Basic function principles

The thermocouple terminals can evaluate thermocouples of the types B, E, J, K, L, N, R, S, T and U. The characteristic curves are linearized and the reference temperature determined directly within the terminal. Temperatures are output in 1/10°C, for example (device-dependent). The terminal is fully configurable via the Bus Coupler or the control system. Different output formats may be selected or own scaling activated. In addition, linearization of the characteristic curve and determination and calculation of the reference temperature (temperature at the terminal connection contacts) can be switched off.

Measuring principle of the thermocouple

Thermocouples can be classified as active transducers. They exploit the thermo-electric effect (Seebeck, Peltier, Thomson). A voltage referred to as thermovoltage occurs over the length of a cable with different temperatures at both ends. It is an unambiguous function of the temperature and the material. In a “TC element” this effect is utilized by operating two different conductor materials in parallel (s. fig.)

Basic function principles 1:
Principle of the thermocouple

Example:

In the following example, the voltage Uth is given which is present at a type-K thermocouple at the temperature Tm.

Uth = (kNiCr - kNi) x ΔT

with

ΔT = Tm - Tv

A type-K thermocouple consists of a junction of a nickel-chrome alloy and nickel, where kNiCr and kNi represent the thermoelectric coefficients of nickel-chrome and nickel respectively. By adapting the equation according to Tm, the sought-after temperature can be calculated from the voltage measured across the thermocouple. Based on the difference to the cold junction temperature, the temperature at the measurement point can be determined to an accuracy of better than one tenth of a Kelvin with the aid of the above thermocouple equation.

Basic function principles 2:

Sensor circuit

A modification of the sensor circuit with additional devices such as change over switches or multiplexer decreases the measure accuracy. We strongly advise against such modifications.

Internal conversion of the thermovoltage and the reference voltage

Since the coefficients are determined at a reference temperature of 0°C, it is necessary to compensate for the effect of the reference temperature. This is done by converting the reference temperature into a reference voltage that depends on the type of thermocouple, and adding this to the measured thermovoltage. The temperature is found from the resulting voltage and the corresponding characteristic curve.

Uk = Um+ Ur

Tout = f(Uk)

The four LEDs indicate the operating state of the associated terminal channels.

Process data output format

In the delivery state, the measured value is displayed in increments of 1/10 °C in two's complement format (integer). Other presentation types can be selected via the feature register (R32) (e.g. signed amount representation, Siemens output format).

Measured value

Output

Hexadecimal output

Signed integer output

-200.0 °C

0xF830

-2000

100.0°C

0xFC18

-1000

0.1°C

0xFFFF

-1

0.0°C

0x0000

0

0.1°C

0x0001

1

100.0°C

0x03E8

1000

200.0°C

0x07D0

2000

500.0°C

0x1388

5000

850.0°C

0x2134

8500

1,000.0°C

0x2710

10000

Voltage limits

For overrange or underrange the red error LED is switched on.

Calculation of process data

The process data that are transferred to the Bus Coupler are calculated using the following equations:

Tref = A00 * X_ref

Uref = a1 * Tref2 + b1 * Tref + c1

(1.0)

(1.1)

Voltage value of the cold junction

Um1 = A_a * X_ X_m + B_a

Uk = Uref + Um1

T = a0 * Uk2 + b0 * Uk + c0

(1.2)

(1.3)

(1.4)

Measured temperature in 1/16°C

 

Tout = T

(1.5)

Neither user nor manufacturer scaling is active

Th = A_h * T + B_h

Tout = Th

(1.6)

Manufacturer scaling active (factory setting)

Ta = A_w * T + B_w

Tout = Ta

(1.7)

User scaling active

Th = A_h * T + B_h

Ta = A_w * T + B_w

Tout = Ta

(1.7)

Manufacturer and user scaling active

Key

Name

Name

Register

X_ref

Output value of the A/D converter

 

Tref

Temperature of the cold junction

 

Uref

Voltage value of the cold junction

 

X_m

ADC value of the temperature sensor

 

Um1

Voltage value of the temperature sensor

 

A_a

Vendor calibration: Gain

R17

B_a

Vendor calibration: Offset

R18

A_h

Manufacturer scaling: Gain

R20

B_h

Manufacturer scaling: Offset

R19

A_w

User scaling: Gain

R34

B_w

User scaling: Offset

R33

Uk

Sum of Uref and Um1

 

T

Measured temperature in 1/16°C

 

Th

Temperature after vendor scaling (1/10 °C)

 

Ta

Temperature after user scaling

 

Tout

Process data to PLC

 

The equations of the straight line are enabled via register R32

Basic function principles 3:
Data Flow