Technical data
All values are typical values over the entire temperature range, unless stated otherwise.
IO-Link | |
|---|---|
Connection | 1 x M12 plug, 5-pin, A-coded |
Data transfer rate | 230.4 kbaud (COM 3) |
Specification version | IO-Link V1.1, Class A |
Requirements for IO-Link master | V1.1 |
Current consumption from L+ | 100 mA + sensor supply |
Digital inputs | EPI1809-0021 | EPI1809-0022 |
|---|---|---|
Number | 16 | |
Connection | 16 x M8 socket | 16 x M12 socket |
Characteristics | Type 3 according to EN 61131-2, compatible with type 1 | |
Input filter | 3 ms (default). Adjustable from 0 ms to 20 ms. | |
Pulse extension | 0 ms (default). Adjustable from 0 ms to 100 ms. | |
Signal voltage "0" | -3 … +5 V | |
Signal voltage "1" | +11 … +30 V | |
Input current | 3 mA at 24 VDC | |
Sensor power supply US1 | 24 VDC from L+. max. 0.5 A in total, short-circuit proof. | |
Housing data | EPI1809-002x | ERI1809-002x |
|---|---|---|
Dimensions W x H x D | 60 mm x 126 mm x 26.5 mm (without plug connectors) | |
Weight | approx. 250 g | |
Installation position | variable | |
Material | PA6 (polyamide) | Zinc die-cast |
Environmental conditions | |
|---|---|
Ambient temperature during operation | -25 … +60 °C |
Ambient temperature during storage | -40 … +85 °C |
Vibration resistance, shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 |
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 |
Protection class | IP65, IP66, IP67 (conforms to EN 60529) |
Approvals/markings | |
|---|---|
Approvals/markings *) | CE, cURus |
*) Real applicable approvals/markings see type plate on the side (product marking).
Additional tests
The devices have undergone the following additional tests:
Test | Explanation |
|---|---|
Vibration | 10 frequency sweeps in 3 axes |
5 Hz < f < 60 Hz displacement 0.35 mm, constant amplitude | |
60.1 Hz < f < 500 Hz acceleration 5 g, constant amplitude | |
Shocks | 1000 shocks in each direction, in 3 axes |
35 g, 11 ms |