LED filter
Note | |
Critical operating states may not be displayed under certain circumstances. If you filter out messages with the LED filter, critical operating states may no longer be displayed by the LEDs under certain circumstances.
|
Use the LED filter if you do not wish certain messages to be displayed by the LEDs. The LED filter can filter out two types of message:
- Messages that concern currents.
- Messages that concern voltages.
The LED filter can be set individually for each input channel:
Input channel | CoE parameters for setting the LED filter | |
|---|---|---|
1 | Control voltage US | |
2 | Peripheral voltage UP | |
The following options are available:
Value | Enum | Description |
|---|---|---|
0 | "Voltage and current" | The LEDs signal all messages. |
1 | "Voltage only" | The LEDs signal only messages that concern currents. |
2 | "Current only" | The LEDs signal only messages that concern voltages. |
255dec | "LEDs off" | All LEDs are off. |