Scan motor

CAUTION

The motor moves during scanning

The motor rotates in both directions by approx. 1 revolution each during scanning. Injuries and property damage are possible.

  • Ensure that no persons or materials are harmed when the motor is in motion
  • Ensure that the axis can move freely. Release brakes, clamping devices, etc.

You can perform the scan with or without a connected load. If you perform the scan with a connected load, the joint moment of inertia of the motor shaft and the load is measured when the parameter 0x2003:18 "Rotor moment of inertia" is measured.

Prerequisite: all previous steps in this quick start guide have been carried out correctly.
1. If you have already enabled the axis, cancel the axis enable
2. For Channel 1: Write command 0x8007 to parameter FB00:01 Request.
For Channel 2: Write command 0x8017 to parameter FB00:01 Request.
The scan will be executed. It takes about one minute.
3. Monitor the status of the scan in parameter 0xFB00:02:

Value of 0xFB00:02 "Status"

Meaning

100dec…200dec

Progress of the scan

  • 100 = 0%
  • 200 = 100%

0

The scan was successful

1

The scan was successful

0xFB00:03 Response contains additional information

2

Error

3

Error

0xFB00:03 Response contains additional information

If the scan was successful, the values determined are saved in the following CoE parameters (Channel 1/2):