appears in diagnosis protocol.

Reaction

Class

4

Movement stop of axes.

Solution

Class

1

Diagnosis

Parameter

%1:

Limit value [1mm/sec^2 or 1°/sec^2]

Lower limit of path acceleration

%2:

Limit value [1mm/sec^2 or 1°/sec^2]

Upper limit of path acceleration

%3:

Actual value [1mm/sec^2 or 1°/sec^2]

Actual path acceleration

Error type

1, Error message from NC-program.

 

50546 - 50556

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

3

 

Solution

Class

8

Restart of NC-control necessary.

50557

Characteristic filter frequency greater than half of sampling rate.

 

Description

According to the sampling theorem of Shannon, the cut-off frequency can be at the maximum (½*TA = Cycle time of numerical control). The cut-off frequency of the PT1-filter is calculated from the time constant as follows: fc = 1 / (2 * PI * P-AXIS-00357). The cut-off frequency of all other filters are specified directly in the parameter P-AXIS-00067.

Possible solutions:

- Reduce the cut-off frequency P-AXIS-00067. Increase the time constant P-AXIS-00357 for PT1-filters.

- Reduce the cycle time of the numerical control

Reaction

Class

3

Filter is deactivated.

Solution

Class

7

Reduce the cut-off frequency P-AXIS-00067 or increase the time constant P-AXIS-00357

 

%3:

Actual value [-]

Type of filter P-AXIS-00204

%4:

Incorrect value [-]

Actual cut-off frequency P-AXIS-00067 of filter

%5:

Actual value [-]

Sample rate of the numerical control (1 / TA)

Error type

-

 

50558

Filter design with given parameters not possible.

 

Description

Not all filter parameters lead to valid filter coefficients e.g. due to the limited computational accuracy. Possible solutions are:

  • Reduce the filter order P-AXIS-00140
  • Reduce the reciprocal bandwidth P-AXIS-00080 of band-pass and band-stop filters
  • Choose a different filter prototype P-AXIS-00153
  • Increase the ratio of cut-off frequency to sample rate

Reaction

Class

3

Filter is deactivated

Solution

Class

7

Change filter parameters

 

%3:

Actual value [-]

Type of filter P-AXIS-00204

%4:

Actual value [-]

Order of filter P-AXIS-00140

%5:

Actual value [-]

Cut-off frequency P-AXIS-00067 or time constant of P-AXIS-00357 PT1-filter/PT2-filter

Error type

-

 

50559 - 50561

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

6

 

Solution

Class

8

Restart of NC-control necessary.

50562

Drive command could not be written.

 

Description

The number of #DRIVE commands for one axis is limited.

Reaction

Class

6

Movement stop of axis.

Solution

Class

6

Reduce number of #DRIVE commands in NC program

Parameter

%1:

Logical axis number [-]

Logical axis number(P-AXIS-00016) of affected axis

Error type

1, Error message from NC-program.

 

50563

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

3

 

Solution

Class

8

Restart of NC-control necessary.

50564

Stability reserve of designed filter not sufficient.

 

Description

Not all filter parameters lead to a stable filter e.g. due to the limited computational accuracy. Possible solutions are:

  • Reduce the filter order P-AXIS-00140
  • Reduce the reciprocal bandwidth P-AXIS-00080 of band-pass and band-stop filters
  • Choose a different filter prototype P-AXIS-00153
  • Increase the ratio of cut-off frequency to sample rate

Reaction

Class

3

Filter is deactivated

Solution

Class

7

Change filter parameters

 

%3:

Actual value [-]

Type of filter P-AXIS-00204

%4:

Actual value [-]

Order of filter P-AXIS-00140

%5:

Actual value [-]

Cut-off frequency P-AXIS-00067 or time constant of P-AXIS-00357 PT1-filter or PT2-filter

Error type

-

 

50565 / 50566

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

6

 

Solution

Class

8

Restart of NC-control necessary.

50567

Timeout: Axis filter not within tolerance window.

 

Description

During reset, axis position request or exact stop the CNC waits for the axis filter to reach the tolerance window P-AXIS-00351. However, if the filters do not reach the position window within a certain time (e.g. due to an oscillating filter), the filters of the affected axis are temporarily deactivated. They are reactivated after a CNC-reset.

  • Increase tolerance window P-AXIS-00351 of filters
  • Reduce the filter order P-AXIS-00140
  • Reduce the reciprocal bandwidth P-AXIS-00080 of band-pass and band-stop filters
  • Choose a different filter prototype P-AXIS-00153
  • Increase the ratio of cut-off frequency to sample rate

Reaction

Class

6

Filter is temporarily deactivated and reactivated after reset

Solution

Class

7

Change filter parameters or increase tolerance window

Parameter

%1:

Logical axis number [-]

Logical axis number P-AXIS-00016 of affected axis

%2:

Incorrect value [-]

True, if axis filters have reached position window

%3:

Actual value [0.1 µm or 0,0001°]

Unfiltered command value

%4:

Actual value [0.1 µm or 0,0001°]

Filtered command value

%5:

Upper limit value [0.1 µm or 0,0001°]

Tolerance window P-AXIS-00351 for axis filters

Error type

-

 

50568

WCS transformation of display-data impossible.

 

Description

The display of W0 coordinates is selected.

The kinematic transformation is not possible with the current selected kinematic structure. The reason could be an invalid kinematic identifier or wrong parameter setting of the kinematic.

Further information to transformation parameter and W0 display data see[KITRA], [CHAN].

Reaction

Class

1

Deactivation of W0 display function.

Solution

Class

1

Only use valid kinematic identifier and correct transformation parameters.

Parameter

%1:

Actual value [-]

Current selected kinematic ID.

%2:

Actual value [-]

 

Error type

1, Error message from NC-program.

 

50569

WCS transformation with actual axis configuration impossible.

 

Description

The display of W0 coordinates is selected.

The kinematic transformation is not possible with the current selected kinematic structure. An invalid axis configuration with to small number or missing axes is active.

Further information to kinematic transformation and W0 display data see[KITRA], [CHAN].

Reaction

Class

1

Deactivation of W0 display function.

Solution

Class

1

Use correct axis configuration setting.

Parameter

%1:

Actual value [-]

Current selected kinematic identifier.

%2:

Actual value [-]

Axis index of missing axis.

Error type

1, Error message from NC-program.

 

50570

Frames per second no multiple integer of CNC-cycle time.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Incorrect value [-]

 

%2:

Corrected value [-]

 

%3:

Actual value [1 µsec]

 

Error type

-

 

50571

Frames per second can not be smaller than CNC-cycle time.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Incorrect value [-]

 

%2:

Corrected value [-]

 

%3:

Actual value [1 µsec]

 

Error type

-

 

50572

The given neg. offset limit is greater than the positive offset limit.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Lower limit value [0.1 µm or 0,0001°]

 

%3:

Upper limit value [0.1 µm or 0,0001°]

 

%4:

Corrected value [0.1 µm or 0,0001°]

 

Error type

1, Error message from NC-program.

 

50573

Edge banding measurement cycle still active.

 

Description

Termination of measurement cycle or SERCOS command S-0-170 is done implicitly or explicitly with G107 depending on channel parameter setting of P-CHAN-00153.

The current error case results in missing deactivation of measurement function with G107.

Further information to edge banding see [PROG].

Reaction

Class

4

Movement stop.

Solution

Class

6

Correct deactivation of function with G107 before program end M30.

Error type

1, Error message from NC-program.

 

50574 - 50576

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

4

 

Solution

Class

8

Restart of NC-control necessary.

50577

Inadmissible motion block type for the IN synchronization.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Actual value [-]

 

Error type

1, Error message from NC-program.

 

50578 - 50586

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

4

 

Solution

Class

8

Restart of NC-control necessary.

50587

Maximum velocity of synchronous axis too small.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Logical axis number [-]

 

Error type

1, Error message from NC-program.

 

50588

Touch probing in this SAI axis is already active.

 

Description

 

Reaction

Class

6

 

Solution

Class

7

 

Parameter

%1:

Logical axis number [-]

 

Error type

1, Error message from NC-program.

 

50589 / 50590

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

6

 

Solution

Class

8

Restart of NC-control necessary.

50591

Inadmissible motion block type for the OUT synchronization.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Actual value [-]

 

Error type

1, Error message from NC-program.

 

50593

Oscillation feed is zero

 

Description

The programmed feed In functionality oscillation axes is to small.

Further information to oscillation axis see [FCT-A8, Oscillating Axes].

Reaction

Class

5

Movement stop of axes.

Solution

Class

6

Check feed programming, value should be > 0.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis P-AXIS-00016.

%2:

Actual value [1µm/sec or 0,001°/sec]

Programmed feed.

Error type

1, Error message from NC-program.

 

50594

Transformation of current positions not possible.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Actual value [-]

 

%2:

Actual value [-]

 

Error type

1, Error message from NC-program.

 

50595

Trafo for conveyor sync. with axis config. and kin. structure not possible.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Actual value [-]

 

%2:

Actual value [-]

 

Error type

1, Error message from NC-program.

 

50596

Inadmissible slope type by band synchronization.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Expected value [-]

 

Error type

1, Error message from NC-program.

 

50597

Velocity of the conveyor is to small

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Actual value [1µm/sec or 0,001°/sec]

 

%2:

Lower limit value [1µm/sec or 0,001°/sec]

 

Error type

1, Error message from NC-program.

 

50598

Y-axis is synchronized before X-Axis, during #SYNC IN with FEED_CONT > 0.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Logical axis number [-]

 

Error type

1, Error message from NC-program.

 

50599

Act.-/Deactivation of kin. trafo not permissible by active bandsync.

 

Description

 

Reaction

Class

6

 

Solution

Class

6

 

Error type

1, Error message from NC-program.

 

50600

License: to much axes shall move at the same time.

 

Description

 

Reaction

Class

1

 

Solution

Class

7

 

Parameter

%1:

Limit value [-]

 

Error type

-

 

50601

Inadmissible command after Sync. OUT.

 

Description

 

Reaction

Class

6

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Expected value [-]

 

%3:

Actual value [-]

 

%4:

Block number [-]

 

Error type

1, Error message from NC-program.

 

50602

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

4

 

Solution

Class

8

Restart of NC-control necessary.

50603

Inadmissible instruction for independent axis.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

Error type

1, Error message from NC-program.

 

50604

The order of the position filter is greater than the acceptable maximum.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

50605

The order of the position filter is odd numbered.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

50606

Inadmissible type of position filter.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

50607

The order of the velocity filter is greater than the acceptable maximum.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Limit value [-]

 

%4:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

50608

The order of the velocity filter is odd numbered.

 

Description

 

Reaction

Class

1

 

Solution

Class

1

 

Parameter

%1:

Logical axis number [-]

 

%2:

Actual value [-]

 

%3:

Corrected value [-]

 

Error type

2, Error message by data transfer from parameter list into control device.

 

50609

End of motion range in direction of positive software limit switch reached.

 

Description

Positive travel limit of axis parallel to conveyor axis is reached.

The axis which is moving in direction of conveyor axis decelerates to ensure stopping before soft limit in throughput processing. This error should only occur if the conveyor moving direction has positive sign.

There are different possible reasons:

  • The conveyor velocity is to high.
  • The programmed feed in NC program is to small.
  • To many contour elements or description is to extensive (Path travel of Y axis)

..

Reaction

Class

4

Movement stop of axes

Solution

Class

6

Check and correct conveyor speed and NC program

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis (P-AXIS-00016)

%2:

Limit value [0.1 µm or 0,0001°]

Positive limit of travel

%3:

Actual value [0.1 µm or 0,0001°]

Current position including braking distance

%4:

Actual value [0.1 µm or 0,0001°]

PCS 0 position

%5:

Actual value [0.1 µm or 0,0001°]

Braking distance

Error type

1, Error message from NC-program.

 

50610

End of motion range in direction of negative software limit switch reached.

 

Description

Negative travel limit of axis parallel to conveyor axis is reached.

The axis which is moving in direction of conveyor axis decelerates to ensure stopping before soft limit in throughput processing. This error should only occur if the conveyor moving direction has negative sign.

There are different possible reasons:

  • The conveyor velocity is to high
  • The programmed feed in NC program is to small
  • To many contour elements or description is to extensive (Path travel of Y axis)

.

Reaction

Class

4

Movement stop of axes

Solution

Class

6

Check and correct conveyor speed or NC program

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis (P-AXIS-00016)

%2:

Limit value [0.1 µm or 0,0001°]

Negative limit of travel

%3:

Actual value [0.1 µm or 0,0001°]

Current position including braking distance

%4:

Actual value [0.1 µm or 0,0001°]

PCS 0 position

%5:

Actual value [0.1 µm or 0,0001°]

Braking distance

Error type

1, Error message from NC-program.

 

50611

The number of look-ahead blocks are to small.

 

Description

 

Reaction

Class

3

 

Solution

Class

1

 

Parameter

%1:

Actual value [-]

 

%2:

Lower limit value [-]

 

%3:

Corrected value [-]

 

Error type

-

 

50612

The number of look-ahead blocks are to large.

 

Description

 

Reaction

Class

3

 

Solution

Class

1

 

Parameter

%1:

Actual value [-]

 

%2:

Upper limit value [-]

 

%3:

Corrected value [-]

 

Error type

-

 

50613

Axis can't reach the moving pcs-origin.

 

Description

 

Reaction

Class

-

 

Solution

Class

-

 

Error type

-

 

50614 / 50615

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

6

 

Solution

Class

8

Restart of NC-control necessary.

50616

The velocity of the conveyor belt exceeds the axis' G0-feedrate.

 

Description

 

Reaction

Class

-

 

Solution

Class

-

 

Parameter

%1:

Actual value [1µm/sec or 0,001°/sec]

 

%2:

Upper limit value [1µm/sec or 0,001°/sec]

 

Error type

-

 

50618

Axis exceeds its range during Sync-Out or Sync-Stop.

 

Description

 

Reaction

Class

-

 

Solution

Class

-

 

Error type

-

 

50619

The velocity of the conveyor belt exceeds the axis' maximum feed rate.

 

Description

 

Reaction

Class

-

 

Solution

Class

-

 

Error type

-

 

50620 - 50624

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

4

 

Solution

Class

8

Restart of NC-control necessary.

50625

Axis exchange during "suppress psi" not allowed.

 

Description

 

Reaction

Class

6

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Actual value [-]

 

%3:

Actual value [-]

 

Error type

1, Error message from NC-program.

 

50626

Gear change during "suppress psi" not allowed.

 

Description

 

Reaction

Class

6

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

%2:

Expected value [-]

 

Error type

1, Error message from NC-program.

 

50627

Coupling on a conveyor is active at program end.

 

Description

 

Reaction

Class

2

 

Solution

Class

6

 

Error type

1, Error message from NC-program.

 

50629

Axes are controlled by single ax IPO.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

Error type

1, Error message from NC-program.

 

50630

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

6

 

Solution

Class

8

Restart of NC-control necessary.

50631

Moved axis is not at the position before the retraction.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Logical axis number [-]

 

Error type

1, Error message from NC-program.

 

50632

Error occurred in single axis.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Logical axis number [-]

 

Error type

-

 

50633

Sync IN/OUT is interrupted by single axis movement.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Logical axis number [-]

 

Error type

-

 

50634

Sync-IN/OUT commanded during error.

 

Description

 

Reaction

Class

6

 

Solution

Class

6

 

Parameter

%1:

Actual value [-]

 

Error type

1, Error message from NC-program.

 

50635

Forced error during SYNC IN.

 

Description

 

Reaction

Class

6

 

Solution

Class

6

 

Parameter

%1:

Logical axis number [-]

 

Error type

1, Error message from NC-program.

 

50636

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

6

 

Solution

Class

8

Restart of NC-control necessary.

50637

Changing measuring parameters only allowed for measuring axes.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Actual value [-]

 

%4:

Actual value [-]

 

%5:

Actual value [-]

 

Error type

1, Error message from NC-program.

 

50638

Drive type does not support selected measuring signal input.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Logical axis number [-]

 

%2:

Drive type [-]

 

%3:

Incorrect value [-]

 

Error type

1, Error message from NC-program.

 

50639

Selected measuring input of drive is invalid.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Logical axis number [-]

 

%2:

Drive type [-]

 

%3:

Incorrect value [-]

 

%4:

Upper limit value [-]

 

Error type

1, Error message from NC-program.

 

50640

Edge banding cannot be activated since function not selected in axis parameters.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Logical axis number [-]

 

%2:

Incorrect value [-]

 

%3:

Actual value [-]

 

Error type

1, Error message from NC-program.

 

50641

Adoption of new measuring parameters not possible during active measurement.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Error type

1, Error message from NC-program.

 

50642

Maximum number of timers for conveyor synchronization exceeded.

 

Description

 

Reaction

Class

4

 

Solution

Class

6

 

Parameter

%1:

Limit value [-]

 

Error type

1, Error message from NC-program.

 

50643

Positive soft limit exceeded with automatic repositioning in block search.

 

Description

Additional check of axes positions is done with block search repositioning movement. Particularly in combination with active kinematic transformation, because of necessary compensation movement it can occur that the repositioning movement leads to exceeding of soft limits.

Reaction

Class

6

Movement stop.

Solution

Class

6

Move axis more into valid range.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis P-AXIS-00016.

%2:

Actual value [0.1 µm or 0,0001°]

Current active command position.

%3:

Lower limit value [0.1 µm or 0,0001°]

Negative software limit switch P-AXIS-00177.

Error type

1, Error message from NC-program.

 

50644

Negative soft limit exceeded with automatic repositioning in block search.

 

Description

Additional check of axes positions is done with block search repositioning movement. Particularly in combination with active kinematic transformation, because of necessary compensation movements it can occur that the repositioning movement leads to exceeding of soft limits.

Reaction

Class

6

Movement stop.

Solution

Class

6

Move axis more into valid range.

Parameter

%1:

Logical axis number [-]

Logical axis number of affected axis P-AXIS-00016.

%2:

Actual value [0.1 µm or 0,0001°]

Current active command position.

%3:

Upper limit value [0.1 µm or 0,0001°]

Positive software limit switch P-AXIS-00178.

Error type

1, Error message from NC-program.

 

50645 - 50647

Troubleshooting classes

 

Description

This error message informs about internal states, error solutions and the place of error in the source. Please give the complete error message data to the CNC manufacturer.

Reaction

Class

6

 

Solution

Class

8

Restart of NC-control necessary.