Diag Messages
Text ID  | Type  | Location  | Text Message  | Comment  | 
|---|---|---|---|---|
0x8105  | Error  | General  | PD-Watchdog / Watchdog timeout to field-side  | Watchdog error at the analog output or at a PWM output. Analog output: see chapter Behavior in the event of communication interruption: watchdog PWM output: see chapter Set PWM state in the event of a bus error (watchdog).  | 
0x8107  | Error  | General  | Power supply missing  | The supply voltage UP is missing.  | 
0x817F  | Error  | General  | Slotgroup %d (%s): Error module group  | Error when assigning the ModuleGroups. A common reason for this Diag Message is a SlotGroup without an assigned ModuleGroup. Assign the ModuleGroup "EMPTYn" to unused SlotGroups. See chapter Selection of I/O functions.  | 
0x870A  | Error  | 
  | Slotgroup %d (%s): Analog range error  | Overrange or Underrange at one of the analog outputs or analog inputs.  |