Synchronization type of H-functions (P-CHAN-00027)
In the array "h_synch[i]", the synchronization type of the corresponding H-function is defined. Here, the field index "i" defines the number of the H-function. The value states the synchronization type of the H-function, this means the time for the check of the existence of a PLC-acknowledgement. A motion is not executed or stopped at block end, if at the time for the check from PLC no acknowledgement is received.
Variable name | Type | Permitted range | Dimension |
|---|---|---|---|
h_synch[i] | SYNCHRO_ART | NO_SYNCH, MOS, MVS_SVS, MVS_SNS, MNS_SNS, MNE_SNS, MEP_SVS, MET_SVS, BWD_SYNCH, FWD_SYNCH, FAW_SYNCH | ---- |
i | UNS16 | 0 ... [H_FKT_ANZ-1] | ---- |
Value H_FKT_ANZ | Significance | ||
application-dependent | Maximum number of H-functions | ||
Constant | Value | Significance |
|---|---|---|
NO_SYNCH | 0x00000000 | No output of H-function to PLC |
MOS | 0x00000001 | Output of H-function to PLC without synchronization |
MVS_SVS | 0x00000002 | Output of H-function to PLC before the motion block, |
MVS_SNS | 0x00000004 | Output of H-function to PLC before the motion block, |
MNS_SNS | 0x00000008 | Output of H-function to PLC after the motion block, |
MNE_SNS | 0x00000020 | Output of H-function to PLC after (measurement-)signal, |
BWD_SYNCH | 0x00400000 | Synchronization of H-function during backward on path as MVS_SVS |
FWD_SYNCH | 0x00800000 | Synchronization of H-function during "Simulated forward on path" based on the defined synchronization type |
MEP_SVS | 0x01000000 | Output of H-function before specified path, synchronization before next block |
MET_SVS | 0x02000000 | Output of H-function before specified time, synchronization before next block |
FAW_SYNCH | 0x10000000 | Stop of decoding (Flush and Wait): Output of H-function to PLC and stop of program decoding at block end until all NC blocks in NC-channel were executed. FAW_SYNCH can be set in addition to other synchronization types. H-functions with FAW_SYNCH may not be used during active tool radius correction (WRK), polynomial contouring and HSC-mode. |
Examples see chapter 2.1.1.1 - Synchronization types of M-functions.