Feature register (R32) IP/IE3202

The module's fundamental settings can be modified in the feature register.

Write protection must first be cancelled in the code-word register before it is possible to write into this register  (default: 0x0106).

Notice

Attention

2-, 3- or 4-wire connection has to be the same in the registers of all four channels.

 

Bit

Value

Description

Manufacturer’s setting

0

0bin

User scaling is inactive

0bin

1bin

User scaling is active (registers 33, 34)

1

0bin

Manufacturer scaling is inactive

1bin

1bin

Manufacturer scaling is active (registers 19, 20)

2

0bin

no function

0bin

3

0bin

Sign-amount representation is inactive

0bin

1bin

Sign-amount representation is active

4

0bin

Hide Siemens extension bits

0bin

1bin

Reveal Siemens extension bits

5

0bin

no function

0bin

6

0bin

no function

0bin

7

0bin

Deactivate manual filter setting in register 37

0bin

1bin

Activate manual filter setting in register 37

8

0bin

Deactivate over range protection

1bin

1bin

Activate over range protection
If the temperature exceeds 850°C the status bits are correspondingly set and the output value is restricted to 850°C.

10... 9

00bin

Four-wire connection is activated (Attention: this has to be same for all four channels)

00bin

01bin

Three-wire connection is activated* (Attention: this has to be same for all four channels)

10bin

Two-wire connection is activated (Attention: this has to be same for all four channels)

11

0bin

no function

0bin

15...12

0hex

PT100

-200°C - 850°C ± 0.3°C

0hex

1hex

NI100

-60°C - 250°C ± 0.3°C

2hex

PT1000

-200°C - 850°C ± 0.3°C

3hex

PT500

-200°C - 850°C ± 0.5°C

4hex

PT200

-200°C - 850°C ± 0.3°C

5hex

NI1000

-200°C - 850°C ± 0.3°C

6hex

NI120

-80°C - 320°C ± 0.3°C

7hex

RSNE1000

Nickel 1000, special Siemens temperature curve

Ehex

Ohm

10 - 5000 ohms (in 1/2 Ohm)

Fhex

Ohm

10 -1200 ohms (in 1/10 Ohm)

*) as from I/O circuit board firmware version 2 of IP3202 resp. as from I/O circuit board firmware version 0 of IE3202

Explanation of the sign bit

The default representation is twos complement, i.e. -1 is represented as 0xFFFF

Sign-amount representation is active, i.e. -1 is represented by 0x8001

Scaling example

Manufacturers scaling active, user scaling active, output in ohms, 10-5000 ohms
Register 34 0x0500 0.100 ohm / digit
Register 34 0x0400 0.125 ohm / digit
Register 34 0x0200 0.250 ohm / digit
Register 34 0x0100 0.500 ohm / digit
Register 34 0x0080 1.000 ohm / digit

Siemens output format (S5)

If the Siemens output format is selected, the lowest three bits are used to assess the status. The process data is represented in bits 3-15, where bit 15 is the arithmetic sign bit.

Bit

Name

Description

0

Overflow

0bin

Value in Range

1bin

Value out of range

1

Error

0bin

No error

1bin

Error

2

-

0bin

reserverd

14...3

Value

0bin

process data

15

Sign

0bin

plus

1bin

minus

Two-wire connection

A resistance can be measured directly through the two-wire connection. That proportion of the resistance represented by the connecting cables can be measured and entered in register 21. For two-wire connection, it is necessary to copy the raw ADC value from register 1 into register 22 while the conductor resistance is short-circuited (+RL -RL).

User scaling

Example of scaling to Fahrenheit