Objects for parameterization

Index 1011 Restore default parameters

Index (hex)

Name

Meaning

Data type

Flags

Default

1011:0

Restore default parameters

Restore default parameters

UINT8

RO

0x01 (1dec)

1011:01

SubIndex 001

If this object is set to "0x64616F6C" in the set value dialog, all backup objects are reset to their delivery state.

UINT32

RW

0x00000000 (0dec)

Index 8000 DPO Settings Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

8000:0

DPO Settings Ch.1

 

UINT8

RO

0x16 (22dec)

8000:02

Default State Us

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8000:03

Default State Up

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8000:04

Enable Sum Current Limitation

Activates the overcurrent protection for the sum current Us+Up on this output.

See chapter Overcurrent protection for sum currents.

BOOLEAN

RW

0x00 (0dec)

8000:11

Characteristic

Tripping characteristics of the overload switch-off:

  • 0: Very fast acting
  • 1: Fast acting
  • 2: Slow acting
  • 3: Time delay

See chapter Overload protection.

UINT16

RW

0x0001 (1dec)

8000:12

Nominal Current Us

Nominal current for US. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8000:13

Nominal Current Up

Nominal current for UP. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8000:14

Nominal Sum Current

Nominal maximum sum current (Us+Up) at the output.

See chapter Overcurrent protection for sum currents.

UINT16

RW

0x1770 (8000dec)

8000:15

Timestamp 1 Trigger

Defines which events are detected by the peak value detector at this port.

Possible values:

  • 0: Error Us
  • 1: Error Up
  • 2: Warning Us
  • 3: Warning Up
  • 7: Error Sum Current
  • 8: Warning Sum Current
  • 16: Minimum Current Us
  • 17: Maximum Current Us
  • 18: Minimum Current Up
  • 19: Maximum Current Up

See chapter Peak value detector.

UINT16

RW

0x0000 (0dec)

8000:16

Timestamp 2 Trigger

See 8000:15.

UINT16

RW

0x0000 (0dec)

Index 8010 DPO Settings Ch.2

Index (hex)

Name

Meaning

Data type

Flags

Default

8010:0

DPO Settings Ch.2

 

UINT8

RO

0x16 (22dec)

8010:02

Default State Us

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8010:03

Default State Up

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8010:04

Enable Sum Current Limitation

Activates the overcurrent protection for the sum current Us+Up on this output.

See chapter Overcurrent protection for sum currents.

BOOLEAN

RW

0x00 (0dec)

8010:11

Characteristic

Tripping characteristics of the overload switch-off:

  • 0: Very fast acting
  • 1: Fast acting
  • 2: Slow acting
  • 3: Time delay

See chapter Overload protection.

UINT16

RW

0x0001 (1dec)

8010:12

Nominal Current Us

Nominal current for US. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8010:13

Nominal Current Up

Nominal current for UP. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8010:14

Nominal Sum Current

Nominal maximum sum current (Us+Up) at the output.

See chapter Overcurrent protection for sum currents.

UINT16

RW

0x1770 (8000dec)

8010:15

Timestamp 1 Trigger

Defines which events are detected by the peak value detector at this port.

Possible values:

  • 0: Error Us
  • 1: Error Up
  • 2: Warning Us
  • 3: Warning Up
  • 7: Error Sum Current
  • 8: Warning Sum Current
  • 16: Minimum Current Us
  • 17: Maximum Current Us
  • 18: Minimum Current Up
  • 19: Maximum Current Up

See chapter Peak value detector.

UINT16

RW

0x0000 (0dec)

8010:16

Timestamp 2 Trigger

See 8010:15.

UINT16

RW

0x0000 (0dec)

Index 8020 DPO Settings Ch.3

Index (hex)

Name

Meaning

Data type

Flags

Default

8020:0

DPO Settings Ch.3

 

UINT8

RO

0x16 (22dec)

8020:02

Default State Us

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8020:03

Default State Up

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8020:04

Enable Sum Current Limitation

Activates the overcurrent protection for the sum current Us+Up on this output.

See chapter Overcurrent protection for sum currents.

BOOLEAN

RW

0x00 (0dec)

8020:11

Characteristic

Tripping characteristics of the overload switch-off:

  • 0: Very fast acting
  • 1: Fast acting
  • 2: Slow acting
  • 3: Time delay

See chapter Overload protection.

UINT16

RW

0x0001 (1dec)

8020:12

Nominal Current Us

Nominal current for US. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8020:13

Nominal Current Up

Nominal current for UP. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8020:14

Nominal Sum Current

Nominal maximum sum current (Us+Up) at the output.

See chapter Overcurrent protection for sum currents.

UINT16

RW

0x1770 (8000dec)

8020:15

Timestamp 1 Trigger

Defines which events are detected by the peak value detector at this port.

Possible values:

  • 0: Error Us
  • 1: Error Up
  • 2: Warning Us
  • 3: Warning Up
  • 7: Error Sum Current
  • 8: Warning Sum Current
  • 16: Minimum Current Us
  • 17: Maximum Current Us
  • 18: Minimum Current Up
  • 19: Maximum Current Up

See chapter Peak value detector.

UINT16

RW

0x0000 (0dec)

8020:16

Timestamp 2 Trigger

See 8020:15

UINT16

RW

0x0000 (0dec)

Index 8030 DPO Settings Ch.4

Index (hex)

Name

Meaning

Data type

Flags

Default

8030:0

DPO Settings Ch.4

 

UINT8

RO

0x16 (22dec)

8030:02

Default State Us

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8030:03

Default State Up

If F707:01 “Enable Control Via Fieldbus” is not set, the output assumes this value.

See chapter Switch output voltages.

BOOLEAN

RW

0x01 (1dec)

8030:04

Enable Sum Current Limitation

Activates the overcurrent protection for the sum current Us+Up on this output.

See chapter Overcurrent protection for sum currents.

BOOLEAN

RW

0x00 (0dec)

8030:11

Characteristic

Tripping characteristics of the overload switch-off:

  • 0: Very fast acting
  • 1: Fast acting
  • 2: Slow acting
  • 3: Time delay

See chapter Overload protection.

UINT16

RW

0x0001 (1dec)

8030:12

Nominal Current Us

Nominal current for US. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8030:13

Nominal Current Up

Nominal current for UP. Unit: mA

Value range: 1000 ... 4000dec

See chapter Overload protection.

UINT16

RW

0x0BB8 (4000dec)

8030:14

Nominal Sum Current

Nominal maximum sum current (Us+Up) at the output.

See chapter Overcurrent protection for sum currents.

UINT16

RW

0x1770 (8000dec)

8030:15

Timestamp 1 Trigger

Defines which events are detected by the peak value detector at this port.

Possible values:

  • 0: Error Us
  • 1: Error Up
  • 2: Warning Us
  • 3: Warning Up
  • 7: Error Sum Current
  • 8: Warning Sum Current
  • 16: Minimum Current Us
  • 17: Maximum Current Us
  • 18: Minimum Current Up
  • 19: Maximum Current Up

See chapter Peak value detector.

UINT16

RW

0x0000 (0dec)

8030:16

Timestamp 2 Trigger

See 8030:15

UINT16

RW

0x0000 (0dec)

Index 8040 LOG Settings

Index (hex)

Name

Meaning

Data type

Flags

Default

8040:0

LOG Settings

 

UINT8

RO

0x11 (17dec)

8040:11

Sampling Rate

Sampling rate of the data logger

  • 1: 1 ms
  • 10: 10 ms
  • 25: 25 ms
  • 100: 100 ms
  • 1000: 1000 ms

See chapter Data logger.

UINT16

RW

0x000A (10dec)

Index F707 DPO Outputs Device

Index (hex)

Name

Meaning

Data type

Flags

Default

707F:0

DPO Outputs Device

 

UINT8

RO

0x11 (17dec)

F707:01

Enable Control Via Fieldbus

0bin: All outputs are set according to their default values (80n0:02, 80n0:03)

1bin: All outputs are set according to their PDOs (70n0:01, 70n0:02)

See chapter Switch output voltages.

BOOLEAN

RO

0x00 (0dec)

707F:04

Global Reset

Reset all errors.

BOOLEAN

RO

0x00 (0dec)

707F:11

Reset Extended Diag Data

Reset all values of the peak value detector.

See chapter Peak value detector.

BOOLEAN

RO

0x00 (0dec)

Index F80E DPO Settings Device

Index (hex)

Name

Meaning

Data type

Flags

Default

F80E:0

DPO Settings Device

 

UINT8

RO

0x16 (22dec)

F80E:02

Enable Sum Current Limitation

Enables the overcurrent protection for the sum current ∑ US + ∑ UP.

BOOLEAN

RW

0x00 (0dec)

F80E:05

Disable Up Undervoltage Error

Disables the undervoltage protection for the peripheral voltage UP.

BOOLEAN

RW

0x00 (0dec)

F80E:11

Startup Delay

Sets the time that is kept between two switch-on procedures:

  • 0: Fast (10 ms)
  • 1: Moderate (100 ms)
  • 2: Slow (200 ms)

UINT16

RW

0x0001 (1dec)

F80E:12

Nominal Sum Current

Nominal maximum current for the sum current.

INT16

RW

0x5DC0 (24000dec)

F80E:13

Sum Current Characteristic

Specifies the characteristic with which the current monitoring reacts:

  • 0: Very fast acting
  • 1: Fast acting
  • 2: Slow acting
  • 3: Time delay

UINT16

RW

0x0001 (1dec)

F80E:15

Timestamp 1 Trigger

Defines which events are detected by the peak value detector.

Possible values:

  • 0: Temperature Warning
  • 1: Temperature Error
  • 2: Us Warning
  • 3: Us Error
  • 4: Up Warning
  • 5: Up Error
  • 7: Sum Current Warning
  • 8: Sum Current Error
  • 16: Minimum Current Us
  • 17: Maximum Current Us
  • 18: Minimum Current Up
  • 19: Maximum Current Up
  • 20: Minimum Voltage Us
  • 21: Maximum Voltage Us
  • 22: Minimum Voltage Up
  • 23: Maximum Voltage Up
  • 24: Minimum Temperature
  • 25: Maximum Temperature

See chapter Peak value detector.

UINT16

RW

0x0000 (0dec)

F80E:16

Timestamp 2 Trigger

See F80E:15.

UINT16

RW

0x0000 (0dec)