1 counter, 1 digital input, 1 digital output: "CNT_DI_DO" (SlotGroup 1)

Connections X03 and X07

1 x digital input

1 x digital output

The X03 and X07 connections have the same pin assignment. Each pin of X03 is directly connected internally to the corresponding pin of X07.

X03 and X07

M12 socket

Pin

Function

Description

Process data

1 counter, 1 digital input, 1 digital output: "CNT_DI_DO" (SlotGroup 1) 1:

1 counter, 1 digital input, 1 digital output: "CNT_DI_DO" (SlotGroup 1) 2:

1

+24 V US

Supply voltage output

--

2

DO

Digital output

SlotGroup 1 > DOS Outputs Channel 1

3

GNDS

Ground

--

4

DI

Digital input

SlotGroup 1 > DIP Inputs Channel 1

5

FE

Functional Earth

--

 

Connection X08

1 x counter input

Notice

Incorrect signal levels due to electromagnetic interference

The counter input is optimized for fast signal transmission and is therefore susceptible to electromagnetic interference.

Under the influence of electromagnetic interference, a false signal level can be detected.

  • If necessary, use shielded signal lines.

X08

M12 socket

Pin

Function

Description

1 counter, 1 digital input, 1 digital output: "CNT_DI_DO" (SlotGroup 1) 3:

1 counter, 1 digital input, 1 digital output: "CNT_DI_DO" (SlotGroup 1) 4:

1

+24 V US

Supply voltage output

2

CNT Dir

Digital input for the counting direction

3

GNDS

Ground

4

CNT Clk

Clock input

5

FE

Functional Earth