Technical data

All values are typical values over the entire temperature range, unless stated otherwise.

EtherCAT P

Connection

2 x M8 socket, 4-pin, P-coded, red

Distributed Clocks

yes

Supply voltages

Connection

See EtherCAT P connection

US nominal voltage

24 VDC (-15 % / +20 %)

US sum current: IS,sum

max. 3 A

Current consumption from US

100 mA

Rated voltage UP

24 VDC (-15 % / +20 %)

UP sum current: IP,sum

max. 3 A

Current consumption from UP

= Current consumption of connected sensors.

Analog inputs

EPP3174-0002

EPP3174-0002

Number

4

Connection technology

two-wire, four-wire

single ended

Connection

M12 sockets

M12 sockets

Measuring range

Configurable:

  • 0 … +10 V
  • -10 … +10 V
  • 0 … 20 mA
  • 4 … 20 mA

Internal resistance

> 200 kΩ (typ. 85 Ω + diode voltage)

Common-mode voltage UCM

max. 35 V

Resolution

16 bits (including sign)

Input filter

configurable

Input filter limit frequency

5 kHz

Conversion time

~ 100 μs

Measurement deviation

< ±0.3 %, relative to full scale value.

See chapter Measurement error/measurement deviation/measurement uncertainty, output uncertainty.

Sensor power supply

from the load voltage UP

Housing data

Dimensions W x H x D

30 mm x 126 mm x 26.5 mm (without connectors)

Weight

approx. 165 g

Installation position

variable

Material

PA6 (polyamide)

Environmental conditions

Ambient temperature during operation

-25 … +60 °C
-25 … +55 °C according to cULus

Ambient temperature during storage

-40 … +85 °C

Vibration resistance, shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27
Additional checks

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP65, IP66, IP67 (conforms to EN 60529)

Approvals / markings

Approvals / markings *)

CE, cULus

*) Real applicable approvals/markings see type plate on the side (product marking).

Additional tests

The devices have undergone the following additional tests:

Test

Explanation

Vibration

10 frequency sweeps in 3 axes

5 Hz < f < 60 Hz displacement 0.35 mm, constant amplitude

60.1 Hz < f < 500 Hz acceleration 5 g, constant amplitude

Shocks

1000 shocks in each direction, in 3 axes

35 g, 11 ms