Measuring ranges

Analog inputs

The measuring range can be switched during operation. The following table shows the electrical specifications depending on the selected measuring range.

Technical data

Measuring range

-10…10 V

0…10 V

0…20 mA

4…20 mA

Input type

Differential

Input resistance

> 200 kΩ

> 200 kΩ

85 Ω typ. + diode voltage

85 Ω typ. + diode voltage

Digital resolution

16-bit

15-bit

15-bit

15-bit

Measuring error

< 0.3 % relative to full scale value

Conversion time

approx. 100 µs

Input filter limit frequency

5 kHz

Value of the least significant bit

approx. 305 µV

approx. 305 µV

approx. 610 µA

approx. 488 µA

The analog inputs and outputs have a common analog ground potential. The analog ground potential is electrically isolated from all other ground potentials in the box.