Objects for parameterization

Index 1011 Restore default parameters

Index (hex)

Name

Meaning

Data type

Flags

Default

1011:0

Restore default parameters

Restore default parameters

UINT8

RO

0x01 (1dec)

1011:01

SubIndex 001

If this object is set to "0x64616F6C" in the set value dialog, all backup objects are reset to their delivery state.

UINT32

RW

0x00000000 (0dec)

Index 8000 DPO Settings Ch.1 (EP9214-0023, EP9214-0024)

Index (hex)

Name

Meaning

Data type

Flags

Default

8000:0

DPO Settings Ch.1

 

UINT8

RO

0x16 (22dec)

8000:02

Default State Us

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8000:03

Default State Up

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8000:11

Characteristic

Tripping characteristics of the overload switch-off:

  • 0: Very fast acting
  • 1: Fast acting
  • 2: Slow acting
  • 3: Time delay

See chapter Overload protection.

UINT16

RW

0x0001 (1dec)

8000:12

Nominal Current Us

Nominal current for US. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8000:13

Nominal Current Up

Nominal current for UP. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

Index 8000 DPO Settings Ch.1 (EP9224-0023, EP9224-0024)

Index (hex)

Name

Meaning

Data type

Flags

Default

8000:0

DPO Settings Ch.1

 

UINT8

RO

0x16 (22dec)

8000:02

Default State Us

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8000:03

Default State Up

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8000:04

Enable Sum Current Limitation

Activates the overcurrent protection for the sum current Us+Up on this output.

See chapter Overcurrent protection for sum currents.

BOOLEAN

RW

0x00 (0dec)

8000:11

Characteristic

Tripping characteristics of the overload switch-off:

  • 0: Very fast acting
  • 1: Fast acting
  • 2: Slow acting
  • 3: Time delay

See chapter Overload protection.

UINT16

RW

0x0001 (1dec)

8000:12

Nominal Current Us

Nominal current for US. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8000:13

Nominal Current Up

Nominal current for UP. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8000:14

Nominal Sum Current

Nominal maximum sum current (Us+Up) at the output.

See chapter Overcurrent protection for sum currents.

UINT16

RW

0x1770 (8000dec)

8000:15

Timestamp 1 Trigger

Defines which events are detected by the peak value detector at this port.

Possible values:

  • 0: Error Us
  • 1: Error Up
  • 2: Warning Us
  • 3: Warning Up
  • 7: Error Sum Current
  • 8: Warning Sum Current
  • 16: Minimum Current Us
  • 17: Maximum Current Us
  • 18: Minimum Current Up
  • 19: Maximum Current Up

See chapter Peak value detector.

UINT16

RW

0x0000 (0dec)

8000:16

Timestamp 2 Trigger

See 8000:15.

UINT16

RW

0x0000 (0dec)

800F DPO Vendor Data Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

800F:0

DPO Vendor Data Ch.1

 

USINT

RO

0x14 (20dec)

800F:11

GainS

 

UINT

RW

0x4000 (16384dec)

800F:12

OffsetS

 

INT

RW

0x0 (0dec)

800F:13

GainP

 

UINT

RW

0x4000 (16384dec)

800F:14

OffsetP

 

INT

RW

0x0 (0dec)

Index 8010 DPO Settings Ch.2 (EP9214-0023, EP9214-0024)

Index (hex)

Name

Meaning

Data type

Flags

Default

8010:0

DPO Settings Ch.2

 

UINT8

RO

0x16 (22dec)

8010:02

Default State Us

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8010:03

Default State Up

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8010:11

Characteristic

Tripping characteristics of the overload switch-off:

  • 0: Very fast acting
  • 1: Fast acting
  • 2: Slow acting
  • 3: Time delay

See chapter Overload protection.

UINT16

RW

0x0001 (1dec)

8010:12

Nominal Current Us

Nominal current for US. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8010:13

Nominal Current Up

Nominal current for UP. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

Index 8010 DPO Settings Ch.2 (EP9224-0023, EP9224-0024)

Index (hex)

Name

Meaning

Data type

Flags

Default

8010:0

DPO Settings Ch.2

 

UINT8

RO

0x16 (22dec)

8010:02

Default State Us

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8010:03

Default State Up

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8010:04

Enable Sum Current Limitation

Activates the overcurrent protection for the sum current Us+Up on this output.

See chapter Overcurrent protection for sum currents.

BOOLEAN

RW

0x00 (0dec)

8010:11

Characteristic

Tripping characteristics of the overload switch-off:

  • 0: Very fast acting
  • 1: Fast acting
  • 2: Slow acting
  • 3: Time delay

See chapter Overload protection.

UINT16

RW

0x0001 (1dec)

8010:12

Nominal Current Us

Nominal current for US. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8010:13

Nominal Current Up

Nominal current for UP. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8010:14

Nominal Sum Current

Nominal maximum sum current (Us+Up) at the output.

See chapter Overcurrent protection for sum currents.

UINT16

RW

0x1770 (8000dec)

8010:15

Timestamp 1 Trigger

Defines which events are detected by the peak value detector at this port.

Possible values:

  • 0: Error Us
  • 1: Error Up
  • 2: Warning Us
  • 3: Warning Up
  • 7: Error Sum Current
  • 8: Warning Sum Current
  • 16: Minimum Current Us
  • 17: Maximum Current Us
  • 18: Minimum Current Up
  • 19: Maximum Current Up

See chapter Peak value detector.

UINT16

RW

0x0000 (0dec)

8010:16

Timestamp 2 Trigger

See 8010:15.

UINT16

RW

0x0000 (0dec)

801F DPO Vendor Data Ch.2

Index (hex)

Name

Meaning

Data type

Flags

Default

801F:0

DPO Vendor Data Ch.2

 

USINT

RO

0x14 (20dec)

801F:11

GainS

 

UINT

RW

0x4000 (16384dec)

801F:12

OffsetS

 

INT

RW

0x0 (0dec)

801F:13

GainP

 

UINT

RW

0x4000 (16384dec)

801F:14

OffsetP

 

INT

RW

0x0 (0dec)

Index 8020 DPO Settings Ch.3 (EP9214-0023, EP9214-0024)

Index (hex)

Name

Meaning

Data type

Flags

Default

8020:0

DPO Settings Ch.3

 

UINT8

RO

0x16 (22dec)

8020:02

Default State Us

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8020:03

Default State Up

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8020:11

Characteristic

Tripping characteristics of the overload switch-off:

  • 0: Very fast acting
  • 1: Fast acting
  • 2: Slow acting
  • 3: Time delay

See chapter Overload protection.

UINT16

RW

0x0001 (1dec)

8020:12

Nominal Current Us

Nominal current for US. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8020:13

Nominal Current Up

Nominal current for UP. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

Index 8020 DPO Settings Ch.3 (EP9224-0023, EP9224-0024)

Index (hex)

Name

Meaning

Data type

Flags

Default

8020:0

DPO Settings Ch.3

 

UINT8

RO

0x16 (22dec)

8020:02

Default State Us

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8020:03

Default State Up

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8020:04

Enable Sum Current Limitation

Activates the overcurrent protection for the sum current Us+Up on this output.

See chapter Overcurrent protection for sum currents.

BOOLEAN

RW

0x00 (0dec)

8020:11

Characteristic

Tripping characteristics of the overload switch-off:

  • 0: Very fast acting
  • 1: Fast acting
  • 2: Slow acting
  • 3: Time delay

See chapter Overload protection.

UINT16

RW

0x0001 (1dec)

8020:12

Nominal Current Us

Nominal current for US. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8020:13

Nominal Current Up

Nominal current for UP. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8020:14

Nominal Sum Current

Nominal maximum sum current (Us+Up) at the output.

See chapter Overcurrent protection for sum currents.

UINT16

RW

0x1770 (8000dec)

8020:15

Timestamp 1 Trigger

Defines which events are detected by the peak value detector at this port.

Possible values:

  • 0: Error Us
  • 1: Error Up
  • 2: Warning Us
  • 3: Warning Up
  • 7: Error Sum Current
  • 8: Warning Sum Current
  • 16: Minimum Current Us
  • 17: Maximum Current Us
  • 18: Minimum Current Up
  • 19: Maximum Current Up

See chapter Peak value detector.

UINT16

RW

0x0000 (0dec)

8020:16

Timestamp 2 Trigger

See 8020:15

UINT16

RW

0x0000 (0dec)

802F DPO Vendor Data Ch.3

Index (hex)

Name

Meaning

Data type

Flags

Default

802F:0

DPO Vendor Data Ch.3

 

USINT

RO

0x14 (20dec)

802F:11

GainS

 

UINT

RW

0x4000 (16384dec)

802F:12

OffsetS

 

INT

RW

0x0 (0dec)

802F:13

GainP

 

UINT

RW

0x4000 (16384dec)

802F:14

OffsetP

 

INT

RW

0x0 (0dec)

Index 8030 DPO Settings Ch.4 (EP9214-0023, EP9214-0024)

Index (hex)

Name

Meaning

Data type

Flags

Default

8030:0

DPO Settings Ch.4

 

UINT8

RO

0x16 (22dec)

8030:02

Default State Us

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8030:03

Default State Up

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8030:11

Characteristic

Tripping characteristics of the overload switch-off:

  • 0: Very fast acting
  • 1: Fast acting
  • 2: Slow acting
  • 3: Time delay

See chapter Overload protection.

UINT16

RW

0x0001 (1dec)

8030:12

Nominal Current Us

Nominal current for US. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8030:13

Nominal Current Up

Nominal current for UP. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

Index 8030 DPO Settings Ch.4 (EP9224-0023, EP9224-0024)

Index (hex)

Name

Meaning

Data type

Flags

Default

8030:0

DPO Settings Ch.4

 

UINT8

RO

0x16 (22dec)

8030:02

Default State Us

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8030:03

Default State Up

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8030:04

Enable Sum Current Limitation

Activates the overcurrent protection for the sum current Us+Up on this output.

See chapter Overcurrent protection for sum currents.

BOOLEAN

RW

0x00 (0dec)

8030:11

Characteristic

Tripping characteristics of the overload switch-off:

  • 0: Very fast acting
  • 1: Fast acting
  • 2: Slow acting
  • 3: Time delay

See chapter Overload protection.

UINT16

RW

0x0001 (1dec)

8030:12

Nominal Current Us

Nominal current for US. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8030:13

Nominal Current Up

Nominal current for UP. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8030:14

Nominal Sum Current

Nominal maximum sum current (Us+Up) at the output.

See chapter Overcurrent protection for sum currents.

UINT16

RW

0x1770 (8000dec)

8030:15

Timestamp 1 Trigger

Defines which events are detected by the peak value detector at this port.

Possible values:

  • 0: Error Us
  • 1: Error Up
  • 2: Warning Us
  • 3: Warning Up
  • 7: Error Sum Current
  • 8: Warning Sum Current
  • 16: Minimum Current Us
  • 17: Maximum Current Us
  • 18: Minimum Current Up
  • 19: Maximum Current Up

See chapter Peak value detector.

UINT16

RW

0x0000 (0dec)

8030:16

Timestamp 2 Trigger

See 8030:15

UINT16

RW

0x0000 (0dec)

803F DPO Vendor Data Ch.4

Index (hex)

Name

Meaning

Data type

Flags

Default

803F:0

DPO Vendor Data Ch.4

 

USINT

RO

0x14 (20dec)

803F:11

GainS

 

UINT

RW

0x4000 (16384dec)

803F:12

OffsetS

 

INT

RW

0x0 (0dec)

803F:13

GainP

 

UINT

RW

0x4000 (16384dec)

803F:14

OffsetP

 

INT

RW

0x0 (0dec)

Index 8040 LOG Settings (only EP9224-0023 and EP9224-0024)

Index (hex)

Name

Meaning

Data type

Flags

Default

8040:0

LOG Settings

 

UINT8

RO

0x11 (17dec)

8040:11

Sampling Rate

Sampling rate of the data logger

  • 1: 1 ms
  • 10: 10 ms
  • 25: 25 ms
  • 100: 100 ms
  • 1000: 1000 ms

See chapter Data logger.

UINT16

RW

0x000A (10dec)

Index F80E DPO Settings Device (EP9214-0023 and EP9214-0024)

Index (hex)

Name

Meaning

Data type

Flags

Default

F80E:0

DPO Settings Device

 

UINT8

RO

0x16 (22dec)

F80E:11

Startup Delay

Sets the time that is kept between two switch-on procedures:

  • 0: Fast (10 ms)
  • 1: Moderate (100 ms)
  • 2: Slow (200 ms)

UINT16

RW

0x0001 (1dec)

Index F80E DPO Settings Device (EP9224-0023 and EP9224-0024)

Index (hex)

Name

Meaning

Data type

Flags

Default

F80E:0

DPO Settings Device

 

UINT8

RO

0x16 (22dec)

F80E:02

Enable Sum Current Limitation

Enables the overcurrent protection for the sum current ∑ US + ∑ UP.

BOOLEAN

RW

0x00 (0dec)

F80E:03

Automatic Restart After Uncritic Events on Us

Automatic restart after undervoltage and overtemperature:

0bin: enabled

1bin: disabled

BOOLEAN

RW

0x00 (0dec)

F80E:04

Automatic Restart After Uncritic Events on Up

Automatic restart after undervoltage and overtemperature:

0bin: enabled

1bin: disabled

BOOLEAN

RW

0x00 (0dec)

F80E:11

Startup Delay

Sets the time that is kept between two switch-on procedures:

  • 0: Fast (10 ms)
  • 1: Moderate (100 ms)
  • 2: Slow (200 ms)

UINT16

RW

0x0001 (1dec)

F80E:12

Nominal Sum Current

Nominal maximum current for the sum current.

INT16

RW

0x5DC0 (24000dec)

F80E:13

Sum Current Characteristic

Specifies the characteristic with which the current monitoring reacts:

  • 0: Very fast acting
  • 1: Fast acting
  • 2: Slow acting
  • 3: Time delay

UINT16

RW

0x0001 (1dec)

F80E:15

Timestamp 1 Trigger

Defines which events are detected by the peak value detector.

Possible values:

  • 0: Temperature Warning
  • 1: Temperature Error
  • 2: Us Warning
  • 3: Us Error
  • 4: Up Warning
  • 5: Up Error
  • 7: Sum Current Warning
  • 8: Sum Current Error
  • 16: Minimum Current Us
  • 17: Maximum Current Us
  • 18: Minimum Current Up
  • 19: Maximum Current Up
  • 20: Minimum Voltage Us
  • 21: Maximum Voltage Us
  • 22: Minimum Voltage Up
  • 23: Maximum Voltage Up
  • 24: Minimum Temperature
  • 25: Maximum Temperature

See chapter Peak value detector.

UINT16

RW

0x0000 (0dec)

F80E:16

Timestamp 2 Trigger

See F80E:15.

UINT16

RW

0x0000 (0dec)

F81F DPO Vendor Data Device

Index (hex)

Name

Meaning

Data type

Flags

Default

F81F:0

DPO Vendor Data Device

 

USINT

RO

0x1a (26dec)

F81F:10

Enable Calibration Mode

 

BOOL

RW

00

F81F:11

GainS

 

UINT

RW

0x4000 (16384dec)

F81F:12

OffsetS

 

INT

RW

0x0 (0dec)

F81F:13

GainP

 

UINT

RW

0x4000 (16384dec)

F81F:14

OffsetP

 

INT

RW

0x0 (0dec)

F81F:15

Gain US

 

UINT

RW

0x4000 (16384dec)

F81F:16

Offset US

 

INT

RW

0x0 (0dec)

F81F:17

Gain UP

 

UINT

RW

0x4000 (16384dec)

F81F:18

Offset UP

 

INT

RW

0x0 (0dec)

F81F:19

Gain Temperature

 

UINT

RW

0x4000 (16384dec)

F81F:1A

Offset Temperature

 

INT

RW

0x0 (0dec)