IO-Link - Basics
IO-Link represents a communication system for the connection of intelligent sensors and actuators to an automation system in the IEC 61131-9 standard under the designation "Single-drop digital communication interface for small sensors and actuators" (SDCI).
Both the electrical connection data and the communication protocol are standardized and summarized in the IO-Link Spec.
![]() | IO-Link specification The development of the EL6224 was subject to the IO-Link specification 1.1. At the time of the preparation of this documentation, the IO-Link specification is entering the IEC standardization and will be adopted in extended form as IEC 61131-9. The new designation SDCI will be introduced at the same time. |
An IO-Link system consists of an IO-Link master and one or more IO-Link devices, i.e. sensors or actuators. The IO-Link master provides the interface to the higher-level controller and controls communication with the connected IO-Link devices. The Beckhoff EL6224 IO-Link Master Terminal has four IO-Link ports. One IO-Link device can be connected to each of them. Therefore, IO-Link is not a fieldbus, but a peer-to-peer connection (see Fig. Peer-to-peer communication IO-Link).

The connected IO-Link devices have individual parameter information in the form of an IO device description (IODD), which is set with the KS2000 configuration software (see chapter KS2000 - Settings).
Parameter data exchange
An intelligent IO-Link device can support parameterization through SPDUs (service protocol data units). The PLC must explicitly query or, when marked as such, send these acyclic service data.
![]() | SPDU access TwinCAT currently only supports access via ADS. |
The so-called SPDU index is used to address the corresponding parameter. The following ranges are available.
Index range | Name |
|---|---|
0x00...0x0F | System |
0x10...0x1F | Identification |
0x20...0x2F | Diagnostic |
0x30...0x3F | Communication |
0x40...0xFE | Preferred Index |
0x0100...0x3FFF | Extended Index |
0x4000...0xFFFF | not specified (reserved) |
The use and implementation of these ranges is the responsibility of the sensor/actuator manufacturer.
For clarification, just a few of the possible indices are listed here; refer to the documentation for the IO-Link device used.
Index | Name |
|---|---|
0x0010 | Vendor Name |
0x0011 | Vendor Text |
0x0012 | Product Name |
0x0013 | Product ID |
0x0015 | Serial Number |
0x0016 | Hardware Revision |
0x0017 | Firmware Revision |
... | ... |
