Output

The output provides an SELV/PELV nominal voltage that is electrically isolated from the input voltage.

The output is electronically protected against overload, no-load and short circuit. In the event of a protection event, audible noises may occur.

The output is designed to supply any type of load, including capacitive and inductive loads.

Output

Output voltage

Nom.

24 V

 

Adjustment range

Min.

24 - 28 V

Guaranteed value

Max.

30.0 V

This is the maximum output voltage that can occur in the end position of the potentiometer in clockwise direction due to tolerances. It is not a guaranteed value that can be achieved.

Factory settings

Typ.

24.1 V

±0.2%, at full load and with the device cold

Line regulation

Max.

10 mV

Between 85 Vac and 300 Vac

Load regulation

Max.

100 mV

Between 0 A and 10 A, statistical value, see fig. Output voltage over output current

Residual ripple and ripple voltage

Max.

50 mVSS

Bandwidth 20 Hz to 20 MHz, 50 ohm

Output current -
continuous2)

Nom.

10 A

At 24 V and 60 °C ambient temperature

Nom.

7.5 A

At 24 V and 70 °C ambient temperature

Nom.

9.0 A

At 28 V and 60 °C ambient temperature

Nom.

6.8 A

At 28 V and 70 °C ambient temperature

Output current -
Extra Power up to 4 s1)

Nom.

15 A

At 24 V and 70 °C ambient temperature

Nom.

13.5 A

At 28 V and 70 °C ambient temperature

Output power -
continuous

Nom.

240 W

 

Output power -
Extra Power 4 s1)

Nom.

360 W

 

Extra Power time
(bonus time)

Typ.

4 s

Time until the output voltage drops, see Fig. Bonus time over output power

Recovery time

Typ.

7 s

Overload-free time until the power manager is reset, see Fig. Extra Power recovery time

Overload behavior

 

Continuous current

 

Short circuit current

Max.

12.5 A

Continuous current, load impedance 100 mOhm

Max.

15 A

Continuous current, load impedance 10 mOhm

Max.

21 A

During Extra Power recovery time, load impedance 100 mOhm,

Output capacity

Typ.

7,000 μF

Included in the power supply

Load feedback

Max.

35 V

The device is resistant and does not show any malfunction when a load feeds back voltage to the power supply. It does not matter whether the power supply is switched on or off. The absorbed energy can be calculated by means of the built-in large-size output capacitor.

1) Extra Power
The power supply is designed to support loads with higher short-term power requirements without damage or shutdown.
The short-time duration/bonus time is controlled in hardware by an output power manager.
Extra Power is available repeatedly. Detailed information can be found in the chapter on Repeated pulse load.
If the power supply is loaded with Extra Power for longer than in the bonus time diagram (see fig. Output voltage over output current, typ.; bonus time over output power), the output current is automatically reduced to the continuous output current.

2) Linear derating between +60 °C and 70 °C ambient temperature

Peak current capability (up to several milliseconds)

The power supply can deliver a peak current that is higher than the specified short-term current. This helps to start current-intensive loads or safely operate downstream circuit breakers.

The additional current is supplied by the built-in output capacitors of the power supply. During this process the capacitors are discharged and cause a voltage drop at the output. Further information can be found in the chapter on Peak current capability.

Voltage drops at peak currents

Typ. 24 V to 20.5 V

At 20 A for 50 ms, ohmic load

Typ. 24 V to 18 V

At 50 A for 2 ms, ohmic load

Typ. 24 V to 14 V

At 50 A for 5 ms, ohmic load

Output 1:Fig.5: Output voltage over output current, typ.; bonus time over output power
Output 2:Fig.6: Extra Power recovery time

Extra Power is available as soon as the power is turned on and after an output short-circuit or output overload.

Output 3:Fig.7: Extra Power after switching on; Extra Power after short circuit or overload