IP232x-Bxxx, IE232x
4 digital inputs (3.0 ms input filter) and 4 digital outputs, 24 VDC, Imax = 2.0 A, total current 4 A
The IP232x digital I/O modules combine 4 digital inputs with a 3 ms input filter and four digital outputs in one device. The outputs handle load currents of up to 2.0 A, are short-circuit proof and protected against inverse polarity. The state of each signal is indicated by means of light emitting diodes. The signals are connected optionally via 8 mm snap-on plugs (IP2320), screw-in M8 connectors (IP2321) or screw-in M12 connectors (IP2322).
|
Technical data |
IP2320-Bxxx / IE2320 |
IP2321-Bxxx / IE2321 |
IP2322-Bxxx / IE2322 |
|---|---|---|---|
|
Number of outputs |
4 inputs and 4 outputs | ||
|
Output connections |
Ø 8 snap on |
M8 screw-in |
M12 screw-in |
|
Input filter |
3.0 ms | ||
|
Signals „0“ / „1“ |
-3 ... 5 V / 11 ... 30 V, 6 mA input current (EN61131-2, type 2) | ||
|
Load type |
ohmic, inductive, lamp load | ||
|
Rated load voltage |
24 VDC (20 V ... 29 V) | ||
|
Output current |
max. 2.0 A each channel, individually short-circuit proof, total current 4 A | ||
|
Short circuit current |
typical 4.0 A | ||
|
Load voltage current consumption |
typical 30 mA per channel | ||
|
Sensor supply |
derived from the control voltage, max. 0.5 A per channel, fully short-circuit proof | ||
|
Power supply |
Feed: 1 x M8 connector, 4-pin; downstream connection: 1 x M8 socket, 4-pin | ||
|
Bits in process image |
4 bits input and 4 bits output | ||
|
Electrical isolation |
control voltage / fieldbus:
yes | ||
|
Permissible ambient temperature during operation |
0°C ... +55°C | ||
|
Permissible ambient temperature during storage |
-25 °C ... +85°C | ||
|
Vibration / shock resistance |
conforms to EN 60068-2-6 / EN 60068-2-27 | ||
|
EMC resistance burst / ESD |
conforms to EN 61000-6-2 / EN 61000-6-4 | ||
|
Protection class |
IP65, IP66, IP67 (conforms to EN 60529) | ||
|
Installation position |
variable | ||
See the connection diagram for details of the connection.
See the mapping description for details of the mapping.
See dimension page for weight and dimensions.