CAN Identifier List
The list provided here should assist in identifying and assigning CANopen messages. All the identifiers allocated by the CANopen default identifier allocation are listed, as well as the manufacturer-specific default identifiers issued by BECKHOFF via object 0x5500 (only to be used in networks with node addresses less than 64).
The following values can be used as search aids and "entry points" in the extensive identifier table in the *chm edition of the documentation:
The identifier distribution via object 0x5500 follows this pattern:
Object | Resulting COB ID (dec) | Resulting COB ID (hex) |
|---|---|---|
129 to 191 [255] | 0x81 to 0xBF [0xFF] | |
385 to 447 [511] | 0x181 to 0x1BF [0x1FF] | |
513 to 575 [639] | 0x201 to 0x23F [0x27F] | |
641 to 676 [767] | 0x281 to 0x2BF [0x2FF] | |
769 to 831 [895] | 0x301 to 0x33F [0x37F] | |
897 to 959 [1023] | 0x381 to 0x3BF [0x3FF] | |
1025 to 1087 [1151] | 0x401 to 0x43F [0x47F] | |
1153 to 1215 [1279] | 0x481 to 0x4BF [0x4FF] | |
1281 to 1343 [1407] | 0x501 to 0x53F [0x57F] | |
1665 to 1727 | 0x681 to 0x6BF | |
1921 to 1983 | 0x781 to 0x7BF | |
449 to 511 | 0x1C1 to 0x1FF | |
577 to 639 | 0x241 to 0x27F | |
705 to 767 | 0x2C1 to 0x2FF | |
833 to 895 | 0x341 to 0x37F | |
961 to 1023 | 0x3C1 to 0x3FF | |
1089 to 1151 | 0x441 to 0x47F | |
1217 to 1279 | 0x4C1 to 0x4FF | |
1345 to 1407 | 0x541 to 0x57F | |
1473 to 1535 | 0x5C1 to 0x5FF | |
1601 to 1663 | 0x641 to 0x67F | |
1729 to 1791 | 0x6C1 to 0x6FF | |
1857 to 1919 | 0x741 to 0x77F | |
1409 to 1471 [1535] | 0x581 to 0x5BF [0x5FF] | |
1537 to 1599 [1663] | 0x601 to 0x63F [0x67F] | |
1793 to 1855 [1919] | 0x701 to 0x73F [0x77F] |
Identifier List
Identifiers marked with * are given manufacturer-specific assignments on the Bus Couplers after writing index 0x5500
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
0 | 0x00 | NMT | 149 | 0x95 | EMCY Nd.21 | 171 | 0xAB | EMCY Nd.43 |
128 | 0x80 | SYNC | 150 | 0x96 | EMCY Nd.22 | 172 | 0xAC | EMCY Nd.44 |
129 | 0x81 | EMCY Nd.1 | 151 | 0x97 | EMCY Nd.23 | 173 | 0xAD | EMCY Nd.45 |
130 | 0x82 | EMCY Nd.2 | 152 | 0x98 | EMCY Nd.24 | 174 | 0xAE | EMCY Nd.46 |
131 | 0x83 | EMCY Nd.3 | 153 | 0x99 | EMCY Nd.25 | 175 | 0xAF | EMCY Nd.47 |
132 | 0x84 | EMCY Nd.4 | 154 | 0x9A | EMCY Nd.26 | 176 | 0xB0 | EMCY Nd.48 |
133 | 0x85 | EMCY Nd.5 | 155 | 0x9B | EMCY Nd.27 | 177 | 0xB1 | EMCY Nd.49 |
134 | 0x86 | EMCY Nd.6 | 156 | 0x9C | EMCY Nd.28 | 178 | 0xB2 | EMCY Nd.50 |
135 | 0x87 | EMCY Nd.7 | 157 | 0x9D | EMCY Nd.29 | 179 | 0xB3 | EMCY Nd.51 |
136 | 0x88 | EMCY Nd.8 | 158 | 0x9E | EMCY Nd.30 | 180 | 0xB4 | EMCY Nd.52 |
137 | 0x89 | EMCY Nd.9 | 159 | 0x9F | EMCY Nd.31 | 181 | 0xB5 | EMCY Nd.53 |
138 | 0x8A | EMCY Nd.10 | 160 | 0xA0 | EMCY Nd.32 | 182 | 0xB6 | EMCY Nd.54 |
139 | 0x8B | EMCY Nd.11 | 161 | 0xA1 | EMCY Nd.33 | 183 | 0xB7 | EMCY Nd.55 |
140 | 0x8C | EMCY Nd.12 | 162 | 0xA2 | EMCY Nd.34 | 184 | 0xB8 | EMCY Nd.56 |
141 | 0x8D | EMCY Nd.13 | 163 | 0xA3 | EMCY Nd.35 | 185 | 0xB9 | EMCY Nd.57 |
142 | 0x8E | EMCY Nd.14 | 164 | 0xA4 | EMCY Nd.36 | 186 | 0xBA | EMCY Nd.58 |
143 | 0x8F | EMCY Nd.15 | 165 | 0xA5 | EMCY Nd.37 | 187 | 0xBB | EMCY Nd.59 |
144 | 0x90 | EMCY Nd.16 | 166 | 0xA6 | EMCY Nd.38 | 188 | 0xBC | EMCY Nd.60 |
145 | 0x91 | EMCY Nd.17 | 167 | 0xA7 | EMCY Nd.39 | 189 | 0xBD | EMCY Nd.61 |
146 | 0x92 | EMCY Nd.18 | 168 | 0xA8 | EMCY Nd.40 | 190 | 0xBE | EMCY Nd.62 |
147 | 0x93 | EMCY Nd.19 | 169 | 0xA9 | EMCY Nd.41 | 191 | 0xBF | EMCY Nd.63 |
148 | 0x94 | EMCY Nd.20 | 170 | 0xAA | EMCY Nd.42 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
385 | 0x181 | TxPDO1, DI, Nd.1 | 406 | 0x196 | TxPDO1, DI, Nd.22 | 427 | 0x1AB | TxPDO1, DI, Nd.43 |
386 | 0x182 | TxPDO1, DI, Nd.2 | 407 | 0x197 | TxPDO1, DI, Nd.23 | 428 | 0x1AC | TxPDO1, DI, Nd.44 |
387 | 0x183 | TxPDO1, DI, Nd.3 | 408 | 0x198 | TxPDO1, DI, Nd.24 | 429 | 0x1AD | TxPDO1, DI, Nd.45 |
388 | 0x184 | TxPDO1, DI, Nd.4 | 409 | 0x199 | TxPDO1, DI, Nd.25 | 430 | 0x1AE | TxPDO1, DI, Nd.46 |
389 | 0x185 | TxPDO1, DI, Nd.5 | 410 | 0x19A | TxPDO1, DI, Nd.26 | 431 | 0x1AF | TxPDO1, DI, Nd.47 |
390 | 0x186 | TxPDO1, DI, Nd.6 | 411 | 0x19B | TxPDO1, DI, Nd.27 | 432 | 0x1B0 | TxPDO1, DI, Nd.48 |
391 | 0x187 | TxPDO1, DI, Nd.7 | 412 | 0x19C | TxPDO1, DI, Nd.28 | 433 | 0x1B1 | TxPDO1, DI, Nd.49 |
392 | 0x188 | TxPDO1, DI, Nd.8 | 413 | 0x19D | TxPDO1, DI, Nd.29 | 434 | 0x1B2 | TxPDO1, DI, Nd.50 |
393 | 0x189 | TxPDO1, DI, Nd.9 | 414 | 0x19E | TxPDO1, DI, Nd.30 | 435 | 0x1B3 | TxPDO1, DI, Nd.51 |
394 | 0x18A | TxPDO1, DI, Nd.10 | 415 | 0x19F | TxPDO1, DI, Nd.31 | 436 | 0x1B4 | TxPDO1, DI, Nd.52 |
395 | 0x18B | TxPDO1, DI, Nd.11 | 416 | 0x1A0 | TxPDO1, DI, Nd.32 | 437 | 0x1B5 | TxPDO1, DI, Nd.53 |
396 | 0x18C | TxPDO1, DI, Nd.12 | 417 | 0x1A1 | TxPDO1, DI, Nd.33 | 438 | 0x1B6 | TxPDO1, DI, Nd.54 |
397 | 0x18D | TxPDO1, DI, Nd.13 | 418 | 0x1A2 | TxPDO1, DI, Nd.34 | 439 | 0x1B7 | TxPDO1, DI, Nd.55 |
398 | 0x18E | TxPDO1, DI, Nd.14 | 419 | 0x1A3 | TxPDO1, DI, Nd.35 | 440 | 0x1B8 | TxPDO1, DI, Nd.56 |
399 | 0x18F | TxPDO1, DI, Nd.15 | 420 | 0x1A4 | TxPDO1, DI, Nd.36 | 441 | 0x1B9 | TxPDO1, DI, Nd.57 |
400 | 0x190 | TxPDO1, DI, Nd.16 | 421 | 0x1A5 | TxPDO1, DI, Nd.37 | 442 | 0x1BA | TxPDO1, DI, Nd.58 |
401 | 0x191 | TxPDO1, DI, Nd.17 | 422 | 0x1A6 | TxPDO1, DI, Nd.38 | 443 | 0x1BB | TxPDO1, DI, Nd.59 |
402 | 0x192 | TxPDO1, DI, Nd.18 | 423 | 0x1A7 | TxPDO1, DI, Nd.39 | 444 | 0x1BC | TxPDO1, DI, Nd.60 |
403 | 0x193 | TxPDO1, DI, Nd.19 | 424 | 0x1A8 | TxPDO1, DI, Nd.40 | 445 | 0x1BD | TxPDO1, DI, Nd.61 |
404 | 0x194 | TxPDO1, DI, Nd.20 | 425 | 0x1A9 | TxPDO1, DI, Nd.41 | 446 | 0x1BE | TxPDO1, DI, Nd.62 |
405 | 0x195 | TxPDO1, DI, Nd.21 | 426 | 0x1AA | TxPDO1, DI, Nd.42 | 447 | 0x1BF | TxPDO1, DI, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
513 | 0x201 | RxPDO1, DO, Nd.1 | 534 | 0x216 | RxPDO1, DO, Nd.22 | 555 | 0x22B | RxPDO1, DO, Nd.43 |
514 | 0x202 | RxPDO1, DO, Nd.2 | 535 | 0x217 | RxPDO1, DO, Nd.23 | 556 | 0x22C | RxPDO1, DO, Nd.44 |
515 | 0x203 | RxPDO1, DO, Nd.3 | 536 | 0x218 | RxPDO1, DO, Nd.24 | 557 | 0x22D | RxPDO1, DO, Nd.45 |
516 | 0x204 | RxPDO1, DO, Nd.4 | 537 | 0x219 | RxPDO1, DO, Nd.25 | 558 | 0x22E | RxPDO1, DO, Nd.46 |
517 | 0x205 | RxPDO1, DO, Nd.5 | 538 | 0x21A | RxPDO1, DO, Nd.26 | 559 | 0x22F | RxPDO1, DO, Nd.47 |
518 | 0x206 | RxPDO1, DO, Nd.6 | 539 | 0x21B | RxPDO1, DO, Nd.27 | 560 | 0x230 | RxPDO1, DO, Nd.48 |
519 | 0x207 | RxPDO1, DO, Nd.7 | 540 | 0x21C | RxPDO1, DO, Nd.28 | 561 | 0x231 | RxPDO1, DO, Nd.49 |
520 | 0x208 | RxPDO1, DO, Nd.8 | 541 | 0x21D | RxPDO1, DO, Nd.29 | 562 | 0x232 | RxPDO1, DO, Nd.50 |
521 | 0x209 | RxPDO1, DO, Nd.9 | 542 | 0x21E | RxPDO1, DO, Nd.30 | 563 | 0x233 | RxPDO1, DO, Nd.51 |
522 | 0x20A | RxPDO1, DO, Nd.10 | 543 | 0x21F | RxPDO1, DO, Nd.31 | 564 | 0x234 | RxPDO1, DO, Nd.52 |
523 | 0x20B | RxPDO1, DO, Nd.11 | 544 | 0x220 | RxPDO1, DO, Nd.32 | 565 | 0x235 | RxPDO1, DO, Nd.53 |
524 | 0x20C | RxPDO1, DO, Nd.12 | 545 | 0x221 | RxPDO1, DO, Nd.33 | 566 | 0x236 | RxPDO1, DO, Nd.54 |
525 | 0x20D | RxPDO1, DO, Nd.13 | 546 | 0x222 | RxPDO1, DO, Nd.34 | 567 | 0x237 | RxPDO1, DO, Nd.55 |
526 | 0x20E | RxPDO1, DO, Nd.14 | 547 | 0x223 | RxPDO1, DO, Nd.35 | 568 | 0x238 | RxPDO1, DO, Nd.56 |
527 | 0x20F | RxPDO1, DO, Nd.15 | 548 | 0x224 | RxPDO1, DO, Nd.36 | 569 | 0x239 | RxPDO1, DO, Nd.57 |
528 | 0x210 | RxPDO1, DO, Nd.16 | 549 | 0x225 | RxPDO1, DO, Nd.37 | 570 | 0x23A | RxPDO1, DO, Nd.58 |
529 | 0x211 | RxPDO1, DO, Nd.17 | 550 | 0x226 | RxPDO1, DO, Nd.38 | 571 | 0x23B | RxPDO1, DO, Nd.59 |
530 | 0x212 | RxPDO1, DO, Nd.18 | 551 | 0x227 | RxPDO1, DO, Nd.39 | 572 | 0x23C | RxPDO1, DO, Nd.60 |
531 | 0x213 | RxPDO1, DO, Nd.19 | 552 | 0x228 | RxPDO1, DO, Nd.40 | 573 | 0x23D | RxPDO1, DO, Nd.61 |
532 | 0x214 | RxPDO1, DO, Nd.20 | 553 | 0x229 | RxPDO1, DO, Nd.41 | 574 | 0x23E | RxPDO1, DO, Nd.62 |
533 | 0x215 | RxPDO1, DO, Nd.21 | 554 | 0x22A | RxPDO1, DO, Nd.42 | 575 | 0x23F | RxPDO1, DO, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
641 | 0x281 | TxPDO2, AI, Nd.1 | 662 | 0x296 | TxPDO2, AI, Nd.22 | 683 | 0x2AB | TxPDO2, AI, Nd.43 |
642 | 0x282 | TxPDO2, AI, Nd.2 | 663 | 0x297 | TxPDO2, AI, Nd.23 | 684 | 0x2AC | TxPDO2, AI, Nd.44 |
643 | 0x283 | TxPDO2, AI, Nd.3 | 664 | 0x298 | TxPDO2, AI, Nd.24 | 685 | 0x2AD | TxPDO2, AI, Nd.45 |
644 | 0x284 | TxPDO2, AI, Nd.4 | 665 | 0x299 | TxPDO2, AI, Nd.25 | 686 | 0x2AE | TxPDO2, AI, Nd.46 |
645 | 0x285 | TxPDO2, AI, Nd.5 | 666 | 0x29A | TxPDO2, AI, Nd.26 | 687 | 0x2AF | TxPDO2, AI, Nd.47 |
646 | 0x286 | TxPDO2, AI, Nd.6 | 667 | 0x29B | TxPDO2, AI, Nd.27 | 688 | 0x2B0 | TxPDO2, AI, Nd.48 |
647 | 0x287 | TxPDO2, AI, Nd.7 | 668 | 0x29C | TxPDO2, AI, Nd.28 | 689 | 0x2B1 | TxPDO2, AI, Nd.49 |
648 | 0x288 | TxPDO2, AI, Nd.8 | 669 | 0x29D | TxPDO2, AI, Nd.29 | 690 | 0x2B2 | TxPDO2, AI, Nd.50 |
649 | 0x289 | TxPDO2, AI, Nd.9 | 670 | 0x29E | TxPDO2, AI, Nd.30 | 691 | 0x2B3 | TxPDO2, AI, Nd.51 |
650 | 0x28A | TxPDO2, AI, Nd.10 | 671 | 0x29F | TxPDO2, AI, Nd.31 | 692 | 0x2B4 | TxPDO2, AI, Nd.52 |
651 | 0x28B | TxPDO2, AI, Nd.11 | 672 | 0x2A0 | TxPDO2, AI, Nd.32 | 693 | 0x2B5 | TxPDO2, AI, Nd.53 |
652 | 0x28C | TxPDO2, AI, Nd.12 | 673 | 0x2A1 | TxPDO2, AI, Nd.33 | 694 | 0x2B6 | TxPDO2, AI, Nd.54 |
653 | 0x28D | TxPDO2, AI, Nd.13 | 674 | 0x2A2 | TxPDO2, AI, Nd.34 | 695 | 0x2B7 | TxPDO2, AI, Nd.55 |
654 | 0x28E | TxPDO2, AI, Nd.14 | 675 | 0x2A3 | TxPDO2, AI, Nd.35 | 696 | 0x2B8 | TxPDO2, AI, Nd.56 |
655 | 0x28F | TxPDO2, AI, Nd.15 | 676 | 0x2A4 | TxPDO2, AI, Nd.36 | 697 | 0x2B9 | TxPDO2, AI, Nd.57 |
656 | 0x290 | TxPDO2, AI, Nd.16 | 677 | 0x2A5 | TxPDO2, AI, Nd.37 | 698 | 0x2BA | TxPDO2, AI, Nd.58 |
657 | 0x291 | TxPDO2, AI, Nd.17 | 678 | 0x2A6 | TxPDO2, AI, Nd.38 | 699 | 0x2BB | TxPDO2, AI, Nd.59 |
658 | 0x292 | TxPDO2, AI, Nd.18 | 679 | 0x2A7 | TxPDO2, AI, Nd.39 | 700 | 0x2BC | TxPDO2, AI, Nd.60 |
659 | 0x293 | TxPDO2, AI, Nd.19 | 680 | 0x2A8 | TxPDO2, AI, Nd.40 | 701 | 0x2BD | TxPDO2, AI, Nd.61 |
660 | 0x294 | TxPDO2, AI, Nd.20 | 681 | 0x2A9 | TxPDO2, AI, Nd.41 | 702 | 0x2BE | TxPDO2, AI, Nd.62 |
661 | 0x295 | TxPDO2, AI, Nd.21 | 682 | 0x2AA | TxPDO2, AI, Nd.42 | 703 | 0x2BF | TxPDO2, AI, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
769 | 0x301 | RxPDO2, AO, Nd.1 | 790 | 0x316 | RxPDO2, AO, Nd.22 | 811 | 0x32B | RxPDO2, AO, Nd.43 |
770 | 0x302 | RxPDO2, AO, Nd.2 | 791 | 0x317 | RxPDO2, AO, Nd.23 | 812 | 0x32C | RxPDO2, AO, Nd.44 |
771 | 0x303 | RxPDO2, AO, Nd.3 | 792 | 0x318 | RxPDO2, AO, Nd.24 | 813 | 0x32D | RxPDO2, AO, Nd.45 |
772 | 0x304 | RxPDO2, AO, Nd.4 | 793 | 0x319 | RxPDO2, AO, Nd.25 | 814 | 0x32E | RxPDO2, AO, Nd.46 |
773 | 0x305 | RxPDO2, AO, Nd.5 | 794 | 0x31A | RxPDO2, AO, Nd.26 | 815 | 0x32F | RxPDO2, AO, Nd.47 |
774 | 0x306 | RxPDO2, AO, Nd.6 | 795 | 0x31B | RxPDO2, AO, Nd.27 | 816 | 0x330 | RxPDO2, AO, Nd.48 |
775 | 0x307 | RxPDO2, AO, Nd.7 | 796 | 0x31C | RxPDO2, AO, Nd.28 | 817 | 0x331 | RxPDO2, AO, Nd.49 |
776 | 0x308 | RxPDO2, AO, Nd.8 | 797 | 0x31D | RxPDO2, AO, Nd.29 | 818 | 0x332 | RxPDO2, AO, Nd.50 |
777 | 0x309 | RxPDO2, AO, Nd.9 | 798 | 0x31E | RxPDO2, AO, Nd.30 | 819 | 0x333 | RxPDO2, AO, Nd.51 |
778 | 0x30A | RxPDO2, AO, Nd.10 | 799 | 0x31F | RxPDO2, AO, Nd.31 | 820 | 0x334 | RxPDO2, AO, Nd.52 |
779 | 0x30B | RxPDO2, AO, Nd.11 | 800 | 0x320 | RxPDO2, AO, Nd.32 | 821 | 0x335 | RxPDO2, AO, Nd.53 |
780 | 0x30C | RxPDO2, AO, Nd.12 | 801 | 0x321 | RxPDO2, AO, Nd.33 | 822 | 0x336 | RxPDO2, AO, Nd.54 |
781 | 0x30D | RxPDO2, AO, Nd.13 | 802 | 0x322 | RxPDO2, AO, Nd.34 | 823 | 0x337 | RxPDO2, AO, Nd.55 |
782 | 0x30E | RxPDO2, AO, Nd.14 | 803 | 0x323 | RxPDO2, AO, Nd.35 | 824 | 0x338 | RxPDO2, AO, Nd.56 |
783 | 0x30F | RxPDO2, AO, Nd.15 | 804 | 0x324 | RxPDO2, AO, Nd.36 | 825 | 0x339 | RxPDO2, AO, Nd.57 |
784 | 0x310 | RxPDO2, AO, Nd.16 | 805 | 0x325 | RxPDO2, AO, Nd.37 | 826 | 0x33A | RxPDO2, AO, Nd.58 |
785 | 0x311 | RxPDO2, AO, Nd.17 | 806 | 0x326 | RxPDO2, AO, Nd.38 | 827 | 0x33B | RxPDO2, AO, Nd.59 |
786 | 0x312 | RxPDO2, AO, Nd.18 | 807 | 0x327 | RxPDO2, AO, Nd.39 | 828 | 0x33C | RxPDO2, AO, Nd.60 |
787 | 0x313 | RxPDO2, AO, Nd.19 | 808 | 0x328 | RxPDO2, AO, Nd.40 | 829 | 0x33D | RxPDO2, AO, Nd.61 |
788 | 0x314 | RxPDO2, AO, Nd.20 | 809 | 0x329 | RxPDO2, AO, Nd.41 | 830 | 0x33E | RxPDO2, AO, Nd.62 |
789 | 0x315 | RxPDO2, AO, Nd.21 | 810 | 0x32A | RxPDO2, AO, Nd.42 | 831 | 0x33F | RxPDO2, AO, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
897 | 0x381 | TxPDO3*, Nd.1 | 918 | 0x396 | TxPDO3*, Nd.22 | 939 | 0x3AB | TxPDO3*, Nd.43 |
898 | 0x382 | TxPDO3*, Nd.2 | 919 | 0x397 | TxPDO3*, Nd.23 | 940 | 0x3AC | TxPDO3*, Nd.44 |
899 | 0x383 | TxPDO3*, Nd.3 | 920 | 0x398 | TxPDO3*, Nd.24 | 941 | 0x3AD | TxPDO3*, Nd.45 |
900 | 0x384 | TxPDO3*, Nd.4 | 921 | 0x399 | TxPDO3*, Nd.25 | 942 | 0x3AE | TxPDO3*, Nd.46 |
901 | 0x385 | TxPDO3*, Nd.5 | 922 | 0x39A | TxPDO3*, Nd.26 | 943 | 0x3AF | TxPDO3*, Nd.47 |
902 | 0x386 | TxPDO3*, Nd.6 | 923 | 0x39B | TxPDO3*, Nd.27 | 944 | 0x3B0 | TxPDO3*, Nd.48 |
903 | 0x387 | TxPDO3*, Nd.7 | 924 | 0x39C | TxPDO3*, Nd.28 | 945 | 0x3B1 | TxPDO3*, Nd.49 |
904 | 0x388 | TxPDO3*, Nd.8 | 925 | 0x39D | TxPDO3*, Nd.29 | 946 | 0x3B2 | TxPDO3*, Nd.50 |
905 | 0x389 | TxPDO3*, Nd.9 | 926 | 0x39E | TxPDO3*, Nd.30 | 947 | 0x3B3 | TxPDO3*, Nd.51 |
906 | 0x38A | TxPDO3*, Nd.10 | 927 | 0x39F | TxPDO3*, Nd.31 | 948 | 0x3B4 | TxPDO3*, Nd.52 |
907 | 0x38B | TxPDO3*, Nd.11 | 928 | 0x3A0 | TxPDO3*, Nd.32 | 949 | 0x3B5 | TxPDO3*, Nd.53 |
908 | 0x38C | TxPDO3*, Nd.12 | 929 | 0x3A1 | TxPDO3*, Nd.33 | 950 | 0x3B6 | TxPDO3*, Nd.54 |
909 | 0x38D | TxPDO3*, Nd.13 | 930 | 0x3A2 | TxPDO3*, Nd.34 | 951 | 0x3B7 | TxPDO3*, Nd.55 |
910 | 0x38E | TxPDO3*, Nd.14 | 931 | 0x3A3 | TxPDO3*, Nd.35 | 952 | 0x3B8 | TxPDO3*, Nd.56 |
911 | 0x38F | TxPDO3*, Nd.15 | 932 | 0x3A4 | TxPDO3*, Nd.36 | 953 | 0x3B9 | TxPDO3*, Nd.57 |
912 | 0x390 | TxPDO3*, Nd.16 | 933 | 0x3A5 | TxPDO3*, Nd.37 | 954 | 0x3BA | TxPDO3*, Nd.58 |
913 | 0x391 | TxPDO3*, Nd.17 | 934 | 0x3A6 | TxPDO3*, Nd.38 | 955 | 0x3BB | TxPDO3*, Nd.59 |
914 | 0x392 | TxPDO3*, Nd.18 | 935 | 0x3A7 | TxPDO3*, Nd.39 | 956 | 0x3BC | TxPDO3*, Nd.60 |
915 | 0x393 | TxPDO3*, Nd.19 | 936 | 0x3A8 | TxPDO3*, Nd.40 | 957 | 0x3BD | TxPDO3*, Nd.61 |
916 | 0x394 | TxPDO3*, Nd.20 | 937 | 0x3A9 | TxPDO3*, Nd.41 | 958 | 0x3BE | TxPDO3*, Nd.62 |
917 | 0x395 | TxPDO3*, Nd.21 | 938 | 0x3AA | TxPDO3*, Nd.42 | 959 | 0x3BF | TxPDO3*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
1025 | 0x401 | RxPDO3*, Nd.1 | 1046 | 0x416 | RxPDO3*, Nd.22 | 1067 | 0x42B | RxPDO3*, Nd.43 |
1026 | 0x402 | RxPDO3*, Nd.2 | 1047 | 0x417 | RxPDO3*, Nd.23 | 1068 | 0x42C | RxPDO3*, Nd.44 |
1027 | 0x403 | RxPDO3*, Nd.3 | 1048 | 0x418 | RxPDO3*, Nd.24 | 1069 | 0x42D | RxPDO3*, Nd.45 |
1028 | 0x404 | RxPDO3*, Nd.4 | 1049 | 0x419 | RxPDO3*, Nd.25 | 1070 | 0x42E | RxPDO3*, Nd.46 |
1029 | 0x405 | RxPDO3*, Nd.5 | 1050 | 0x41A | RxPDO3*, Nd.26 | 1071 | 0x42F | RxPDO3*, Nd.47 |
1030 | 0x406 | RxPDO3*, Nd.6 | 1051 | 0x41B | RxPDO3*, Nd.27 | 1072 | 0x430 | RxPDO3*, Nd.48 |
1031 | 0x407 | RxPDO3*, Nd.7 | 1052 | 0x41C | RxPDO3*, Nd.28 | 1073 | 0x431 | RxPDO3*, Nd.49 |
1032 | 0x408 | RxPDO3*, Nd.8 | 1053 | 0x41D | RxPDO3*, Nd.29 | 1074 | 0x432 | RxPDO3*, Nd.50 |
1033 | 0x409 | RxPDO3*, Nd.9 | 1054 | 0x41E | RxPDO3*, Nd.30 | 1075 | 0x433 | RxPDO3*, Nd.51 |
1034 | 0x40A | RxPDO3*, Nd.10 | 1055 | 0x41F | RxPDO3*, Nd.31 | 1076 | 0x434 | RxPDO3*, Nd.52 |
1035 | 0x40B | RxPDO3*, Nd.11 | 1056 | 0x420 | RxPDO3*, Nd.32 | 1077 | 0x435 | RxPDO3*, Nd.53 |
1036 | 0x40C | RxPDO3*, Nd.12 | 1057 | 0x421 | RxPDO3*, Nd.33 | 1078 | 0x436 | RxPDO3*, Nd.54 |
1037 | 0x40D | RxPDO3*, Nd.13 | 1058 | 0x422 | RxPDO3*, Nd.34 | 1079 | 0x437 | RxPDO3*, Nd.55 |
1038 | 0x40E | RxPDO3*, Nd.14 | 1059 | 0x423 | RxPDO3*, Nd.35 | 1080 | 0x438 | RxPDO3*, Nd.56 |
1039 | 0x40F | RxPDO3*, Nd.15 | 1060 | 0x424 | RxPDO3*, Nd.36 | 1081 | 0x439 | RxPDO3*, Nd.57 |
1040 | 0x410 | RxPDO3*, Nd.16 | 1061 | 0x425 | RxPDO3*, Nd.37 | 1082 | 0x43A | RxPDO3*, Nd.58 |
1041 | 0x411 | RxPDO3*, Nd.17 | 1062 | 0x426 | RxPDO3*, Nd.38 | 1083 | 0x43B | RxPDO3*, Nd.59 |
1042 | 0x412 | RxPDO3*, Nd.18 | 1063 | 0x427 | RxPDO3*, Nd.39 | 1084 | 0x43C | RxPDO3*, Nd.60 |
1043 | 0x413 | RxPDO3*, Nd.19 | 1064 | 0x428 | RxPDO3*, Nd.40 | 1085 | 0x43D | RxPDO3*, Nd.61 |
1044 | 0x414 | RxPDO3*, Nd.20 | 1065 | 0x429 | RxPDO3*, Nd.41 | 1086 | 0x43E | RxPDO3*, Nd.62 |
1045 | 0x415 | RxPDO3*, Nd.21 | 1066 | 0x42A | RxPDO3*, Nd.42 | 1087 | 0x43F | RxPDO3*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
1153 | 0x481 | TxPDO4*, Nd.1 | 1174 | 0x496 | TxPDO4*, Nd.22 | 1195 | 0x4AB | TxPDO4*, Nd.43 |
1154 | 0x482 | TxPDO4*, Nd.2 | 1175 | 0x497 | TxPDO4*, Nd.23 | 1196 | 0x4AC | TxPDO4*, Nd.44 |
1155 | 0x483 | TxPDO4*, Nd.3 | 1176 | 0x498 | TxPDO4*, Nd.24 | 1197 | 0x4AD | TxPDO4*, Nd.45 |
1156 | 0x484 | TxPDO4*, Nd.4 | 1177 | 0x499 | TxPDO4*, Nd.25 | 1198 | 0x4AE | TxPDO4*, Nd.46 |
1157 | 0x485 | TxPDO4*, Nd.5 | 1178 | 0x49A | TxPDO4*, Nd.26 | 1199 | 0x4AF | TxPDO4*, Nd.47 |
1158 | 0x486 | TxPDO4*, Nd.6 | 1179 | 0x49B | TxPDO4*, Nd.27 | 1200 | 0x4B0 | TxPDO4*, Nd.48 |
1159 | 0x487 | TxPDO4*, Nd.7 | 1180 | 0x49C | TxPDO4*, Nd.28 | 1201 | 0x4B1 | TxPDO4*, Nd.49 |
1160 | 0x488 | TxPDO4*, Nd.8 | 1181 | 0x49D | TxPDO4*, Nd.29 | 1202 | 0x4B2 | TxPDO4*, Nd.50 |
1161 | 0x489 | TxPDO4*, Nd.9 | 1182 | 0x49E | TxPDO4*, Nd.30 | 1203 | 0x4B3 | TxPDO4*, Nd.51 |
1162 | 0x48A | TxPDO4*, Nd.10 | 1183 | 0x49F | TxPDO4*, Nd.31 | 1204 | 0x4B4 | TxPDO4*, Nd.52 |
1163 | 0x48B | TxPDO4*, Nd.11 | 1184 | 0x4A0 | TxPDO4*, Nd.32 | 1205 | 0x4B5 | TxPDO4*, Nd.53 |
1164 | 0x48C | TxPDO4*, Nd.12 | 1185 | 0x4A1 | TxPDO4*, Nd.33 | 1206 | 0x4B6 | TxPDO4*, Nd.54 |
1165 | 0x48D | TxPDO4*, Nd.13 | 1186 | 0x4A2 | TxPDO4*, Nd.34 | 1207 | 0x4B7 | TxPDO4*, Nd.55 |
1166 | 0x48E | TxPDO4*, Nd.14 | 1187 | 0x4A3 | TxPDO4*, Nd.35 | 1208 | 0x4B8 | TxPDO4*, Nd.56 |
1167 | 0x48F | TxPDO4*, Nd.15 | 1188 | 0x4A4 | TxPDO4*, Nd.36 | 1209 | 0x4B9 | TxPDO4*, Nd.57 |
1168 | 0x490 | TxPDO4*, Nd.16 | 1189 | 0x4A5 | TxPDO4*, Nd.37 | 1210 | 0x4BA | TxPDO4*, Nd.58 |
1169 | 0x491 | TxPDO4*, Nd.17 | 1190 | 0x4A6 | TxPDO4*, Nd.48 | 1211 | 0x4BB | TxPDO4*, Nd.59 |
1170 | 0x492 | TxPDO4*, Nd.18 | 1191 | 0x4A7 | TxPDO4*, Nd.49 | 1212 | 0x4BC | TxPDO4*, Nd.60 |
1171 | 0x493 | TxPDO4*, Nd.19 | 1192 | 0x4A8 | TxPDO4*, Nd.40 | 1213 | 0x4BD | TxPDO4*, Nd.61 |
1172 | 0x494 | TxPDO4*, Nd.20 | 1193 | 0x4A9 | TxPDO4*, Nd.41 | 1214 | 0x4BE | TxPDO4*, Nd.62 |
1173 | 0x495 | TxPDO4*, Nd.21 | 1194 | 0x4AA | TxPDO4*, Nd.42 | 1215 | 0x4BF | TxPDO4*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
1281 | 0x501 | RxPDO4*, Nd.1 | 1302 | 0x516 | RxPDO4*, Nd.22 | 1323 | 0x52B | RxPDO4*, Nd.43 |
1282 | 0x502 | RxPDO4*, Nd.2 | 1303 | 0x517 | RxPDO4*, Nd.23 | 1324 | 0x52C | RxPDO4*, Nd.44 |
1283 | 0x503 | RxPDO4*, Nd.3 | 1304 | 0x518 | RxPDO4*, Nd.24 | 1325 | 0x52D | RxPDO4*, Nd.45 |
1284 | 0x504 | RxPDO4*, Nd.4 | 1305 | 0x519 | RxPDO4*, Nd.25 | 1326 | 0x52E | RxPDO4*, Nd.46 |
1285 | 0x505 | RxPDO4*, Nd.5 | 1306 | 0x51A | RxPDO4*, Nd.26 | 1327 | 0x52F | RxPDO4*, Nd.47 |
1286 | 0x506 | RxPDO4*, Nd.6 | 1307 | 0x51B | RxPDO4*, Nd.27 | 1328 | 0x530 | RxPDO4*, Nd.48 |
1287 | 0x507 | RxPDO4*, Nd.7 | 1308 | 0x51C | RxPDO4*, Nd.28 | 1329 | 0x531 | RxPDO4*, Nd.49 |
1288 | 0x508 | RxPDO4*, Nd.8 | 1309 | 0x51D | RxPDO4*, Nd.29 | 1330 | 0x532 | RxPDO4*, Nd.50 |
1289 | 0x509 | RxPDO4*, Nd.9 | 1310 | 0x51E | RxPDO4*, Nd.30 | 1331 | 0x533 | RxPDO4*, Nd.51 |
1290 | 0x50A | RxPDO4*, Nd.10 | 1311 | 0x51F | RxPDO4*, Nd.31 | 1332 | 0x534 | RxPDO4*, Nd.52 |
1291 | 0x50B | RxPDO4*, Nd.11 | 1312 | 0x520 | RxPDO4*, Nd.32 | 1333 | 0x535 | RxPDO4*, Nd.53 |
1292 | 0x50C | RxPDO4*, Nd.12 | 1313 | 0x521 | RxPDO4*, Nd.33 | 1334 | 0x536 | RxPDO4*, Nd.54 |
1293 | 0x50D | RxPDO4*, Nd.13 | 1314 | 0x522 | RxPDO4*, Nd.34 | 1335 | 0x537 | RxPDO4*, Nd.55 |
1294 | 0x50E | RxPDO4*, Nd.14 | 1315 | 0x523 | RxPDO4*, Nd.35 | 1336 | 0x538 | RxPDO4*, Nd.56 |
1295 | 0x50F | RxPDO4*, Nd.15 | 1316 | 0x524 | RxPDO4*, Nd.36 | 1337 | 0x539 | RxPDO4*, Nd.57 |
1296 | 0x510 | RxPDO4*, Nd.16 | 1317 | 0x525 | RxPDO4*, Nd.37 | 1338 | 0x53A | RxPDO4*, Nd.58 |
1297 | 0x511 | RxPDO4*, Nd.17 | 1318 | 0x526 | RxPDO4*, Nd.38 | 1339 | 0x53B | RxPDO4*, Nd.59 |
1298 | 0x512 | RxPDO4*, Nd.18 | 1319 | 0x527 | RxPDO4*, Nd.39 | 1340 | 0x53C | RxPDO4*, Nd.60 |
1299 | 0x513 | RxPDO4*, Nd.19 | 1320 | 0x528 | RxPDO4*, Nd.40 | 1341 | 0x53D | RxPDO4*, Nd.61 |
1300 | 0x514 | RxPDO4*, Nd.20 | 1321 | 0x529 | RxPDO4*, Nd.41 | 1342 | 0x53E | RxPDO4*, Nd.62 |
1301 | 0x515 | RxPDO4*, Nd.21 | 1322 | 0x52A | RxPDO4*, Nd.42 | 1343 | 0x53F | RxPDO4*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
1665 | 0x681 | TxPDO5*, Nd.1 | 1686 | 0x696 | TxPDO5*, Nd.22 | 1707 | 0x6AB | TxPDO5*, Nd.43 |
1666 | 0x682 | TxPDO5*, Nd.2 | 1687 | 0x697 | TxPDO5*, Nd.23 | 1708 | 0x6AC | TxPDO5*, Nd.44 |
1667 | 0x683 | TxPDO5*, Nd.3 | 1688 | 0x698 | TxPDO5*, Nd.24 | 1709 | 0x6AD | TxPDO5*, Nd.45 |
1668 | 0x684 | TxPDO5*, Nd.4 | 1689 | 0x699 | TxPDO5*, Nd.25 | 1710 | 0x6AE | TxPDO5*, Nd.46 |
1669 | 0x685 | TxPDO5*, Nd.5 | 1690 | 0x69A | TxPDO5*, Nd.26 | 1711 | 0x6AF | TxPDO5*, Nd.47 |
1670 | 0x686 | TxPDO5*, Nd.6 | 1691 | 0x69B | TxPDO5*, Nd.27 | 1712 | 0x6B0 | TxPDO5*, Nd.48 |
1671 | 0x687 | TxPDO5*, Nd.7 | 1692 | 0x69C | TxPDO5*, Nd.28 | 1713 | 0x6B1 | TxPDO5*, Nd.49 |
1672 | 0x688 | TxPDO5*, Nd.8 | 1693 | 0x69D | TxPDO5*, Nd.29 | 1714 | 0x6B2 | TxPDO5*, Nd.50 |
1673 | 0x689 | TxPDO5*, Nd.9 | 1694 | 0x69E | TxPDO5*, Nd.30 | 1715 | 0x6B3 | TxPDO5*, Nd.51 |
1674 | 0x68A | TxPDO5*, Nd.10 | 1695 | 0x69F | TxPDO5*, Nd.31 | 1716 | 0x6B4 | TxPDO5*, Nd.52 |
1675 | 0x68B | TxPDO5*, Nd.11 | 1696 | 0x6A0 | TxPDO5*, Nd.32 | 1717 | 0x6B5 | TxPDO5*, Nd.53 |
1676 | 0x68C | TxPDO5*, Nd.12 | 1697 | 0x6A1 | TxPDO5*, Nd.33 | 1718 | 0x6B6 | TxPDO5*, Nd.54 |
1677 | 0x68D | TxPDO5*, Nd.13 | 1698 | 0x6A2 | TxPDO5*, Nd.34 | 1719 | 0x6B7 | TxPDO5*, Nd.55 |
1678 | 0x68E | TxPDO5*, Nd.14 | 1699 | 0x6A3 | TxPDO5*, Nd.35 | 1720 | 0x6B8 | TxPDO5*, Nd.56 |
1679 | 0x68F | TxPDO5*, Nd.15 | 1700 | 0x6A4 | TxPDO5*, Nd.36 | 1721 | 0x6B9 | TxPDO5*, Nd.57 |
1680 | 0x690 | TxPDO5*, Nd.16 | 1701 | 0x6A5 | TxPDO5*, Nd.37 | 1722 | 0x6BA | TxPDO5*, Nd.58 |
1681 | 0x691 | TxPDO5*, Nd.17 | 1702 | 0x6A6 | TxPDO5*, Nd.38 | 1723 | 0x6BB | TxPDO5*, Nd.59 |
1682 | 0x692 | TxPDO5*, Nd.18 | 1703 | 0x6A7 | TxPDO5*, Nd.39 | 1724 | 0x6BC | TxPDO5*, Nd.60 |
1683 | 0x693 | TxPDO5*, Nd.19 | 1704 | 0x6A8 | TxPDO5*, Nd.40 | 1725 | 0x6BD | TxPDO5*, Nd.61 |
1684 | 0x694 | TxPDO5*, Nd.20 | 1705 | 0x6A9 | TxPDO5*, Nd.41 | 1726 | 0x6BE | TxPDO5*, Nd.62 |
1685 | 0x695 | TxPDO5*, Nd.21 | 1706 | 0x6AA | TxPDO5*, Nd.42 | 1727 | 0x6BF | TxPDO5*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
1921 | 0x781 | RxPDO5*, Nd.1 | 1942 | 0x796 | RxPDO5*, Nd.22 | 1963 | 0x7AB | RxPDO5*, Nd.43 |
1922 | 0x782 | RxPDO5*, Nd.2 | 1943 | 0x797 | RxPDO5*, Nd.23 | 1964 | 0x7AC | RxPDO5*, Nd.44 |
1923 | 0x783 | RxPDO5*, Nd.3 | 1944 | 0x798 | RxPDO5*, Nd.24 | 1965 | 0x7AD | RxPDO5*, Nd.45 |
1924 | 0x784 | RxPDO5*, Nd.4 | 1945 | 0x799 | RxPDO5*, Nd.25 | 1966 | 0x7AE | RxPDO5*, Nd.46 |
1925 | 0x785 | RxPDO5*, Nd.5 | 1946 | 0x79A | RxPDO5*, Nd.26 | 1967 | 0x7AF | RxPDO5*, Nd.47 |
1926 | 0x786 | RxPDO5*, Nd.6 | 1947 | 0x79B | RxPDO5*, Nd.27 | 1968 | 0x7B0 | RxPDO5*, Nd.48 |
1927 | 0x787 | RxPDO5*, Nd.7 | 1948 | 0x79C | RxPDO5*, Nd.28 | 1969 | 0x7B1 | RxPDO5*, Nd.49 |
1928 | 0x788 | RxPDO5*, Nd.8 | 1949 | 0x79D | RxPDO5*, Nd.29 | 1970 | 0x7B2 | RxPDO5*, Nd.50 |
1929 | 0x789 | RxPDO5*, Nd.9 | 1950 | 0x79E | RxPDO5*, Nd.30 | 1971 | 0x7B3 | RxPDO5*, Nd.51 |
1930 | 0x78A | RxPDO5*, Nd.10 | 1951 | 0x79F | RxPDO5*, Nd.31 | 1972 | 0x7B4 | RxPDO5*, Nd.52 |
1931 | 0x78B | RxPDO5*, Nd.11 | 1952 | 0x7A0 | RxPDO5*, Nd.32 | 1973 | 0x7B5 | RxPDO5*, Nd.53 |
1932 | 0x78C | RxPDO5*, Nd.12 | 1953 | 0x7A1 | RxPDO5*, Nd.33 | 1974 | 0x7B6 | RxPDO5*, Nd.54 |
1933 | 0x78D | RxPDO5*, Nd.13 | 1954 | 0x7A2 | RxPDO5*, Nd.34 | 1975 | 0x7B7 | RxPDO5*, Nd.55 |
1934 | 0x78E | RxPDO5*, Nd.14 | 1955 | 0x7A3 | RxPDO5*, Nd.35 | 1976 | 0x7B8 | RxPDO5*, Nd.56 |
1935 | 0x78F | RxPDO5*, Nd.15 | 1956 | 0x7A4 | RxPDO5*, Nd.36 | 1977 | 0x7B9 | RxPDO5*, Nd.57 |
1936 | 0x790 | RxPDO5*, Nd.16 | 1957 | 0x7A5 | RxPDO5*, Nd.37 | 1978 | 0x7BA | RxPDO5*, Nd.58 |
1937 | 0x791 | RxPDO5*, Nd.17 | 1958 | 0x7A6 | RxPDO5*, Nd.38 | 1979 | 0x7BB | RxPDO5*, Nd.59 |
1938 | 0x792 | RxPDO5*, Nd.18 | 1959 | 0x7A7 | RxPDO5*, Nd.39 | 1980 | 0x7BC | RxPDO5*, Nd.60 |
1939 | 0x793 | RxPDO5*, Nd.19 | 1960 | 0x7A8 | RxPDO5*, Nd.40 | 1981 | 0x7BD | RxPDO5*, Nd.61 |
1940 | 0x794 | RxPDO5*, Nd.20 | 1961 | 0x7A9 | RxPDO5*, Nd.41 | 1982 | 0x7BE | RxPDO5*, Nd.62 |
1941 | 0x795 | RxPDO5*, Nd.21 | 1962 | 0x7AA | RxPDO5*, Nd.42 | 1983 | 0x7BF | RxPDO5*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
449 | 0x1C1 | TxPDO6*, Nd.1 | 470 | 0x1D6 | TxPDO6*, Nd.22 | 491 | 0x1EB | TxPDO6*, Nd.43 |
450 | 0x1C2 | TxPDO6*, Nd.2 | 471 | 0x1D7 | TxPDO6*, Nd.23 | 492 | 0x1EC | TxPDO6*, Nd.44 |
451 | 0x1C3 | TxPDO6*, Nd.3 | 472 | 0x1D8 | TxPDO6*, Nd.24 | 493 | 0x1ED | TxPDO6*, Nd.45 |
452 | 0x1C4 | TxPDO6*, Nd.4 | 473 | 0x1D9 | TxPDO6*, Nd.25 | 494 | 0x1EE | TxPDO6*, Nd.46 |
453 | 0x1C5 | TxPDO6*, Nd.5 | 474 | 0x1DA | TxPDO6*, Nd.26 | 495 | 0x1EF | TxPDO6*, Nd.47 |
454 | 0x1C6 | TxPDO6*, Nd.6 | 475 | 0x1DB | TxPDO6*, Nd.27 | 496 | 0x1F0 | TxPDO6*, Nd.48 |
455 | 0x1C7 | TxPDO6*, Nd.7 | 476 | 0x1DC | TxPDO6*, Nd.28 | 497 | 0x1F1 | TxPDO6*, Nd.49 |
456 | 0x1C8 | TxPDO6*, Nd.8 | 477 | 0x1DD | TxPDO6*, Nd.29 | 498 | 0x1F2 | TxPDO6*, Nd.50 |
457 | 0x1C9 | TxPDO6*, Nd.9 | 478 | 0x1DE | TxPDO6*, Nd.30 | 499 | 0x1F3 | TxPDO6*, Nd.51 |
458 | 0x1CA | TxPDO6*, Nd.10 | 479 | 0x1DF | TxPDO6*, Nd.31 | 500 | 0x1F4 | TxPDO6*, Nd.52 |
459 | 0x1CB | TxPDO6*, Nd.11 | 480 | 0x1E0 | TxPDO6*, Nd.32 | 501 | 0x1F5 | TxPDO6*, Nd.53 |
460 | 0x1CC | TxPDO6*, Nd.12 | 481 | 0x1E1 | TxPDO6*, Nd.33 | 502 | 0x1F6 | TxPDO6*, Nd.54 |
461 | 0x1CD | TxPDO6*, Nd.13 | 482 | 0x1E2 | TxPDO6*, Nd.34 | 503 | 0x1F7 | TxPDO6*, Nd.55 |
462 | 0x1CE | TxPDO6*, Nd.14 | 483 | 0x1E3 | TxPDO6*, Nd.35 | 504 | 0x1F8 | TxPDO6*, Nd.56 |
463 | 0x1CF | TxPDO6*, Nd.15 | 484 | 0x1E4 | TxPDO6*, Nd.36 | 505 | 0x1F9 | TxPDO6*, Nd.57 |
464 | 0x1D0 | TxPDO6*, Nd.16 | 485 | 0x1E5 | TxPDO6*, Nd.37 | 506 | 0x1FA | TxPDO6*, Nd.58 |
465 | 0x1D1 | TxPDO6*, Nd.17 | 486 | 0x1E6 | TxPDO6*, Nd.38 | 507 | 0x1FB | TxPDO6*, Nd.59 |
466 | 0x1D2 | TxPDO6*, Nd.18 | 487 | 0x1E7 | TxPDO6*, Nd.39 | 508 | 0x1FC | TxPDO6*, Nd.60 |
467 | 0x1D3 | TxPDO6*, Nd.19 | 488 | 0x1E8 | TxPDO6*, Nd.40 | 509 | 0x1FD | TxPDO6*, Nd.61 |
468 | 0x1D4 | TxPDO6*, Nd.20 | 489 | 0x1E9 | TxPDO6*, Nd.41 | 510 | 0x1FE | TxPDO6*, Nd.62 |
469 | 0x1D5 | TxPDO6*, Nd.21 | 490 | 0x1EA | TxPDO6*, Nd.42 | 511 | 0x1FF | TxPDO6*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
577 | 0x241 | RxPDO6*, Nd.1 | 598 | 0x256 | RxPDO6*, Nd.22 | 619 | 0x26B | RxPDO6* Nd.43 |
578 | 0x242 | RxPDO6*, Nd.2 | 599 | 0x257 | RxPDO6*, Nd.23 | 620 | 0x26C | RxPDO6, Nd.44 |
579 | 0x243 | RxPDO6*, Nd.3 | 600 | 0x258 | RxPDO6*, Nd.24 | 621 | 0x26D | RxPDO6*, Nd.45 |
580 | 0x244 | RxPDO6*, Nd.4 | 601 | 0x259 | RxPDO6*, Nd.25 | 622 | 0x26E | RxPDO6*, Nd.46 |
581 | 0x245 | RxPDO6*, Nd.5 | 602 | 0x25A | RxPDO6*, Nd.26 | 623 | 0x26F | RxPDO6*, Nd.47 |
582 | 0x246 | RxPDO6*, Nd.6 | 603 | 0x25B | RxPDO6*, Nd.27 | 624 | 0x270 | RxPDO6*, Nd.48 |
583 | 0x247 | RxPDO6*, Nd.7 | 604 | 0x25C | RxPDO6*, Nd.28 | 625 | 0x271 | RxPDO6*, Nd.49 |
584 | 0x248 | RxPDO6*, Nd.8 | 605 | 0x25D | RxPDO6*, Nd.29 | 626 | 0x272 | RxPDO6*, Nd.50 |
585 | 0x249 | RxPDO6*, Nd.9 | 606 | 0x25E | RxPDO6*, Nd.30 | 627 | 0x273 | RxPDO6*, Nd.51 |
586 | 0x24A | RxPDO6*, Nd.10 | 607 | 0x25F | RxPDO6*, Nd.31 | 628 | 0x274 | RxPDO6*, Nd.52 |
587 | 0x24B | RxPDO6*, Nd.11 | 608 | 0x260 | RxPDO6*, Nd.32 | 629 | 0x275 | RxPDO6*, Nd.53 |
588 | 0x24C | RxPDO6*, Nd.12 | 609 | 0x261 | RxPDO6*, Nd.33 | 630 | 0x276 | RxPDO6*, Nd.54 |
589 | 0x24D | RxPDO6*, Nd.13 | 610 | 0x262 | RxPDO6*, Nd.34 | 631 | 0x277 | RxPDO6*, Nd.55 |
590 | 0x24E | RxPDO6*, Nd.14 | 611 | 0x263 | RxPDO6*, Nd.35 | 632 | 0x278 | RxPDO6*, Nd.56 |
591 | 0x24F | RxPDO6*, Nd.15 | 612 | 0x264 | RxPDO6*, Nd.36 | 633 | 0x279 | RxPDO6*, Nd.57 |
592 | 0x250 | RxPDO6*, Nd.16 | 613 | 0x265 | RxPDO6*, Nd.3 | 634 | 0x27A | RxPDO6*, Nd.58 |
593 | 0x251 | RxPDO6*, Nd.17 | 614 | 0x266 | RxPDO6*, Nd.8 | 635 | 0x27B | RxPDO6*, Nd.59 |
594 | 0x252 | RxPDO6*, Nd.18 | 615 | 0x267 | RxPDO6*, Nd39 | 636 | 0x27C | RxPDO6*, Nd.60 |
595 | 0x253 | RxPDO6*, Nd.19 | 616 | 0x268 | RxPDO6*, N.40 | 637 | 0x27D | RxPDO6*, Nd.61 |
596 | 0x254 | RxPDO6*, Nd.20 | 617 | 0x269 | RxPDO6*, d.41 | 638 | 0x27E | RxPDO6*, Nd.62 |
597 | 0x255 | RxPDO6*, Nd.21 | 618 | 0x26A | RxPDO6*,Nd.42 | 639 | 0x27F | RxPDO6*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
705 | 0x2C1 | TxPDO7*, Nd.1 | 726 | 0x2D6 | TxPDO7*, Nd.22 | 747 | 0x2EB | TxPDO7*, Nd.43 |
706 | 0x2C2 | TxPDO7*, Nd.2 | 727 | 0x2D7 | TxPDO7*, Nd.23 | 748 | 0x2EC | TxPDO7*, Nd.44 |
707 | 0x2C3 | TxPDO7*, Nd.3 | 728 | 0x2D8 | TxPDO7*, Nd.24 | 749 | 0x2ED | TxPDO7*, Nd.45 |
708 | 0x2C4 | TxPDO7*, Nd.4 | 729 | 0x2D9 | TxPDO7*, Nd.25 | 750 | 0x2EE | TxPDO7*, Nd.46 |
709 | 0x2C5 | TxPDO7*, Nd.5 | 730 | 0x2DA | TxPDO7*, Nd.26 | 751 | 0x2EF | TxPDO7*, Nd.47 |
710 | 0x2C6 | TxPDO7*, Nd.6 | 731 | 0x2DB | TxPDO7*, Nd.27 | 752 | 0x2F0 | TxPDO7*, Nd.48 |
711 | 0x2C7 | TxPDO7*, Nd.7 | 732 | 0x2DC | TxPDO7*, Nd.28 | 753 | 0x2F1 | TxPDO7*, Nd.49 |
712 | 0x2C8 | TxPDO7*, Nd.8 | 733 | 0x2DD | TxPDO7*, Nd.29 | 754 | 0x2F2 | TxPDO7*, Nd.50 |
713 | 0x2C9 | TxPDO7*, Nd.9 | 734 | 0x2DE | TxPDO7*, Nd.30 | 755 | 0x2F3 | TxPDO7*, Nd.51 |
714 | 0x2CA | TxPDO7*, Nd.10 | 735 | 0x2DF | TxPDO7*, Nd.31 | 756 | 0x2F4 | TxPDO7*, Nd.52 |
715 | 0x2CB | TxPDO7*, Nd.11 | 736 | 0x2E0 | TxPDO7*, Nd.32 | 757 | 0x2F5 | TxPDO7*, Nd.53 |
716 | 0x2CC | TxPDO7*, Nd.12 | 737 | 0x2E1 | TxPDO7*, Nd.33 | 758 | 0x2F6 | TxPDO7*, Nd.54 |
717 | 0x2CD | TxPDO7*, Nd.13 | 738 | 0x2E2 | TxPDO7*, Nd.34 | 759 | 0x2F7 | TxPDO7*, Nd.55 |
718 | 0x2CE | TxPDO7*, Nd.14 | 739 | 0x2E3 | TxPDO7*, Nd.35 | 760 | 0x2F8 | TxPDO7*, Nd.56 |
719 | 0x2CF | TxPDO7*, Nd.15 | 740 | 0x2E4 | TxPDO7*, Nd.36 | 761 | 0x2F9 | TxPDO7*, Nd.57 |
720 | 0x2D0 | TxPDO7*, Nd.16 | 741 | 0x2E5 | TxPDO7*, Nd.37 | 762 | 0x2FA | TxPDO7*, Nd.58 |
721 | 0x2D1 | TxPDO7*, Nd.17 | 742 | 0x2E6 | TxPDO7*, Nd.38 | 763 | 0x2FB | TxPDO7*, Nd.59 |
722 | 0x2D2 | TxPDO7*, Nd.18 | 743 | 0x2E7 | TxPDO7*, Nd.39 | 764 | 0x2FC | TxPDO7*, Nd.60 |
723 | 0x2D3 | TxPDO7*, Nd.19 | 744 | 0x2E8 | TxPDO7*, Nd.40 | 765 | 0x2FD | TxPDO7*, Nd.61 |
724 | 0x2D4 | TxPDO7*, Nd.20 | 745 | 0x2E9 | TxPDO7*, Nd.41 | 766 | 0x2FE | TxPDO7*, Nd.62 |
725 | 0x2D5 | TxPDO7*, Nd.21 | 746 | 0x2EA | TxPDO7*, Nd.42 | 767 | 0x2FF | TxPDO7*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
833 | 0x341 | RxPDO7*, Nd.1 | 854 | 0x356 | RxPDO7*, Nd.22 | 875 | 0x36B | RxPDO7*, Nd.43 |
834 | 0x342 | RxPDO7*, Nd.2 | 855 | 0x357 | RxPDO7*, Nd.23 | 876 | 0x36C | RxPDO7*, Nd.44 |
835 | 0x343 | RxPDO7*, Nd.3 | 856 | 0x358 | RxPDO7*, Nd.24 | 877 | 0x36D | RxPDO7*, Nd.45 |
836 | 0x344 | RxPDO7*, Nd.4 | 857 | 0x359 | RxPDO7*, Nd.25 | 878 | 0x36E | RxPDO7*, Nd.46 |
837 | 0x345 | RxPDO7*, Nd.5 | 858 | 0x35A | RxPDO7*, Nd.26 | 879 | 0x36F | RxPDO7*, Nd.47 |
838 | 0x346 | RxPDO7*, Nd.6 | 859 | 0x35B | RxPDO7*, Nd.27 | 880 | 0x370 | RxPDO7*, Nd.48 |
839 | 0x347 | RxPDO7*, Nd.7 | 860 | 0x35C | RxPDO7*, Nd.28 | 881 | 0x371 | RxPDO7*, Nd.49 |
840 | 0x348 | RxPDO7*, Nd.8 | 861 | 0x35D | RxPDO7*, Nd.29 | 882 | 0x372 | RxPDO7*, Nd.50 |
841 | 0x349 | RxPDO7*, Nd.9 | 862 | 0x35E | RxPDO7*, Nd.30 | 883 | 0x373 | RxPDO7*, Nd.51 |
842 | 0x34A | RxPDO7*, Nd.10 | 863 | 0x35F | RxPDO7*, Nd.31 | 884 | 0x374 | RxPDO7*, Nd.52 |
843 | 0x34B | RxPDO7*, Nd.11 | 864 | 0x360 | RxPDO7*, Nd.32 | 885 | 0x375 | RxPDO7*, Nd.53 |
844 | 0x34C | RxPDO7*, Nd.12 | 865 | 0x361 | RxPDO7*, Nd.33 | 886 | 0x376 | RxPDO7*, Nd.54 |
845 | 0x34D | RxPDO7*, Nd.13 | 866 | 0x362 | RxPDO7*, Nd.34 | 887 | 0x377 | RxPDO7*, Nd.55 |
846 | 0x34E | RxPDO7*, Nd.14 | 867 | 0x363 | RxPDO7*, Nd.35 | 888 | 0x378 | RxPDO7*, Nd.56 |
847 | 0x34F | RxPDO7*, Nd.15 | 868 | 0x364 | RxPDO7*, Nd.36 | 889 | 0x379 | RxPDO7*, Nd.57 |
848 | 0x350 | RxPDO7*, Nd.16 | 869 | 0x365 | RxPDO7*, Nd.37 | 890 | 0x37A | RxPDO7*, Nd.58 |
849 | 0x351 | RxPDO7*, Nd.17 | 870 | 0x366 | RxPDO7*, Nd.38 | 891 | 0x37B | RxPDO7*, Nd.59 |
850 | 0x352 | RxPDO7*, Nd.18 | 871 | 0x367 | RxPDO7*, Nd.39 | 892 | 0x37C | RxPDO7*, Nd.60 |
851 | 0x353 | RxPDO7*, Nd.19 | 872 | 0x368 | RxPDO7*, Nd.40 | 893 | 0x37D | RxPDO7*, Nd.61 |
852 | 0x354 | RxPDO7*, Nd.20 | 873 | 0x369 | RxPDO7*, Nd.41 | 894 | 0x37E | RxPDO7*, Nd.62 |
853 | 0x355 | RxPDO7*, Nd.21 | 874 | 0x36A | RxPDO7*, Nd.42 | 895 | 0x37F | RxPDO7*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
961 | 0x3C1 | TxPDO8*, Nd.1 | 982 | 0x3D6 | TxPDO8*, Nd.22 | 1003 | 0x3EB | TxPDO8*, Nd.43 |
962 | 0x3C2 | TxPDO8*, Nd.2 | 983 | 0x3D7 | TxPDO8*, Nd.23 | 1004 | 0x3EC | TxPDO8*, Nd.44 |
963 | 0x3C3 | TxPDO8*, Nd.3 | 984 | 0x3D8 | TxPDO8*, Nd.24 | 1005 | 0x3ED | TxPDO8*, Nd.45 |
964 | 0x3C4 | TxPDO8*, Nd.4 | 985 | 0x3D9 | TxPDO8*, Nd.25 | 1006 | 0x3EE | TxPDO8*, Nd.46 |
965 | 0x3C5 | TxPDO8*, Nd.5 | 986 | 0x3DA | TxPDO8*, Nd.26 | 1007 | 0x3EF | TxPDO8*, Nd.47 |
966 | 0x3C6 | TxPDO8*, Nd.6 | 987 | 0x3DB | TxPDO8*, Nd.27 | 1008 | 0x3F0 | TxPDO8*, Nd.48 |
967 | 0x3C7 | TxPDO8*, Nd.7 | 988 | 0x3DC | TxPDO8*, Nd.28 | 1009 | 0x3F1 | TxPDO8*, Nd.49 |
968 | 0x3C8 | TxPDO8*, Nd.8 | 989 | 0x3DD | TxPDO8*, Nd.29 | 1010 | 0x3F2 | TxPDO8*, Nd.50 |
969 | 0x3C9 | TxPDO8*, Nd.9 | 990 | 0x3DE | TxPDO8*, Nd.30 | 1011 | 0x3F3 | TxPDO8*, Nd.51 |
970 | 0x3CA | TxPDO8*, Nd.10 | 991 | 0x3DF | TxPDO8*, Nd.31 | 1012 | 0x3F4 | TxPDO8*, Nd.52 |
971 | 0x3CB | TxPDO8*, Nd.11 | 992 | 0x3E0 | TxPDO8*, Nd.32 | 1013 | 0x3F5 | TxPDO8*, Nd.53 |
972 | 0x3CC | TxPDO8*, Nd.12 | 993 | 0x3E1 | TxPDO8*, Nd.33 | 1014 | 0x3F6 | TxPDO8*, Nd.54 |
973 | 0x3CD | TxPDO8*, Nd.13 | 994 | 0x3E2 | TxPDO8*, Nd.34 | 1015 | 0x3F7 | TxPDO8*, Nd.55 |
974 | 0x3CE | TxPDO8*, Nd.14 | 995 | 0x3E3 | TxPDO8*, Nd.35 | 1016 | 0x3F8 | TxPDO8*, Nd.56 |
975 | 0x3CF | TxPDO8*, Nd.15 | 996 | 0x3E4 | TxPDO8*, Nd.36 | 1017 | 0x3F9 | TxPDO8*, Nd.57 |
976 | 0x3D0 | TxPDO8*, Nd.16 | 997 | 0x3E5 | TxPDO8*, Nd.37 | 1018 | 0x3FA | TxPDO8*, Nd.58 |
977 | 0x3D1 | TxPDO8*, Nd.17 | 998 | 0x3E6 | TxPDO8*, Nd.38 | 1019 | 0x3FB | TxPDO8*, Nd.59 |
978 | 0x3D2 | TxPDO8*, Nd.18 | 999 | 0x3E7 | TxPDO8*, Nd.39 | 1020 | 0x3FC | TxPDO8*, Nd.60 |
979 | 0x3D3 | TxPDO8*, Nd.19 | 1000 | 0x3E8 | TxPDO8*, Nd.40 | 1021 | 0x3FD | TxPDO8*, Nd.61 |
980 | 0x3D4 | TxPDO8*, Nd.20 | 1001 | 0x3E9 | TxPDO8*, Nd.41 | 1022 | 0x3FE | TxPDO8*, Nd.62 |
981 | 0x3D5 | TxPDO8*, Nd.21 | 1002 | 0x3EA | TxPDO8*, Nd.42 | 1023 | 0x3FF | TxPDO8*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
1089 | 0x441 | RxPDO8*, Nd.1 | 1110 | 0x456 | RxPDO8*, Nd.22 | 1131 | 0x46B | RxPDO8*, Nd.43 |
1090 | 0x442 | RxPDO8*, Nd.2 | 1111 | 0x457 | RxPDO8*, Nd.23 | 1132 | 0x46C | RxPDO8*, Nd.44 |
1091 | 0x443 | RxPDO8*, Nd.3 | 1112 | 0x458 | RxPDO8*, Nd.24 | 1133 | 0x46D | RxPDO8*, Nd.45 |
1092 | 0x444 | RxPDO8*, Nd.4 | 1113 | 0x459 | RxPDO8*, Nd.25 | 1134 | 0x46E | RxPDO8*, Nd.46 |
1093 | 0x445 | RxPDO8*, Nd.5 | 1114 | 0x45A | RxPDO8*, Nd.26 | 1135 | 0x46F | RxPDO8*, Nd.47 |
1094 | 0x446 | RxPDO8*, Nd.6 | 1115 | 0x45B | RxPDO8*, Nd.27 | 1136 | 0x470 | RxPDO8*, Nd.48 |
1095 | 0x447 | RxPDO8*, Nd.7 | 1116 | 0x45C | RxPDO8*, Nd.28 | 1137 | 0x471 | RxPDO8*, Nd.49 |
1096 | 0x448 | RxPDO8*, Nd.8 | 1117 | 0x45D | RxPDO8*, Nd.29 | 1138 | 0x472 | RxPDO8*, Nd.50 |
1097 | 0x449 | RxPDO8*, Nd.9 | 1118 | 0x45E | RxPDO8*, Nd.30 | 1139 | 0x473 | RxPDO8*, Nd.51 |
1098 | 0x44A | RxPDO8*, Nd.10 | 1119 | 0x45F | RxPDO8*, Nd.31 | 1140 | 0x474 | RxPDO8*, Nd.52 |
1099 | 0x44B | RxPDO8*, Nd.11 | 1120 | 0x460 | RxPDO8*, Nd.32 | 1141 | 0x475 | RxPDO8*, Nd.53 |
1100 | 0x44C | RxPDO8*, Nd.12 | 1121 | 0x461 | RxPDO8*, Nd.33 | 1142 | 0x476 | RxPDO8*, Nd.54 |
1101 | 0x44D | RxPDO8*, Nd.13 | 1122 | 0x462 | RxPDO8*, Nd.34 | 1143 | 0x477 | RxPDO8*, Nd.55 |
1102 | 0x44E | RxPDO8*, Nd.14 | 1123 | 0x463 | RxPDO8*, Nd.35 | 1144 | 0x478 | RxPDO8*, Nd.56 |
1103 | 0x44F | RxPDO8*, Nd.15 | 1124 | 0x464 | RxPDO8*, Nd.36 | 1145 | 0x479 | RxPDO8*, Nd.57 |
1104 | 0x450 | RxPDO8*, Nd.16 | 1125 | 0x465 | RxPDO8*, Nd.37 | 1146 | 0x47A | RxPDO8*, Nd.58 |
1105 | 0x451 | RxPDO8*, Nd.17 | 1126 | 0x466 | RxPDO8*, Nd.38 | 1147 | 0x47B | RxPDO8*, Nd.59 |
1106 | 0x452 | RxPDO8*, Nd.18 | 1127 | 0x467 | RxPDO8*, Nd.39 | 1148 | 0x47C | RxPDO8*, Nd.60 |
1107 | 0x453 | RxPDO8*, Nd.19 | 1128 | 0x468 | RxPDO8*, Nd.40 | 1149 | 0x47D | RxPDO8*, Nd.61 |
1108 | 0x454 | RxPDO8*, Nd.20 | 1129 | 0x469 | RxPDO8*, Nd.41 | 1150 | 0x47E | RxPDO8*, Nd.62 |
1109 | 0x455 | RxPDO8*, Nd.21 | 1130 | 0x46A | RxPDO8*, Nd.42 | 1151 | 0x47F | RxPDO8*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
1217 | 0x4C1 | TxPDO9*, Nd.1 | 1238 | 0x4D6 | TxPDO9*, Nd.22 | 1259 | 0x4EB | TxPDO9*, Nd.43 |
1218 | 0x4C2 | TxPDO9*, Nd.2 | 1239 | 0x4D7 | TxPDO9*, Nd.23 | 1260 | 0x4EC | TxPDO9*, Nd.44 |
1219 | 0x4C3 | TxPDO9*, Nd.3 | 1240 | 0x4D8 | TxPDO9*, Nd.24 | 1261 | 0x4ED | TxPDO9*, Nd.45 |
1220 | 0x4C4 | TxPDO9*, Nd.4 | 1241 | 0x4D9 | TxPDO9*, Nd.25 | 1262 | 0x4EE | TxPDO9*, Nd.46 |
1221 | 0x4C5 | TxPDO9*, Nd.5 | 1242 | 0x4DA | TxPDO9*, Nd.26 | 1263 | 0x4EF | TxPDO9*, Nd.47 |
1222 | 0x4C6 | TxPDO9*, Nd.6 | 1243 | 0x4DB | TxPDO9*, Nd.27 | 1264 | 0x4F0 | TxPDO9*, Nd.48 |
1223 | 0x4C7 | TxPDO9*, Nd.7 | 1244 | 0x4DC | TxPDO9*, Nd.28 | 1265 | 0x4F1 | TxPDO9*, Nd.49 |
1224 | 0x4C8 | TxPDO9*, Nd.8 | 1245 | 0x4DD | TxPDO9*, Nd.29 | 1266 | 0x4F2 | TxPDO9*, Nd.50 |
1225 | 0x4C9 | TxPDO9*, Nd.9 | 1246 | 0x4DE | TxPDO9*, Nd.30 | 1267 | 0x4F3 | TxPDO9*, Nd.51 |
1226 | 0x4CA | TxPDO9*, Nd.10 | 1247 | 0x4DF | TxPDO9*, Nd.31 | 1268 | 0x4F4 | TxPDO9*, Nd.52 |
1227 | 0x4CB | TxPDO9*, Nd.11 | 1248 | 0x4E0 | TxPDO9*, Nd.32 | 1269 | 0x4F5 | TxPDO9*, Nd.53 |
1228 | 0x4CC | TxPDO9*, Nd.12 | 1249 | 0x4E1 | TxPDO9*, Nd.33 | 1270 | 0x4F6 | TxPDO9*, Nd.54 |
1229 | 0x4CD | TxPDO9*, Nd.13 | 1250 | 0x4E2 | TxPDO9*, Nd.34 | 1271 | 0x4F7 | TxPDO9*, Nd.55 |
1230 | 0x4CE | TxPDO9*, Nd.14 | 1251 | 0x4E3 | TxPDO9*, Nd.35 | 1272 | 0x4F8 | TxPDO9*, Nd.56 |
1231 | 0x4CF | TxPDO9*, Nd.15 | 1252 | 0x4E4 | TxPDO9*, Nd.36 | 1273 | 0x4F9 | TxPDO9*, Nd.57 |
1232 | 0x4D0 | TxPDO9*, Nd.16 | 1253 | 0x4E5 | TxPDO9*, Nd.37 | 1274 | 0x4FA | TxPDO9*, Nd.58 |
1233 | 0x4D1 | TxPDO9*, Nd.17 | 1254 | 0x4E6 | TxPDO9*, Nd.38 | 1275 | 0x4FB | TxPDO9*, Nd.59 |
1234 | 0x4D2 | TxPDO9*, Nd.18 | 1255 | 0x4E7 | TxPDO9*, Nd.39 | 1276 | 0x4FC | TxPDO9*, Nd.60 |
1235 | 0x4D3 | TxPDO9*, Nd.19 | 1256 | 0x4E8 | TxPDO9*, Nd.40 | 1277 | 0x4FD | TxPDO9*, Nd.61 |
1236 | 0x4D4 | TxPDO9*, Nd.20 | 1257 | 0x4E9 | TxPDO9*, Nd.41 | 1278 | 0x4FE | TxPDO9*, Nd.62 |
1237 | 0x4D5 | TxPDO9*, Nd.21 | 1258 | 0x4EA | TxPDO9*, Nd.42 | 1279 | 0x4FF | TxPDO9*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
1345 | 0x541 | RxPDO9*, Nd.1 | 1366 | 0x556 | RxPDO9*, Nd.22 | 1387 | 0x56B | RxPDO9*, Nd.43 |
1346 | 0x542 | RxPDO9*, Nd.2 | 1367 | 0x557 | RxPDO9*, Nd.23 | 1388 | 0x56C | RxPDO9*, Nd.44 |
1347 | 0x543 | RxPDO9*, Nd.3 | 1368 | 0x558 | RxPDO9*, Nd.24 | 1389 | 0x56D | RxPDO9*, Nd.45 |
1348 | 0x544 | RxPDO9*, Nd.4 | 1369 | 0x559 | RxPDO9*, Nd.25 | 1390 | 0x56E | RxPDO9*, Nd.46 |
1349 | 0x545 | RxPDO9*, Nd.5 | 1370 | 0x55A | RxPDO9*, Nd.26 | 1391 | 0x56F | RxPDO9*, Nd.47 |
1350 | 0x546 | RxPDO9*, Nd.6 | 1371 | 0x55B | RxPDO9*, Nd.27 | 1392 | 0x570 | RxPDO9*, Nd.48 |
1351 | 0x547 | RxPDO9*, Nd.7 | 1372 | 0x55C | RxPDO9*, Nd.28 | 1393 | 0x571 | RxPDO9*, Nd.49 |
1352 | 0x548 | RxPDO9*, Nd.8 | 1373 | 0x55D | RxPDO9*, Nd.29 | 1394 | 0x572 | RxPDO9*, Nd.50 |
1353 | 0x549 | RxPDO9*, Nd.9 | 1374 | 0x55E | RxPDO9*, Nd.30 | 1395 | 0x573 | RxPDO9*, Nd.51 |
1354 | 0x54A | RxPDO9*, Nd.10 | 1375 | 0x55F | RxPDO9*, Nd.31 | 1396 | 0x574 | RxPDO9*, Nd.52 |
1355 | 0x54B | RxPDO9*, Nd.11 | 1376 | 0x560 | RxPDO9*, Nd.32 | 1397 | 0x575 | RxPDO9*, Nd.53 |
1356 | 0x54C | RxPDO9*, Nd.12 | 1377 | 0x561 | RxPDO9*, Nd.33 | 1398 | 0x576 | RxPDO9*, Nd.54 |
1357 | 0x54D | RxPDO9*, Nd.13 | 1378 | 0x562 | RxPDO9*, Nd.34 | 1399 | 0x577 | RxPDO9*, Nd.55 |
1358 | 0x54E | RxPDO9*, Nd.14 | 1379 | 0x563 | RxPDO9*, Nd.35 | 1400 | 0x578 | RxPDO9*, Nd.56 |
1359 | 0x54F | RxPDO9*, Nd.15 | 1380 | 0x564 | RxPDO9*, Nd.36 | 1401 | 0x579 | RxPDO9*, Nd.57 |
1360 | 0x550 | RxPDO9*, Nd.16 | 1381 | 0x565 | RxPDO9*, Nd.37 | 1402 | 0x57A | RxPDO9*, Nd.58 |
1361 | 0x551 | RxPDO9*, Nd.17 | 1382 | 0x566 | RxPDO9*, Nd.38 | 1403 | 0x57B | RxPDO9*, Nd.59 |
1362 | 0x552 | RxPDO9*, Nd.18 | 1383 | 0x567 | RxPDO9*, Nd.39 | 1404 | 0x57C | RxPDO9*, Nd.60 |
1363 | 0x553 | RxPDO9*, Nd.19 | 1384 | 0x568 | RxPDO9*, Nd.40 | 1405 | 0x57D | RxPDO9*, Nd.61 |
1364 | 0x554 | RxPDO9*, Nd.20 | 1385 | 0x569 | RxPDO9*, Nd.41 | 1406 | 0x57E | RxPDO9*, Nd.62 |
1365 | 0x555 | RxPDO9*, Nd.21 | 1386 | 0x56A | RxPDO9*, Nd.42 | 1407 | 0x57F | RxPDO9*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
1473 | 0x5C1 | TxPDO10*, Nd.1 | 1494 | 0x5D6 | TxPDO10*, Nd.22 | 1515 | 0x5EB | TxPDO10*, Nd.43 |
1474 | 0x5C2 | TxPDO10*, Nd.2 | 1495 | 0x5D7 | TxPDO10*, Nd.23 | 1516 | 0x5EC | TxPDO10*, Nd.44 |
1475 | 0x5C3 | TxPDO10*, Nd.3 | 1496 | 0x5D8 | TxPDO10*, Nd.24 | 1517 | 0x5ED | TxPDO10*, Nd.45 |
1476 | 0x5C4 | TxPDO10*, Nd.4 | 1497 | 0x5D9 | TxPDO10*, Nd.25 | 1518 | 0x5EE | TxPDO10*, Nd.46 |
1477 | 0x5C5 | TxPDO10*, Nd.5 | 1498 | 0x5DA | TxPDO10*, Nd.26 | 1519 | 0x5EF | TxPDO10*, Nd.47 |
1478 | 0x5C6 | TxPDO10*, Nd.6 | 1499 | 0x5DB | TxPDO10*, Nd.27 | 1520 | 0x5F0 | TxPDO10*, Nd.48 |
1479 | 0x5C7 | TxPDO10*, Nd.7 | 1500 | 0x5DC | TxPDO10*, Nd.28 | 1521 | 0x5F1 | TxPDO10*, Nd.49 |
1480 | 0x5C8 | TxPDO10*, Nd.8 | 1501 | 0xDE | TxPDO10*, Nd.29 | 1522 | 0x5F2 | TxPDO10*, Nd.50 |
1481 | 0x5C9 | TxPDO10*, Nd.9 | 1502 | 0x5DE | TxPDO10*, Nd.30 | 1523 | 0x5F3 | TxPDO10*, Nd.51 |
1482 | 0x5CA | TxPDO10*, Nd.10 | 1503 | 0x5DF | TxPDO10*, Nd.31 | 1524 | 0x5F4 | TxPDO10*, Nd.52 |
1483 | 0x5CB | TxPDO10*, Nd.11 | 1504 | 0x5E0 | TxPDO10*, Nd.32 | 1525 | 0x5F5 | TxPDO10*, Nd.53 |
1484 | 0x5CC | TxPDO10*, Nd.12 | 1505 | 0x5E1 | TxPDO10*, Nd.33 | 1526 | 0x5F6 | TxPDO10*, Nd.54 |
1485 | 0x5CD | TxPDO10*, Nd.13 | 1506 | 0x5E2 | TxPDO10*, Nd.34 | 1527 | 0x5F7 | TxPDO10*, Nd.55 |
1486 | 0x5CE | TxPDO10*, Nd.14 | 1507 | 0x5E3 | TxPDO10*, Nd.35 | 1528 | 0x5F8 | TxPDO10*, Nd.56 |
1487 | 0x5CF | TxPDO10*, Nd.15 | 1508 | 0x5E4 | TxPDO10*, Nd.36 | 1529 | 0x5F9 | TxPDO10*, Nd.57 |
1488 | 0x5D0 | TxPDO10*, Nd.16 | 1509 | 0x5E5 | TxPDO10*, Nd.37 | 1530 | 0x5FA | TxPDO10*, Nd.58 |
1489 | 0x5D1 | TxPDO10*, Nd.17 | 1510 | 0x5E6 | TxPDO10*, Nd.38 | 1531 | 0x5FB | TxPDO10*, Nd.59 |
1490 | 0x5D2 | TxPDO10*, Nd.18 | 1511 | 0x5E7 | TxPDO10*, Nd.39 | 1532 | 0x5FC | TxPDO10*, Nd.60 |
1491 | 0x5D3 | TxPDO10*, Nd.19 | 1512 | 0x5E8 | TxPDO10*, Nd.40 | 1533 | 0x5FD | TxPDO10*, Nd.61 |
1492 | 0x5D4 | TxPDO10*, Nd.20 | 1513 | 0x5E9 | TxPDO10*, Nd.41 | 1534 | 0x5FE | TxPDO10*, Nd.62 |
1493 | 0x5D5 | TxPDO10*, Nd.21 | 1514 | 0x5EA | TxPDO10*, Nd.42 | 1535 | 0x5FF | TxPDO10*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
1601 | 0x641 | RxPDO10*, Nd.1 | 1622 | 0x656 | RxPDO10*, Nd.22 | 1643 | 0x66B | RxPDO10*, Nd.43 |
1602 | 0x642 | RxPDO10*, Nd.2 | 1623 | 0x657 | RxPDO10*, Nd.23 | 1644 | 0x66C | RxPDO10*, Nd.44 |
1603 | 0x643 | RxPDO10*, Nd.3 | 1624 | 0x658 | RxPDO10*, Nd.24 | 1645 | 0x66D | RxPDO10*, Nd.45 |
1604 | 0x644 | RxPDO10*, Nd.4 | 1625 | 0x659 | RxPDO10*, Nd.25 | 1646 | 0x66E | RxPDO10*, Nd.46 |
1605 | 0x645 | RxPDO10*, Nd.5 | 1626 | 0x65A | RxPDO10*, Nd.26 | 1647 | 0x66F | RxPDO10*, Nd.47 |
1606 | 0x646 | RxPDO10*, Nd.6 | 1627 | 0x65B | RxPDO10*, Nd.27 | 1648 | 0x670 | RxPDO10*, Nd.48 |
1607 | 0x647 | RxPDO10*, Nd.7 | 1628 | 0x65C | RxPDO10*, Nd.28 | 1649 | 0x671 | RxPDO10*, Nd.49 |
1608 | 0x648 | RxPDO10*, Nd.8 | 1629 | 0x65D | RxPDO10*, Nd.29 | 1650 | 0x672 | RxPDO10*, Nd.50 |
1609 | 0x649 | RxPDO10*, Nd.9 | 1630 | 0x65E | RxPDO10*, Nd.30 | 1651 | 0x673 | RxPDO10*, Nd.51 |
1610 | 0x64A | RxPDO10*, Nd.10 | 1631 | 0x65F | RxPDO10*, Nd.31 | 1652 | 0x674 | RxPDO10*, Nd.52 |
1611 | 0x64B | RxPDO10*, Nd.11 | 1632 | 0x660 | RxPDO10*, Nd.32 | 1653 | 0x675 | RxPDO10*, Nd.53 |
1612 | 0x64C | RxPDO10*, Nd.12 | 1633 | 0x661 | RxPDO10*, Nd.33 | 1654 | 0x676 | RxPDO10*, Nd.54 |
1613 | 0x64D | RxPDO10*, Nd.13 | 1634 | 0x662 | RxPDO10*, Nd.34 | 1655 | 0x677 | RxPDO10*, Nd.55 |
1614 | 0x64E | RxPDO10*, Nd.14 | 1635 | 0x663 | RxPDO10*, Nd.35 | 1656 | 0x678 | RxPDO10*, Nd.56 |
1615 | 0x64F | RxPDO10*, Nd.15 | 1636 | 0x664 | RxPDO10*, Nd.36 | 1657 | 0x679 | RxPDO10*, Nd.57 |
1616 | 0x650 | RxPDO10*, Nd.16 | 1637 | 0x665 | RxPDO10*, Nd.37 | 1658 | 0x67A | RxPDO10*, Nd.58 |
1617 | 0x651 | RxPDO10*, Nd.17 | 1638 | 0x666 | RxPDO10*, Nd.38 | 1659 | 0x67B | RxPDO10*, Nd.59 |
1618 | 0x652 | RxPDO10*, Nd.18 | 1639 | 0x667 | RxPDO10*, Nd.39 | 1660 | 0x67C | RxPDO10*, Nd.60 |
1619 | 0x653 | RxPDO10*, Nd.19 | 1640 | 0x668 | RxPDO10*, Nd.40 | 1661 | 0x67D | RxPDO10*, Nd.61 |
1620 | 0x654 | RxPDO10*, Nd.20 | 1641 | 0x669 | RxPDO10*, Nd.41 | 1662 | 0x67E | RxPDO10*, Nd.62 |
1621 | 0x655 | RxPDO10*, Nd.21 | 1642 | 0x66A | RxPDO10*, Nd.42 | 1663 | 0x67F | RxPDO10*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
1729 | 0x6C1 | TxPDO11*, Nd.1 | 1750 | 0x6D6 | TxPDO11*, Nd.22 | 1771 | 0x6EB | TxPDO11*, Nd.43 |
1730 | 0x6C2 | TxPDO11*, Nd.2 | 1751 | 0x6D7 | TxPDO11*, Nd.23 | 1772 | 0x6EC | TxPDO11*, Nd.44 |
1731 | 0x6C3 | TxPDO11*, Nd.3 | 1752 | 0x6D8 | TxPDO11*, Nd.24 | 1773 | 0x6ED | TxPDO11*, Nd.45 |
1732 | 0x6C4 | TxPDO11*, Nd.4 | 1753 | 0x6D9 | TxPDO11*, Nd.25 | 1774 | 0x6EE | TxPDO11*, Nd.46 |
1733 | 0x6C5 | TxPDO11*, Nd.5 | 1754 | 0x6DA | TxPDO11*, Nd.26 | 1775 | 0x6EF | TxPDO11*, Nd.47 |
1734 | 0x6C6 | TxPDO11*, Nd.6 | 1755 | 0x6DB | TxPDO11*, Nd.27 | 1776 | 0x6F0 | TxPDO11*, Nd.48 |
1735 | 0x6C7 | TxPDO11*, Nd.7 | 1756 | 0x6DC | TxPDO11*, Nd.28 | 1777 | 0x6F1 | TxPDO11*, Nd.49 |
1736 | 0x6C8 | TxPDO11*, Nd.8 | 1757 | 0x6DD | TxPDO11*, Nd.29 | 1778 | 0x6F2 | TxPDO11*, Nd.50 |
1737 | 0x6C9 | TxPDO11*, Nd.9 | 1758 | 0x6DE | TxPDO11*, Nd.30 | 1779 | 0x6F3 | TxPDO11*, Nd.51 |
1738 | 0x6CA | TxPDO11*, Nd.10 | 1759 | 0x6DF | TxPDO11*, Nd.31 | 1780 | 0x6F4 | TxPDO11*, Nd.52 |
1739 | 0x6CB | TxPDO11*, Nd.11 | 1760 | 0x6E0 | TxPDO11*, Nd.32 | 1781 | 0x6F5 | TxPDO11*, Nd.53 |
1740 | 0x6CC | TxPDO11*, Nd.12 | 1761 | 0x6E1 | TxPDO11*, Nd.33 | 1782 | 0x6F6 | TxPDO11*, Nd.54 |
1741 | 0x6CD | TxPDO11*, Nd.13 | 1762 | 0x6E2 | TxPDO11*, Nd.34 | 1783 | 0x6F7 | TxPDO11*, Nd.55 |
1742 | 0x6CE | TxPDO11*, Nd.14 | 1763 | 0x6E3 | TxPDO11*, Nd.35 | 1784 | 0x6F8 | TxPDO11*, Nd.56 |
1743 | 0x6CF | TxPDO11*, Nd.15 | 1764 | 0x6E4 | TxPDO11*, Nd.36 | 1785 | 0x6F9 | TxPDO11*, Nd.57 |
1744 | 0x6D0 | TxPDO11*, Nd.16 | 1765 | 0x6E5 | TxPDO11*, Nd.37 | 1786 | 0x6FA | TxPDO11*, Nd.58 |
1745 | 0x6D1 | TxPDO11*, Nd.17 | 1766 | 0x6E6 | TxPDO11*, Nd.38 | 1787 | 0x6FB | TxPDO11*, Nd.59 |
1746 | 0x6D2 | TxPDO11*, Nd.18 | 1767 | 0x6E7 | TxPDO11*, Nd.39 | 1788 | 0x6FC | TxPDO11*, Nd.60 |
1747 | 0x6D3 | TxPDO11*, Nd.19 | 1768 | 0x6E8 | TxPDO11*, Nd.40 | 1789 | 0x6FD | TxPDO11*, Nd.61 |
1748 | 0x6D4 | TxPDO11*, Nd.20 | 1769 | 0x6E9 | TxPDO11*, Nd.41 | 1790 | 0x6FE | TxPDO11*, Nd.62 |
1749 | 0x6D5 | TxPDO11*, Nd.21 | 1770 | 0x6EA | TxPDO11*, Nd.42 | 1791 | 0x6FF | TxPDO11*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
1857 | 0x741 | RxPDO11*, Nd.1 | 1878 | 0x756 | RxPDO11*, Nd.22 | 1899 | 0x76B | RxPDO11*, Nd.43 |
1858 | 0x742 | RxPDO11*, Nd.2 | 1879 | 0x757 | RxPDO11*, Nd.23 | 1900 | 0x76C | RxPDO11*, Nd.44 |
1859 | 0x743 | RxPDO11*, Nd.3 | 1880 | 0x758 | RxPDO11*, Nd.24 | 1901 | 0x76D | RxPDO11*, Nd.45 |
1860 | 0x744 | RxPDO11*, Nd.4 | 1881 | 0x759 | RxPDO11*, Nd.25 | 1902 | 0x76E | RxPDO11*, Nd.46 |
1861 | 0x745 | RxPDO11*, Nd.5 | 1882 | 0x75A | RxPDO11*, Nd.26 | 1903 | 0x76F | RxPDO11*, Nd.47 |
1862 | 0x746 | RxPDO11*, Nd.6 | 1883 | 0x75B | RxPDO11*, Nd.27 | 1904 | 0x770 | RxPDO11*, Nd.48 |
1863 | 0x747 | RxPDO11*, Nd.7 | 1884 | 0x75C | RxPDO11*, Nd.28 | 1905 | 0x771 | RxPDO11*, Nd.49 |
1864 | 0x748 | RxPDO11*, Nd.8 | 1885 | 0x75D | RxPDO11*, Nd.29 | 1906 | 0x772 | RxPDO11*, Nd.50 |
1865 | 0x749 | RxPDO11*, Nd.9 | 1886 | 0x75E | RxPDO11*, Nd.30 | 1907 | 0x773 | RxPDO11*, Nd.51 |
1866 | 0x74A | RxPDO11*, Nd.10 | 1887 | 0x75F | RxPDO11*, Nd.31 | 1908 | 0x774 | RxPDO11*, Nd.52 |
1867 | 0x74B | RxPDO11*, Nd.11 | 1888 | 0x760 | RxPDO11*, Nd.32 | 1909 | 0x775 | RxPDO11*, Nd.53 |
1868 | 0x74C | RxPDO11*, Nd.12 | 1889 | 0x761 | RxPDO11*, Nd.33 | 1910 | 0x776 | RxPDO11*, Nd.54 |
1869 | 0x74D | RxPDO11*, Nd.13 | 1890 | 0x762 | RxPDO11*, Nd.34 | 1911 | 0x777 | RxPDO11*, Nd.55 |
1870 | 0x74E | RxPDO11*, Nd.14 | 1891 | 0x763 | RxPDO11*, Nd.35 | 1912 | 0x778 | RxPDO11*, Nd.56 |
1871 | 0x74F | RxPDO11*, Nd.15 | 1892 | 0x764 | RxPDO11*, Nd.36 | 1913 | 0x779 | RxPDO11*, Nd.57 |
1872 | 0x750 | RxPDO11*, Nd.16 | 1893 | 0x765 | RxPDO11*, Nd.37 | 1914 | 0x77A | RxPDO11*, Nd.58 |
1873 | 0x751 | RxPDO11*, Nd.17 | 1894 | 0x766 | RxPDO11*, Nd.38 | 1915 | 0x77B | RxPDO11*, Nd.59 |
1874 | 0x752 | RxPDO11*, Nd.18 | 1895 | 0x767 | RxPDO11*, Nd.39 | 1916 | 0x77C | RxPDO11*, Nd.60 |
1875 | 0x753 | RxPDO11*, Nd.19 | 1896 | 0x768 | RxPDO11*, Nd.40 | 1917 | 0x77D | RxPDO11*, Nd.61 |
1876 | 0x754 | RxPDO11*, Nd.20 | 1897 | 0x769 | RxPDO11*, Nd.41 | 1918 | 0x77E | RxPDO11*, Nd.62 |
1877 | 0x755 | RxPDO11*, Nd.21 | 1898 | 0x76A | RxPDO11*, Nd.42 | 1919 | 0x77F | RxPDO11*, Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
1409 | 0x581 | SDO Tx Nd.1 | 1430 | 0x596 | SDO Tx Nd.22 | 1451 | 0x5AB | SDO Tx Nd.43 |
1410 | 0x582 | SDO Tx Nd.2 | 1431 | 0x597 | SDO Tx Nd.23 | 1452 | 0x5AC | SDO Tx Nd.44 |
1411 | 0x583 | SDO Tx Nd.3 | 1432 | 0x598 | SDO Tx Nd.24 | 1453 | 0x5AD | SDO Tx Nd.45 |
1412 | 0x584 | SDO Tx Nd.4 | 1433 | 0x599 | SDO Tx Nd.25 | 1454 | 0x5AE | SDO Tx Nd.46 |
1413 | 0x585 | SDO Tx Nd.5 | 1434 | 0x59A | SDO Tx Nd.26 | 1455 | 0x5AF | SDO Tx Nd.47 |
1414 | 0x586 | SDO Tx Nd.6 | 1435 | 0x59B | SDO Tx Nd.27 | 1456 | 0x5B0 | SDO Tx Nd.48 |
1415 | 0x587 | SDO Tx Nd.7 | 1436 | 0x59C | SDO Tx Nd.28 | 1457 | 0x5B1 | SDO Tx Nd.49 |
1416 | 0x588 | SDO Tx Nd.8 | 1437 | 0x59D | SDO Tx Nd.29 | 1458 | 0x5B2 | SDO Tx Nd.50 |
1417 | 0x589 | SDO Tx Nd.9 | 1438 | 0x59E | SDO Tx Nd.30 | 1459 | 0x5B3 | SDO Tx Nd.51 |
1418 | 0x58A | SDO Tx Nd.10 | 1439 | 0x59F | SDO Tx Nd.31 | 1460 | 0x5B4 | SDO Tx Nd.52 |
1419 | 0x58B | SDO Tx Nd.11 | 1440 | 0x5A0 | SDO Tx Nd.32 | 1461 | 0x5B5 | SDO Tx Nd.53 |
1420 | 0x58C | SDO Tx Nd.12 | 1441 | 0x5A1 | SDO Tx Nd.33 | 1462 | 0x5B6 | SDO Tx Nd.54 |
1421 | 0x58D | SDO Tx Nd.13 | 1442 | 0x5A2 | SDO Tx Nd.34 | 1463 | 0x5B7 | SDO Tx Nd.55 |
1422 | 0x58E | SDO Tx Nd.14 | 1443 | 0x5A3 | SDO Tx Nd.35 | 1464 | 0x5B8 | SDO Tx Nd.56 |
1423 | 0x58F | SDO Tx Nd.15 | 1444 | 0x5A4 | SDO Tx Nd.36 | 1465 | 0x5B9 | SDO Tx Nd.57 |
1424 | 0x590 | SDO Tx Nd.16 | 1445 | 0x5A5 | SDO Tx Nd.37 | 1466 | 0x5BA | SDO Tx Nd.58 |
1425 | 0x591 | SDO Tx Nd.17 | 1446 | 0x5A6 | SDO Tx Nd.38 | 1467 | 0x5BB | SDO Tx Nd.59 |
1426 | 0x592 | SDO Tx Nd.18 | 1447 | 0x5A7 | SDO Tx Nd.39 | 1468 | 0x5BC | SDO Tx Nd.60 |
1427 | 0x593 | SDO Tx Nd.19 | 1448 | 0x5A8 | SDO Tx Nd.40 | 1469 | 0x5BD | SDO Tx Nd.61 |
1428 | 0x594 | SDO Tx Nd.20 | 1449 | 0x5A9 | SDO Tx Nd.41 | 1470 | 0x5BE | SDO Tx Nd.62 |
1429 | 0x595 | SDO Tx Nd.21 | 1450 | 0x5AA | SDO Tx Nd.42 | 1471 | 0x5BF | SDO Tx Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
1537 | 0x601 | SDO Rx Nd.1 | 1558 | 0x616 | SDO Rx Nd.22 | 1579 | 0x62B | SDO Rx Nd.43 |
1538 | 0x602 | SDO Rx Nd.2 | 1559 | 0x617 | SDO Rx Nd.23 | 1580 | 0x62C | SDO Rx Nd.44 |
1539 | 0x603 | SDO Rx Nd.3 | 1560 | 0x618 | SDO Rx Nd.24 | 1581 | 0x62D | SDO Rx Nd.45 |
1540 | 0x604 | SDO Rx Nd.4 | 1561 | 0x619 | SDO Rx Nd.25 | 1582 | 0x62E | SDO Rx Nd.46 |
1541 | 0x605 | SDO Rx Nd.5 | 1562 | 0x61A | SDO Rx Nd.26 | 1583 | 0x62F | SDO Rx Nd.47 |
1542 | 0x606 | SDO Rx Nd.6 | 1563 | 0x61B | SDO Rx Nd.27 | 1584 | 0x630 | SDO Rx Nd.48 |
1543 | 0x607 | SDO Rx Nd.7 | 1564 | 0x61C | SDO Rx Nd.28 | 1585 | 0x631 | SDO Rx Nd.49 |
1544 | 0x608 | SDO Rx Nd.8 | 1565 | 0x61D | SDO Rx Nd.29 | 1586 | 0x632 | SDO Rx Nd.50 |
1545 | 0x609 | SDO Rx Nd.9 | 1566 | 0x61E | SDO Rx Nd.30 | 1587 | 0x633 | SDO Rx Nd.51 |
1546 | 0x60A | SDO Rx Nd.10 | 1567 | 0x61F | SDO Rx Nd.31 | 1588 | 0x634 | SDO Rx Nd.52 |
1547 | 0x60B | SDO Rx Nd.11 | 1568 | 0x620 | SDO Rx Nd.32 | 1589 | 0x635 | SDO Rx Nd.53 |
1548 | 0x60C | SDO Rx Nd.12 | 1569 | 0x621 | SDO Rx Nd.33 | 1590 | 0x636 | SDO Rx Nd.54 |
1549 | 0x60D | SDO Rx Nd.13 | 1570 | 0x622 | SDO Rx Nd.34 | 1591 | 0x637 | SDO Rx Nd.55 |
1550 | 0x60E | SDO Rx Nd.14 | 1571 | 0x623 | SDO Rx Nd.35 | 1592 | 0x638 | SDO Rx Nd.56 |
1551 | 0x60F | SDO Rx Nd.15 | 1572 | 0x624 | SDO Rx Nd.36 | 1593 | 0x639 | SDO Rx Nd.57 |
1552 | 0x610 | SDO Rx Nd.16 | 1573 | 0x625 | SDO Rx Nd.37 | 1594 | 0x63A | SDO Rx Nd.58 |
1553 | 0x611 | SDO Rx Nd.17 | 1574 | 0x626 | SDO Rx Nd.38 | 1595 | 0x63B | SDO Rx Nd.59 |
1554 | 0x612 | SDO Rx Nd.18 | 1575 | 0x627 | SDO Rx Nd.39 | 1596 | 0x63C | SDO Rx Nd.60 |
1555 | 0x613 | SDO Rx Nd.19 | 1576 | 0x628 | SDO Rx Nd.40 | 1597 | 0x63D | SDO Rx Nd.61 |
1556 | 0x614 | SDO Rx Nd.20 | 1577 | 0x629 | SDO Rx Nd.41 | 1598 | 0x63E | SDO Rx Nd.62 |
1557 | 0x615 | SDO Rx Nd.21 | 1578 | 0x62A | SDO Rx Nd.42 | 1599 | 0x63F | SDO Rx Nd.63 |
dec | hex | Telegram type | dec | hex | Telegram type | dec | hex | Telegram type |
|---|---|---|---|---|---|---|---|---|
1793 | 0x701 | Guarding Nd.1 | 1814 | 0x716 | Guarding Nd.22 | 1835 | 0x72B | Guarding Nd.43 |
1794 | 0x702 | Guarding Nd.2 | 1815 | 0x717 | Guarding Nd.23 | 1836 | 0x72C | Guarding Nd.44 |
1795 | 0x703 | Guarding Nd.3 | 1816 | 0x718 | Guarding Nd.24 | 1837 | 0x72D | Guarding Nd.45 |
1796 | 0x704 | Guarding Nd.4 | 1817 | 0x719 | Guarding Nd.25 | 1838 | 0x72E | Guarding Nd.46 |
1797 | 0x705 | Guarding Nd.5 | 1818 | 0x71A | Guarding Nd.26 | 1839 | 0x72F | Guarding Nd.47 |
1798 | 0x706 | Guarding Nd.6 | 1819 | 0x71B | Guarding Nd.27 | 1840 | 0x730 | Guarding Nd.48 |
1799 | 0x707 | Guarding Nd.7 | 1820 | 0x71C | Guarding Nd.28 | 1841 | 0x731 | Guarding Nd.49 |
1800 | 0x708 | Guarding Nd.8 | 1821 | 0x71D | Guarding Nd.29 | 1842 | 0x732 | Guarding Nd.50 |
1801 | 0x709 | Guarding Nd.9 | 1822 | 0x71E | Guarding Nd.30 | 1843 | 0x733 | Guarding Nd.51 |
1802 | 0x70A | Guarding Nd.10 | 1823 | 0x71F | Guarding Nd.31 | 1844 | 0x734 | Guarding Nd.52 |
1803 | 0x70B | Guarding Nd.11 | 1824 | 0x720 | Guarding Nd.32 | 1845 | 0x735 | Guarding Nd.53 |
1804 | 0x70C | Guarding Nd.12 | 1825 | 0x721 | Guarding Nd.33 | 1846 | 0x736 | Guarding Nd.54 |
1805 | 0x70D | Guarding Nd.13 | 1826 | 0x722 | Guarding Nd.34 | 1847 | 0x737 | Guarding Nd.55 |
1806 | 0x70E | Guarding Nd.14 | 1827 | 0x723 | Guarding Nd.35 | 1848 | 0x738 | Guarding Nd.56 |
1807 | 0x70F | Guarding Nd.15 | 1828 | 0x724 | Guarding Nd.36 | 1849 | 0x739 | Guarding Nd.57 |
1808 | 0x710 | Guarding Nd.16 | 1829 | 0x725 | Guarding Nd.37 | 1850 | 0x73A | Guarding Nd.58 |
1809 | 0x711 | Guarding Nd.17 | 1830 | 0x726 | Guarding Nd.38 | 1851 | 0x73B | Guarding Nd.59 |
1810 | 0x712 | Guarding Nd.18 | 1831 | 0x727 | Guarding Nd.39 | 1852 | 0x73C | Guarding Nd.60 |
1811 | 0x713 | Guarding Nd.19 | 1832 | 0x728 | Guarding Nd.40 | 1853 | 0x73D | Guarding Nd.61 |
1812 | 0x714 | Guarding Nd.20 | 1833 | 0x729 | Guarding Nd.41 | 1854 | 0x73E | Guarding Nd.62 |
1813 | 0x715 | Guarding Nd.21 | 1834 | 0x72A | Guarding Nd.42 | 1855 | 0x73F | Guarding Nd.63 |