Commissioning
| |
Open transformer circuits lead to electric shock and arc flashover! Disregarding this will result in death, physical injury or considerable damage to property!
|
| |
Hazardous voltage can lead to electric shock and burns!
|
| |
Induction of high voltages into the secondary circuit!
|
- Interrupt the power supply of the primary conductor and secure against being switched on again inadvertently.
- Install the current transformer on the primary conductor.
- To do this, feed the primary conductor (round conductor) through the window aperture of the current transformer housing. The window aperture is marked with "P1" and "P2".
- Make the secondary connections.
- Observe the markings "S1" and "S2" of the secondary terminals
Notice | |
Observe the conductor cross-sections and lengths! The conductor cross-sections and lengths specified below must be adhered to for trouble-free function! |
Conductor cross-section | Power loss |
|---|---|
0.5 | 0.070 |
0.75 | 0.047 |
1.0 | 0.035 |
1.5 | 0.023 |
Measuring circuit

Assembly notes
- To fasten the device to a mounting plate, use the optionally available snap-on mounting (ZB8201-0110) for DIN rails.
- This can be fastened to the mounting plate with two screws, max. Ø 5 mm.
- Fastening to a 35 mm DIN rail also takes place with the help of the optionally available snap-on mounting ZB8201-0110
- Check whether the current transformer is mounted correctly and the secondary conductors are connected correctly.
- Switch on the power supply to the primary conductor again.

