Diag Messages
Text ID | Type | Location | Text Message | Comment |
|---|---|---|---|---|
0x8105 | Error | General | PD-Watchdog / Watchdog timeout to field-side | Watchdog error at the analog output or at a PWM output. Analog output: see chapter Behavior in the event of communication interruption: watchdog PWM output: see chapter Set PWM state in the event of a bus error (watchdog). |
0x8107 | Error | General | Power supply missing | The supply voltage UP is missing. |
0x817F | Error | General | Slotgroup %d (%s): Error module group | Error when assigning the ModuleGroups. A common reason for this Diag Message is a SlotGroup without an assigned ModuleGroup. Assign the ModuleGroup "EMPTYn" to unused SlotGroups. See chapter Selection of I/O functions. |
0x870A | Error |
| Slotgroup %d (%s): Analog range error | Overrange or Underrange at one of the analog outputs or analog inputs. |