KL2541 - LED Displays
Left LED prism
LED | Display | |
---|---|---|
Run (green) | on | Data transmission on the K-bus is active |
A (green) | on | A signal is present at encoder input A. |
C (green) | on | A signal is present at encoder input C. |
Input 1 (green) | on | A signal is present at digital input E1. |
- | reserved | |
B (green) | on | A signal is present at encoder input B. |
Latch (green) | on | A signal is present at the latch input of the encoder. |
Input 2 (green) | on | A signal is present at digital input E2. |
Right LED prism
LED | Display | |
---|---|---|
- | reserved | |
Turn CW (green) | on | Motor turns clockwise |
Enable (green) | off | Motor control is disabled (bit SB.0 is not set in the status byte) or KL2541 is not ready to operate |
on | Motor control is disabled (bit SB.0 is set in the status byte) and KL2541 is ready to operate | |
Error A (red) | flashes (1 Hz) | Configuration error, e.g.: |
Power (green) | off | Supply voltage (48 VDC) not available or
|
on | Supply voltage (48 VDC) present | |
Turn CCW (green) | on | Motor turns counterclockwise |
Stall detect (yellow) | on | Motor control is disabled (bit SB.0 is not set in the status byte) |
flashes (1 Hz) | The current load angle (SB.3 to SB.1) is greater than the configured load angle threshold (R47). | |
Error B (red) | flashes (1 Hz) | Supply or load error |