Input data
Index 6000 PSU Inputs
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
6000:0 | PSU Inputs |
| UINT8 | RO | 0x16 (22dec) |
6000:01 | Warning | Is set if one of the following conditions applies:
| BOOLEAN | RO | 0x00 (0dec) |
6000:02 | Error | Becomes TRUE and results in the output voltage being switched off if one of the following conditions applies:
| BOOLEAN | RO | 0x00 (0dec) |
6000:04 | DC OK | The output voltage (0x6000:11) falls below the DC OK threshold (0x8000:16) | BOOLEAN | RO | 0x00 (0dec) |
6000:11 | Output voltage | Current output voltage in V | REAL32 | RO | 0x00000000 (0dec) |
6000:12 | Output current | Current output current in A | REAL32 | RO | 0x00000000 (0dec) |
6000:15 | Info data 1 | Synchronous information (selection via subindex 0x8001:19) | UINT16 | RO | 0x0000 (0dec) |
6000:16 | Info data 2 | Synchronous information (selection via subindex 0x8001:21) | UINT16 | RO | 0x0000 (0dec) |
Index F614 PSU Inputs
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
F614:0 | PSU Inputs |
| UINT8 | RO | 0x03 (3dec) |
F614:03 | Input undervoltage | The input voltage "Actual RMS input voltage" (0xFA14:19) falls below the minimum value of the nominal input voltage. | BOOLEAN | RO | 0x00 (0dec) |