Custom Scaling
To change the module to Fahrenheit you have to convert the equation and set the user registers describe.
Equation:
°F = 9/5 x °C + 32
To set the scaling to 1/10 °F, the constant part (offset) is
scaled with 10 multiplied..
This means :
- for offset 32 *10 =320
- for the gain (9/5 *10/16 *256) = 288
Necessary register settings:
- R31 set code word = 0x1235
- R32 disable custom scaling
- R32 enable custom scaling
- R33 custom Offset = 320dez
- R34 custom Gain = 288dez
Scaling changes are valid immediately and are separate for each channel adjustable.