Process image

In the process image, the supply voltage outputs and EtherCAT ports are labeled "Channel 1" to "Channel 4". The following table shows the assignment between the designations in the process image and the connection designations:

Designation in the process image

Supply voltage output

EtherCAT port

Channel 1

X60

X40

Channel 2

X61

X41

Channel 3

X62

X42

Channel 4

X63

X43

Process image 1:

DPO Inputs Channel n
Status bits of the channels.

DPO Inputs Device
Status bits of the entire device.

DPO Outputs Channel n
Output bits of the channels.

DPO Outputs Device
Output bits of the entire device.

WcState and InfoData
EtherCAT system variables.

EP9224-3037
I/O module that represents the second EtherCAT Slave Controller in the device. See chapter Basic Function Principles.

DPO Inputs Channel 1 to 4

Status bits of the individual channels.

Process image 2:

Error Us: US was switched off due to overload.

Error Up: UP was switched off due to overload.

Warning Us: The output current US currently exceeds the nominal current (CoE parameter 80n0:12).
If the overcurrent persists, US is switched off on this channel.

Warning Up: The output current US currently exceeds the nominal current (CoE parameter 80n0:13).
If the overcurrent persists, UP is switched off on this channel.

Status Us: Switching status (on/off) of the output voltage US.

Status Up: Switching status (on/off) of the output voltage UP.

Channel Error: "Error Us" or "Error Up" is TRUE.

Error Sum Current: The channel was switched off due to sum overcurrent.

Warning Sum Current: The sum current IS + IP of the channel currently exceeds the nominal sum current (CoE parameter 80n0:14).
If the overcurrent persists, the channel is switched off.

Current Us, Current Up: 16-bit measured values of the current output currents.

DPO Inputs Device

Status bits for the entire device.

Process image 3:

Temperature Warning: The internal temperature exceeds the warning threshold.

Temperature Error: The internal temperature has exceeded the error threshold. The output channels have been switched off.

US Warning, UP Warning: Undervoltage warning. The respective input voltage is currently below the warning threshold value Uwarn.

Us Error, Up Error: Undervoltage switch-off. The respective input voltage has fallen below the error threshold value Uerr.
The output voltages have been switched off.

Global Error Bit: There is at least one error message.

Sum Current Warning: The input sum current IS + IP currently exceeds the nominal sum current (CoE parameter F80E:12).
If the overcurrent persists, all channels are switched off.

Error Sum Current: All output voltages were switched off due to sum overcurrent.

Current Us: Current US input current at supply voltage input X70.

Current Up: Current UP input current at supply voltage input X70.

Voltage Us: Current value of the supply voltage US in 1/10V

Voltage Up: Current value of the supply voltage UP in 1/10V

Temperature: Current internal temperature of the device.

DPO Outputs Channel 1 to 4

Output data for the individual channels.

Process image 4:

Output US, Output UP: Switches the respective output voltage on or off.

Reset US, Reset UP: Reset the error state of the respective output voltage.

DPO Outputs Device

Output data for the entire device.

Process image 5:

Enable Control Via Fieldbus:

  • TRUE: Enables the switching of the output voltages via the output variables "Output Us" and "Output Up".
  • FALSE: Enables the automatic switching on of the output voltages according to the CoE parameters 80n0:02 and 80n0:03.

Global Reset: Reset the error state of the device and all channels.