Process image
| DPO Inputs Channel n DPO Inputs Device DPO Outputs Channel n DPO Outputs Device WcState and InfoData |
DPO Inputs Channel 1 to 4
Status bits of the individual channels.
EP9214-002x:
| Error Us: US was switched off due to overload. Error Up: UP was switched off due to overload. Warning Us: The output current US currently exceeds the nominal current (CoE parameter 80n0:12). Warning Up: The output current US currently exceeds the nominal current (CoE parameter 80n0:13). Status Us: Switching status (on/off) of the output voltage US. Status Up: Switching status (on/off) of the output voltage UP. Channel Error: "Error Us" or "Error Up" is TRUE. |
EP9224-002x:
| Error Us: US was switched off due to overload. Error Up: UP was switched off due to overload. Warning Us: The output current US currently exceeds the nominal current (CoE parameter 80n0:12). Warning Up: The output current US currently exceeds the nominal current (CoE parameter 80n0:13). Status Us: Switching status (on/off) of the output voltage US. Status Up: Switching status (on/off) of the output voltage UP. Channel Error: "Error Us" or "Error Up" is TRUE. Error Sum Current: The channel was switched off due to sum overcurrent. Warning Sum Current: The sum current IS + IP of the channel currently exceeds the nominal sum current (CoE parameter 80n0:14). Current Us, Current Up: 16-bit measured values of the current output currents. |
DPO Inputs Device
Status bits for the entire device.
EP9214-002x:
| Temperature Warning: The internal temperature exceeds the warning threshold. Temperature Error: The internal temperature has exceeded the error threshold. The output channels have been switched off. US Warning, UP Warning: Undervoltage warning. The respective input voltage is currently below the warning threshold value Uwarn. Us Error, Up Error: Undervoltage switch-off. The respective input voltage has fallen below the error threshold value Uerr. Global Error Bit: There is at least one error message. Reset Input: Input level (0/1) of the reset input. |
EP9224-002x:
| Temperature Warning: The internal temperature exceeds the warning threshold. Temperature Error: The internal temperature has exceeded the error threshold. The output channels have been switched off. US Warning, UP Warning: Undervoltage warning. The respective input voltage is currently below the warning threshold value Uwarn. Us Error, Up Error: Undervoltage switch-off. The respective input voltage has fallen below the error threshold value Uerr. Global Error Bit: There is at least one error message. Sum Current Warning: The input sum current IS + IP currently exceeds the nominal sum current (CoE parameter F80E:12). Sum Current Error: All output voltages were switched off due to sum overcurrent. Reset Input: Input level (0/1) of the reset input. Current Us: Current US input current at supply voltage input X70. Current Up: Current UP input current at supply voltage input X70. Voltage Us: Current value of the supply voltage US in 1/10V Voltage Up: Current value of the supply voltage UP in 1/10V Temperature: Current internal temperature of the device. |
DPO Outputs Channel 1 to 4
Output data for the individual channels.
| Output US, Output UP: Switches the respective output voltage on or off. Reset US, Reset UP: Reset the error state of the respective output voltage. |
DPO Outputs Device
Output data for the entire device.
| Enable Control Via Fieldbus:
Global Reset: Reset the error state of the device and all channels. |