Determine number of pole pairs
If the number of pole pairs of the motor is not specified in the data sheet, you can determine it experimentally.
Procedure
- Prerequisite: the motor has been configured in accordance with the chapter Quick start guide.
- 1. Ensure that the parameter 0x2003:13/0x2803:13 Motor pole pairs Ch.1/Ch.2 has the value 1.
- 2. Send the request to the motor to perform a full rotation.
- The motor only performs a partial rotation because the number of pole pairs has not yet been set correctly.
- 3. Repeat the request until the motor has completed one full rotation.
- The number of requests needed for a full rotation corresponds to the number of pole pairs.
- 4. Enter the number of pole pairs in the parameter 0x2003:13/0x2803:13 Motor pole pairs Ch.1/Ch.2.
- 5. Perform the scanning of the motor again: Scan motor