Front side and operating elements
Input terminals (screw terminals)
Designation (A) | Description |
---|---|
+ | Line input + |
- | Line input - |
N/C | Not connected |
Earth input |
Output terminals (screw terminals)
Designation (B) | Description |
---|---|
+ | 2 identical positive poles, positive output |
- | 2 identical negative poles, negative output |
Output voltage potentiometer
Designation (C) | Description |
---|---|
Potentiometer cover | Multi turn potentiometer; |
DC-OK / Overload LED
Designation (D) | Description |
---|---|
DC-OK LED (green) | • On: |
Overload LED (red) | • On: • Flashing: |
“Parallel Use” / “Single Use” selector
Designation (E) | Description |
---|---|
Jumper | Set jumper to “Parallel Use” when power supplies are connected in parallel to increase the output power. |
DC-OK relay / Shut down contact
Designation (F) | Description |
---|---|
Push-in terminals | The DC-OK relay contact is synchronized with the DC-OK LED. |
Push-in terminals | Allows the power supply to be shut down. Can be activated with a switch contact or an external voltage. |
LEDs
Indicators/LEDs | Overload LED | DC-OK LED | DC-OK contact |
---|---|---|---|
Normal mode | OFF | ON | Closed |
During Extra Power | OFF | ON | Closed |
Overload (Vout < 90%) | ON | OFF | Open |
Output short circuit | ON | OFF | Open |
Temperature Shut-down | flashing | OFF | Open |
Active Shut-down input | flashing | OFF | Open |
No input power | OFF | OFF | Open |