FB_BACnetSchedBinPV
BACnet scheduler of the type Binary Present Value with the function "predictive switch-on and switch-off time".
Functional description
This function block generates a BACnet scheduler object and provides write and read variables for the object within the PLC. The output type of the object is BOOL.
The object is parameterized either from BACnet or via comment lines in the PLC declaration part.
Inputs/outputs
VAR_INPUT
udiPredictTime : UDINT;
udiPredictTime: predicted switch-on and switch-off time in seconds. The time value specified here switches the output bPredictedVal on or off in advance, depending on the timer channels of the BACnet property WeeklySchedule.
VAR_OUTPUT
bPrVal : BOOL;
bPredictedVal : BOOL;
bErr : BOOL;
udiErrId : UDINT;
udiErrArg : UDINT;
bPrVal: Output value of the schedule depending on the currently selected date/time and the schedule entries.
bPredictedVal: output that is switched depending on the switch-on and switch-off time udiPredictTime and the BACnet property WeeklySchedule.
bErr: Indicates a general error in the function block. The cause can be in BACnet, in the ADS data exchange, or due to incorrect parameterization.
udiErrId / udiErrArg: Contains the error number and the error argument. See Error codes.
VAR_IN_OUT
fbDvc : FB_BACnet_Device;
fbDvc: reference to the function block of the BACnet device object
Requirements
Development environment | Target system | required library | required supplement |
|---|---|---|---|
TwinCAT 2.11 R3/x64 | PC/CX | TcBA library from V1.0.0 | TS8040 | TwinCAT Building Automation from V1.0.0 |