Measuring range 0 … 20 mA
Technical data | Measuring range 0...20 mA |
---|---|
Measuring range, nominal | 0…20 mA |
Measuring range, end value (full scale value) | 20 mA |
Measuring range, technically usable | -0.186…+21.474 mA, overcurrent-protected |
Fuse protection | Internal overload limiting, continuous current resistant |
PDO resolution | 16-bit, including sign |
PDO LSB (Extended Range) | 655.35 nA |
PDO LSB (Legacy Range) | 610.37 nA |