KL2541 - LED Displays

KL2541 - LED Displays 1:
KL2541 - LED

Left LED prism

LED

Display

Run (green)

on

Data transmission on the K-bus is active

A (green)

on

A signal is present at encoder input A.

C (green)

on

A signal is present at encoder input C.

Input 1 (green)

on

A signal is present at digital input E1.

-

reserved

B (green)

on

A signal is present at encoder input B.

Latch (green)

on

A signal is present at the latch input of the encoder.

Input 2 (green)

on

A signal is present at digital input E2.

Right LED prism

LED

Display

-

reserved

Turn CW (green)

on

Motor turns clockwise

Enable (green)

off

Motor control is disabled (bit SB.0 is not set in the status byte) or KL2541 is not ready to operate

on

Motor control is disabled (bit SB.0 is set in the status byte) and KL2541 is ready to operate

Error A (red)

flashes (1 Hz)

Configuration error, e.g.:
- Value for motor full steps is 0 (R33)
- Value for encoder increments is 0 (R34)
- Value for min. velocity vmin is 0 (R38)
- Value for max. velocity vmax is 0 (R39)
- Value for max. acceleration amax is 0 (R40)
- Value for coil current IS for a > ath is 0 (R42)
- Value for coil current IS with a ≤ ath is 0 (R43)

Power (green)

off

Supply voltage (48 VDC) not available or

motor control is disabled (bit SB.0 is not set in the status byte)

on

Supply voltage (48 VDC) present

Turn CCW (green)

on

Motor turns counterclockwise

Stall detect (yellow)

on

Motor control is disabled (bit SB.0 is not set in the status byte)

flashes (1 Hz)

The current load angle (SB.3 to SB.1) is greater than the configured load angle threshold (R47).

Error B (red)

flashes (1 Hz)

Supply or load error
- Supply voltage (24 VDC) too low (bit SW.9 in the status word is set)
- Open load at bridge A (bit SW.11 is set in the status word)
- Open load at bridge B (bit SW.12 is set in the status word)
- Overcurrent at bridge A (bit SW.13 is set in the status word)
- Overcurrent at bridge B (bit SW.11 is set in the status word)