Objects to be parameterized during commissioning
Index 8000 AI Settings Ch.1
Index (hex) | Name | Meaning | Data type | Flags | Default | |
|---|---|---|---|---|---|---|
8000:0 | AI Settings | Maximum subindex | UINT8 | RO | 0x18 (24dec) | |
8000:01 | Enable user scale | 1 | User scale is active. | BOOLEAN | RW | 0x00 (0dec) |
8000:02 | Presentation | 0 | Signed presentation | BIT3 | RW | 0x00 (0dec) |
1 | Unsigned presentation | |||||
2 | Absolute value with MSB as sign (signed amount representation) | |||||
8000:06 | Enable filter | 1 | Enable filter, which makes PLC-cycle-synchronous data exchange unnecessary | BOOLEAN | RW | 0x00 (0dec) |
8000:07 | Enable limit 1 | 1 | Limit 1 enabled | BOOLEAN | RW | 0x00 (0dec) |
8000:08 | Enable limit 2 | 1 | Limit 2 enabled | BOOLEAN | RW | 0x00 (0dec) |
8000:0A | Enable user calibration | 1 | Enabling of the user calibration | BOOLEAN | RW | 0x00 (0dec) |
8000:0B | Enable vendor calibration | 1 | Enabling of the vendor calibration | BOOLEAN | RW | 0x01 (1dec) |
8000:11 | User scale offset | User scale offset | INT16 | RW | 0x0000 (0dec) | |
8000:12 | User scale gain | User scale gain. | INT32 | RW | 0x00010000 (65536dec) | |
8000:13 | Limit 1 | First limit value for setting the status bits | INT16 | RW | 0x0000 (0dec) | |
8000:14 | Limit 2 | Second limit value for setting the status bits | INT16 | RW | 0x0000 (0dec) | |
8000:15 | Filter settings | This object determines the digital filter settings for all channels of the module, if it is activated via Enable filter (index 0x80n0:06). The possible settings are sequentially numbered. | UINT16 | RW | 0x0000 (0dec) | |
0 | 50 Hz FIR | |||||
1 | 60 Hz FIR | |||||
2 | IIR 1 | |||||
3 | IIR 2 | |||||
4 | IIR 3 | |||||
5 | IIR 4 | |||||
6 | IIR 5 | |||||
7 | IIR 6 | |||||
8 | IIR 7 | |||||
9 | IIR 8 | |||||
8000:17 | User calibration offset | User calibration: Offset | INT16 | RW | 0x0000 (0dec) | |
8000:18 | User calibration gain | User calibration: Gain | INT16 | RW | 0x4000 (16384dec) | |
Index 8000 AI Settings Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default | |
|---|---|---|---|---|---|---|
8010:0 | AI Settings | Maximum subindex | UINT8 | RO | 0x18 (24dec) | |
8010:01 | Enable user scale | 1 | User scale is active. | BOOLEAN | RW | 0x00 (0dec) |
8010:02 | Presentation | 0 | Signed presentation | BIT3 | RW | 0x00 (0dec) |
1 | Unsigned presentation | |||||
2 | Absolute value with MSB as sign (signed amount representation) | |||||
8010:06 | Enable filter | 1 | Enable filter, which makes PLC-cycle-synchronous data exchange unnecessary | BOOLEAN | RW | 0x00 (0dec) |
8010:07 | Enable limit 1 | 1 | Limit 1 enabled | BOOLEAN | RW | 0x00 (0dec) |
8010:08 | Enable limit 2 | 1 | Limit 2 enabled | BOOLEAN | RW | 0x00 (0dec) |
8010:0A | Enable user calibration | 1 | Enabling of the user calibration | BOOLEAN | RW | 0x00 (0dec) |
8010:0B | Enable vendor calibration | 1 | Enabling of the vendor calibration | BOOLEAN | RW | 0x01 (1dec) |
8010:11 | User scale offset | User scale offset | INT16 | RW | 0x0000 (0dec) | |
8010:12 | User scale gain | User scale gain. | INT32 | RW | 0x00010000 (65536dec) | |
8010:13 | Limit 1 | First limit value for setting the status bits | INT16 | RW | 0x0000 (0dec) | |
8010:14 | Limit 2 | Second limit value for setting the status bits | INT16 | RW | 0x0000 (0dec) | |
8010:15 | Filter settings | This object determines the digital filter settings for all channels of the module, if it is activated via Enable filter (index 0x80n0:06). The possible settings are sequentially numbered. | UINT16 | RW | 0x0000 (0dec) | |
0 | 50 Hz FIR | |||||
1 | 60 Hz FIR | |||||
2 | IIR 1 | |||||
3 | IIR 2 | |||||
4 | IIR 3 | |||||
5 | IIR 4 | |||||
6 | IIR 5 | |||||
7 | IIR 6 | |||||
8 | IIR 7 | |||||
9 | IIR 8 | |||||
8010:17 | User calibration offset | User calibration: Offset | INT16 | RW | 0x0000 (0dec) | |
8010:18 | User calibration gain | User calibration: Gain | INT16 | RW | 0x4000 (16384dec) | |
Index 8020 TACHO Settings Dual Shaft Mode Ch.1
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8020:0 | TACHO Settings Dual Shaft Mode Ch.1 |
| UINT8 | RO | 0x15 (21dec) |
8020:11 | No. of Targets | Number of "cams" on the shaft/axis | UINT16 | RW | 0x0001 (1dec) |
8020:12 | Input Signal Timeout | The process record <Speed Below Threshold> is set after x msec without signal change at the input. | UINT16 | RW | 0x0064 (100dec) |
8020:15 | Presentation | Display of the measured value in RPM, Hz, … | UINT16 | RW | 0x0001 (1dec) |
Index 8030 TACHO Settings Dual Shaft Mode Ch.2
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8030:0 | TACHO Settings Dual Shaft Mode Ch.2 |
| UINT8 | RO | 0x15 (21dec) |
8030:11 | No. of Targets | Number of "cams" on the shaft/axis | UINT16 | RW | 0x0001 (1dec) |
8030:12 | Input Signal Timeout | The process record <Speed Below Threshold> is set after x msec without signal change at the input. | UINT16 | RW | 0x0064 (100dec) |
8030:15 | Presentation | Display of the measured value in RPM, Hz, … | UINT16 | RW | 0x0001 (1dec) |
Index 8031 TACHO Settings Single Shaft Mode
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8031:0 | TACHO Settings Single Shaft Mode |
| UINT8 | RO | 0x15 (21dec) |
8031:0B | Enable Error Detection | Enable/disable error display | BOOLEAN | RW | 0x01 (1dec) |
8031:0C | Reversion of Rotation | Reversion of rotation display in Rotation direction | BOOLEAN | RW | 0x00 (0dec) |
8031:11 | No. of Targets | Number of "cams" on the shaft/axis | UINT16 | RW | 0x0001 (1dec) |
8031:12 | Input Signal Timeout | The process record <Speed Below Threshold> is set after x msec without signal change at the input. | UINT16 | RW | 0x0064 (100dec) |
8031:15 | Presentation | Display of the measured value in RPM, Hz, … | UINT16 | RW | 0x0000 (0dec) |
Index 8040 DIG Safe State Active
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8040:0 | DIG Safe State Active |
| UINT8 | RO | 0x08 (8dec) |
8040:01 | X4 Pin4 | Activation of Safe State Value if communication is canceled | BOOLEAN | RW | TRUE |
8040:02 | X4 Pin2 | Activation of Safe State Value if communication is canceled | BOOLEAN | RW | TRUE |
8040:03 | X5 Pin4 | Activation of Safe State Value if communication is canceled | BOOLEAN | RW | TRUE |
8040:04 | X5 Pin2 | Activation of Safe State Value if communication is canceled | BOOLEAN | RW | TRUE |
8040:05 | X6 Pin4 | Activation of Safe State Value if communication is canceled | BOOLEAN | RW | TRUE |
8040:05 | X6 Pin2 | Activation of Safe State Value if communication is canceled | BOOLEAN | RW | TRUE |
8040:07 | X7 Pin4 | Activation of Safe State Value if communication is canceled | BOOLEAN | RW | TRUE |
8040:08 | X7 Pin2 | Activation of Safe State Value if communication is canceled | BOOLEAN | RW | TRUE |
Index 8041 DIG Safe State Value
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8040:0 | DIG Safe State Value |
| UINT8 | RO | 0x00 (0dec) |
8040:01 | X4 Pin4 | Output value if communication is canceled | BOOLEAN | RW | False |
8040:02 | X4 Pin2 | Output value if communication is canceled | BOOLEAN | RW | False |
8040:03 | X5 Pin4 | Output value if communication is canceled | BOOLEAN | RW | False |
8040:04 | X5 Pin2 | Output value if communication is canceled | BOOLEAN | RW | False |
8040:05 | X6 Pin4 | Output value if communication is canceled | BOOLEAN | RW | False |
8040:05 | X6 Pin2 | Output value if communication is canceled | BOOLEAN | RW | False |
8040:07 | X7 Pin4 | Output value if communication is canceled | BOOLEAN | RW | False |
8040:08 | X7 Pin2 | Output value if communication is canceled | BOOLEAN | RW | False |
Index 8043 DIG Safe State Delay
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8040:0 | DIG Safe State Delay |
| UINT8 | RO | 0x00 (0dec) |
8040:01 | X4 Pin4 | Delay in msec after communication is canceled | UINT16 | RW | False |
8040:02 | X4 Pin2 | Delay in msec after communication is canceled | UINT16 | RW | False |
8040:03 | X5 Pin4 | Delay in msec after communication is canceled | UINT16 | RW | False |
8040:04 | X5 Pin2 | Delay in msec after communication is canceled | UINT16 | RW | False |
8040:05 | X6 Pin4 | Delay in msec after communication is canceled | UINT16 | RW | False |
8040:05 | X6 Pin2 | Delay in msec after communication is canceled | UINT16 | RW | False |
8040:07 | X7 Pin4 | Delay in msec after communication is canceled | UINT16 | RW | False |
8040:08 | X7 Pin2 | Delay in msec after communication is canceled | UINT16 | RW | False |
Index 8050 PWM Settings
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8050:0 | PWM Settings | Maximum subindex | UINT8 | RO | 0x22 (34dec) |
8050:03 | Enable dithering | Dithering is "enabled", activation via process data | BOOLEAN | RW | 0x00 (0dec) |
8050:04 | Invert polarity | Reverse current direction | BOOLEAN | RW | 0x00 (0dec) |
8050:05 | Watchdog | 0: Default watchdog value 1: Watchdog ramp active 2: Last output value active | BIT2 | RW | 0x00 (0dec) |
8050:0B | Offset | This is the user scale offset Scale: 1 = nominal current of the terminal / 1024 | INT16 | RW | 0x0000 (0dec) |
8050:0C | Gain | This is the user scale gain. The gain is a fixed-point number with the factor 2^-16. The value one corresponds to 65536 (0x00010000). | INT32 | RW | 0x00010000 (65536dec) |
8050:0D | Default output | This is the default output value. The value is output if it is activated via 0x8pp0:05. | INT16 | RW | 0x0000 (0dec) |
8050:0E | Default output ramp | This value defines the ramps for the ramp-down to the default value. The value is specified in digits / ms. If the entry is 100 and the default value 0, for example, it takes 327 ms (32767/100) for the output value to change from the maximum value (32767) to the default value in the event of a fault. | UINT16 | RW | 0xFFFF (65535dec) |
8050:10 | Max current [mA] | Maximum output current in mA. Value range: 0 ... 1200dec. | UINT8 | RW | 0x7FFF (32767dec) |
8050:12 | Kp factor | This is the user scale gain. The gain is a fixed-point number with the factor 2-16. The value one corresponds to 65535 (0x00010000). | UINT16 | RW | 0x00FA (250dec) |
8050:13 | Ki factor | This is the default output value | UINT16 | RW | 0x0004 (4dec) |
8050:14 | Kd factor | This value defines the ramps for the ramp-down to the default value. The value is specified in digits / ms. If the entry is 100 and the default value 0, for example, it takes 327 ms (32767/100) for the output value to change from the maximum value (32767) to the default value in the event of a fault. | UINT16 | RW | 0x0032 (50dec) |
8050:1E | Dithering frequency [Hz] | Dither frequency in Hertz | UINT16 | RW | 0x0064 (100dec) |
8050:1F | Dithering amplitude [%] | Dithering amplitude in percent of the maximum permitted current (nominal box current * 0x8pp0:10) | UINT8 | RW | 0x0A (10dec) |
8050:21 | Select info data 1 | Selection of synchronous info data (s. 0x6pp0:11) | UINT8 | RW | 0x00 (0dec) |
8050:22 | Select info data 2 | Selection of synchronous info data (s. 0x6pp0:12) | UINT8 | RW | 0x00 (0dec) |
Index 8060 AO Settings
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
8060:0 | AO Settings |
| UINT8 | RO | 0x16 (22dec) |
8060:01 | Enable user scale | This entry activates the scaling for 0x8pp0:11 and 0x8pp0:12. | BOOLEAN | RW | 0x00 (0dec) |
8060:02 | Presentation | 0: Signed presentation 1: Unsigned presentation The output value range 0x7pp1:11 is shown as 16 bit unsigned integer. Negative values are not possible. 2: Absolute value with MSB as sign, signed amount representation is active. 3: Absolute value, the absolute value of the signed representation is formed. | BIT3 | RW | 0x00 (0dec) |
8060:05 | Watchdog | 0: Default watchdog value 1: Watchdog ramp 2: Last output value | BIT2 | RW | 0x00 (0dec) |
8060:07 | Enable user calibration | Enabling of the user calibration | BOOLEAN | RW | 0x00 (0dec) |
8060:08 | Enable vendor calibration | Enable vendor calibration | BOOLEAN | RW | 0x01 (1dec) |
8060:11 | User scale offset | This is the user scaling offset | INT16 | RW | 0x0000 (0dec) |
8060:12 | User scale gain | This is the user scaling gain. The gain is a fixed-point number with the factor 2^-16. The value 1 corresponds to 65535 (0x00010000). | INT32 | RW | 0x00010000 (65536dec) |
8060:13 | Default output | This is the default output value | INT16 | RW | 0x0000 (0dec) |
8060:14 | Default output ramp | This value defines the ramps for the ramp-down to the default value. The value is specified in digits / ms. If the entry is 100 and the default value 0, for example, it takes 327 ms (32767/100) for the output value to change from the maximum value (32767) to the default value in the event of a fault. | UINT16 | RW | 0xFFFF (65535dec) |
8060:15 | User calibration offset | User calibration offset | INT16 | RW | 0x0000 (0dec) |
8060:16 | User calibration gain | User gain compensation | UINT16 | RW | 0x4000 (16384dec) |
Index F800 AIAO Range settings
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
F800:0 | AIAO Range settings |
| UINT8 | RO | 0x08 (8dec) |
F800:01 | Input type Ch1 | Select input type for Ch1 | UINT16 | RW | 0x0001 (1dec) |
F800:02 | Input type Ch2 | Select input type for Ch2 | UINT16 | RW | 0x0001 (1dec) |
F800:08 | Output type | Select input type for Ch1 | UINT16 | RW | 0x0001 (1dec) |