Settings
The dialog mask for the parameterization of the KL2692 can be found under Settings.

Watchdog time (R35)
This can be used for setting the watchdog time (default: 4 ms). Within the watchdog time, an edge change must occur on the toggle bit of the control bytes (CB.0), in order to prevent the drop-out of the output relays.
Minimum switch-off time (R36)
This can be used for setting the minimum time (default: 50 ms) for which the relays remain switched off after the watchdog has been triggered, even if, after a subsequent monitoring activation, the following pulse sequence is recognized as correct.