E_BACNETSERVICESSUPPORTEDBITS

Bit assignment of the Protocol Services Supported flags (property Protocol_Services_Supported).

TYPE E_BACNETSERVICESSUPPORTEDBITS :
(
  BACnetServicesSupportedBits_AcknowledgeAlarm              := 0,
  BACnetServicesSupportedBits_ConfirmedCOVNotification      := 1,
  BACnetServicesSupportedBits_ConfirmedEventNotification    := 2,
  BACnetServicesSupportedBits_GetAlarmSummary               := 3,
  BACnetServicesSupportedBits_GetEnrollmentSummary          := 4,
  BACnetServicesSupportedBits_SubscribeCOV                  := 5,
  BACnetServicesSupportedBits_AtomicReadFile                := 6,
  BACnetServicesSupportedBits_AtomicWriteFile               := 7,
  BACnetServicesSupportedBits_AddListElement                := 8,
  BACnetServicesSupportedBits_RemoveListElement             := 9,
  BACnetServicesSupportedBits_CreateObject                  := 10,
  BACnetServicesSupportedBits_DeleteObject                  := 11,
  BACnetServicesSupportedBits_ReadProperty                  := 12,
  BACnetServicesSupportedBits_ReadPropertyConditional       := 13,
  BACnetServicesSupportedBits_ReadPropertyMultiple          := 14,
  BACnetServicesSupportedBits_WriteProperty                 := 15,
  BACnetServicesSupportedBits_WritePropertyMultiple         := 16,
  BACnetServicesSupportedBits_DeviceCommunicationControl    := 17,
  BACnetServicesSupportedBits_ConfirmedPrivateTransfer      := 18,
  BACnetServicesSupportedBits_ConfirmedTextMessage          := 19,
  BACnetServicesSupportedBits_ReinitializeDevice            := 20,
  BACnetServicesSupportedBits_VtOpen                        := 21,
  BACnetServicesSupportedBits_VtClose                       := 22,
  BACnetServicesSupportedBits_VtData                        := 23,
  BACnetServicesSupportedBits_Authenticate                  := 24,
  BACnetServicesSupportedBits_RequestKey                    := 25,
  BACnetServicesSupportedBits_IAm                           := 26,
  BACnetServicesSupportedBits_IHave                         := 27,
  BACnetServicesSupportedBits_UnconfirmedCOVNotification    := 28,
  BACnetServicesSupportedBits_UnconfirmedEventNotification  := 29,
  BACnetServicesSupportedBits_UnconfirmedPrivateTransfer    := 30,
  BACnetServicesSupportedBits_UnconfirmedTextMessage        := 31,
  BACnetServicesSupportedBits_TimeSynchronization           := 32,
  BACnetServicesSupportedBits_WhoHas                        := 33,
  BACnetServicesSupportedBits_WhoIs                         := 34,
  BACnetServicesSupportedBits_ReadRange                     := 35,
  BACnetServicesSupportedBits_UtcTimeSynchronization        := 36,
  BACnetServicesSupportedBits_LifeSafetyOperation           := 37,
  BACnetServicesSupportedBits_SubscribeCOVProperty          := 38,
  BACnetServicesSupportedBits_GetEventInformation           := 39
)
END_TYPE