Output signal range
The output signal range can be selected individually for each analog output.
Set the output signal ranges in the CoE parameters "Input Type":
Channel | "Output Type" |
---|---|
1 | 0x803D:11 |
2 | 0x804D:11 |
Possible values for EPP4304-1002
Value | Output signal range |
---|---|
2dec (factory setting) | U ±10V |
14dec | U 0-10V |
65535dec | Disabled |
Possible values for EPP4314-1002
Value | Output signal range |
---|---|
16dec | I ±10 mA |
17dec (factory setting) | I ±20 mA |
18dec | I 0-20 mA |
19dec | I 4-20 mA |
65535dec | Disabled |