Configuration - IL230x-B31x
Parameter data for the IL230x-B31x
Settings
 
Parameter data  | Denomination  | 
|---|---|
DPV1-Services  | |
IP-Link-Error  | Reaction to IP-Link  | 
IP Module diagnosis  | |
Data format  | |
Updating of process image  | |
Reaction on DP-Error  | |
IP-Link-Error-Reaction  | IP-Link error reaction  | 
IL/IE23xx Byte-Align  | Mapping of the 4 DI / DO (IL/IE23xx) modules  | 
Configuration of the IL230x-B31x module with only digital inputs and outputs
Example:
 1 x IL2301-B310
 4 x IE1001
 5 x IE2001
 The sum total of digital bytes must be added together and entered.
 
Example:
 1 x IL2301-B310
 4 x IE1001
 5 x IE2001
The same configuration can also be created as follows. The advantage of this method is that each byte receives a different address, and if a digital extension module is inserted, the addresses of the other modules are not shifted. A maximum of 64 modules can be inserted (slots 0-63)
 
Configuration of the IL230x-B31x module with complex and digital inputs and outputs
Complex modules are the first to be mapped into the process image. For this reason all the complex modules must be entered in the sequence in which they are attached to the IP-Link. Finally the digital signals must be rounded up to a byte.
Example:
 1 x IL2301-B310
 1 x IE3102 compact mapping
Example:
 1 x IL2301-B310
 1 x IE3102 complex mapping