Vendor calibration
Each analog output is calibrated in the factory. The results of the calibration are the coefficients of a correction function. The correction function is:
| YV = GV * XV + OV | YV: Output value after vendor calibration XV: Output value before vendor calibration GV : Gain of the vendor calibration OV : Offset of the vendor calibration |
The coefficients GV and OV cannot be changed by the user. If you wish to carry out a calibration yourself, use the user calibration.
You will find the coefficients for the different output signal ranges in the following CoE objects:
Channel | CoE object (read only) | |
---|---|---|
1 | 803Fhex | AO Vendor data Ch.1 |
2 | 804Fhex | AO Vendor data Ch.2 |
Disabling the vendor calibration
Notice | |
Output error with disabled vendor calibration The output error specified in the technical data is no longer guaranteed if you disable the vendor calibration. |
If you use the user calibration, it may be a good idea to disable the vendor calibration.
Set the CoE parameter "Enable vendor calibration" to FALSE to disable the vendor calibration for the respective output.
Channel | "Enable vendor calibration" |
---|---|
1 | 0x8030:08 |
2 | 0x8040:08 |