Configuration objects

8000 ENC Settings Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

8000:0

ENC Settings Ch.1

 

USINT

RO

0xE (14dec)

8000:0E

Reversion of rotation

Inverts the counting direction of the encoder.

BOOL

RW

00

8010 STM Motor Settings Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

8010:0

STM Motor Settings Ch.1

 

USINT

RO

0x11 (17dec)

8010:01

Maximal current

The maximum current in [mA] that the current controller outputs per motor winding.

UINT

RW

0x1388 (5000dec)

8010:02

Reduced current

Coil current at reduced torque in [mA].

The reduced torque is activated by the "STM Control > Control > Reduce torque" bit.

UINT

RW

0x9C4 (2500dec)

8010:03

Nominal voltage

Rated value of the applied supply voltage UP (8...48 V).

UINT

RW

0xC350 (50000dec)

8010:06

Motor fullsteps

Number of full steps per motor revolution.

UINT

RW

0xC8 (200dec)

8010:09

Start velocity

This value is a threshold value. The box keeps the motor at standstill, as long as the speed setting is smaller than this value.

It is specified in 0.01 % of the parameter 8012:05 "Speed Range".

UINT

RW

0x0 (0dec)

8010:10

Drive on delay time

The delay in [ms] between enabling the output stage (bit "Enable") and setting the bit "Ready".

(deactivation of the brake if necessary)

UINT

RW

0x64 (100dec)

8010:11

Drive off delay time

The delay in [ms] between setting the "Ready" bit to 0 and deactivating the output stage.

(activation of the brake if necessary)

UINT

RW

0x96 (150dec)

8012 STM Features Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

8012:0

STM Features Ch.1

 

USINT

RO

0x45 (69dec)

8012:01

Operation mode

Controller operation mode

Possible values:

  • 0dec: Automatic
  • 1dec: Velocity direct
  • 2dec: Velocity controller
  • 3dec: Position controller

If the value 0 "Automatic" is set, the controller operation mode is set automatically based on the activated process data objects.

You can find the automatically set operation mode in parameter A010:11 "Actual operation mode".

USINT

RW

0x0 (0dec)

Index (hex)

Name

Meaning

Data type

Flags

Default

8012:05

Speed range

Preselection of the speed range.

Possible values:

  • 0dec: 1000 Fullsteps/sec
  • 1dec: 2000 Fullsteps/sec
  • 2dec: 4000 Fullsteps/sec
  • 3dec: 8000 Fullsteps/sec
  • 4dec: 16000 Fullsteps/sec
  • 5dec: 32000 Fullsteps/sec

Important: If you are using TwinCAT NC, you must recalculate the "Reference Velocity" each time you change the "Speed range", see chapter Axis.

USINT

RW

0x1 (1dec)

8012:09

Invert motor polarity

Reverses the direction of rotation of the motor.

BOOL

RW

00

8012:11

Select info data 1

Choice of operating data to be transmitted in the process value "STM Synchron info data > Info data 1".

Possible values:

  • 0dec: Status word
  • 7dec: Motor velocity
  • 9dec: Status word 2
  • 10dec: Motor load
  • 11dec: Motor smart current
  • 101dec: Internal temperature
  • 103dec: Control voltage
  • 104dec: Motor supply voltage
  • 106dec: Motor supply current
  • 150dec: Drive - Status word
  • 151dec: Drive - State
  • 152dec: Drive - Position lag (low word)
  • 153dec: Drive - Position lag (high word)

USINT

RW

0x0 (0dec)

8012:19

Select info data 2

Choice of operating data to be transmitted in the process value "STM Synchron info data > Info data 2".

Possible values:

  • 0dec: Status word
  • 7dec: Motor velocity
  • 9dec: Status word 2
  • 10dec: Motor load
  • 11dec: Motor smart current
  • 101dec: Internal temperature
  • 103dec: Control voltage
  • 104dec: Motor supply voltage
  • 106dec: Motor supply current
  • 150dec: Drive - Status word
  • 151dec: Drive - State
  • 152dec: Drive - Position lag (low word)
  • 153dec: Drive - Position lag (high word)

USINT

RW

0x9 (9dec)

8012:30

Invert digital input 1

Inverts the input level of input DI1 (X01, pin 4).

BOOL

RW

00

8012:31

Invert digital input 2

Inverts the input level of input DI2 (X02, pin 4).

BOOL

RW

00

8012:32

Function for input 1

Function of input DI1 (X01, pin 4)

Possible values:

  • 0dec: Normal input
  • 1dec: Hardware enable
    A logical 1 is also required at DI1 for axis enable.
  • 2dec: Plc cam
  • 3dec: Auto start

USINT

RW

0x0 (0dec)

8012:36

Function for input 2

Function of input DI2 (X02, pin 4)

Possible values:

  • 0dec: Normal input
  • 1dec: Hardware enable
    A logical 1 is also required at DI2 for axis enable.
  • 2dec: Plc cam
  • 3dec: Auto start

USINT

RW

0x0 (0dec)

8012:3A

Function for output 1

Function of the brake output on X03

Possible values:

  • 0dec: Normal output
  • 1dec: Break (linked with driver enable)
    Links the brake output with the axis enable: The brake output is switched on when the axis is enabled.

USINT

RW

0x0 (0dec)

8012:45

Microstepping

Microstep resolution

Possible values:

  • 0dec: Fullstep
  • 1dec: Halfstep
  • 2dec: 1/4 Microstepping
  • 3dec: 1/8 Microstepping
  • 4dec: 1/16 Microstepping
  • 5dec: 1/32 Microstepping
  • 6dec: 1/64 Microstepping
  • 7dec: 1/128 Microstepping
  • 8dec: 1/256 Microstepping

USINT

RW

0x8 (8dec)

8013 STM Controller Settings 2 Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

8013:0

STM Controller Settings 2 Ch.1

 

USINT

RO

0x8 (8dec)

8013:01

Kp factor (velo./pos.)

Proportional component of the controller

UINT

RW

0x3E8 (1000dec)

8013:02

Ki factor (velo./pos.)

Integral component of the controller

UINT

RW

0x0 (0dec)

8013:03

Inner window (velo./pos.)

Inner window of the integral component in [%]

USINT

RW

0x0 (0dec)

8013:05

Outer window (velo./pos.)

Outer window of the integral component in [%]

USINT

RW

0x0 (0dec)

8013:06

Filter cut off frequency (velo./pos.)

Low-pass filter cut-off frequency

Unit: Hz

UINT

RW

0x0 (0dec)

8013:07

Ka factor (velo./pos.)

Factor for adjusting the output current in acceleration phases

UINT

RW

0x0 (0dec)

8013:08

Kd factor (velo./pos.)

Factor for adjusting the output current in braking phases

UINT

RW

0x0 (0dec)

8014 STM Motor Features Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

8014:0

STM Motor Features Ch.1

 

USINT

RO

0x31 (49dec)

8014:01

Chopper: Mode

Possible values:

  • 0dec: Intelligent off time
  • 1dec: Constant off time
  • 2dec: Random off time

USINT

RW

0x0 (0dec)

8014:03

Chopper: Off time

Possible values:

  • 2dec: 4 µs
  • 3dec: 6 µs
  • 4dec: 8 µs
  • 5dec: 10 µs
  • 6dec: 12 µs
  • 7dec: 14 µs
  • 8dec: 16 µs
  • 9dec: 18 µs
  • 10dec: 20 µs
  • 11dec: 22 µs
  • 12dec: 24 µs
  • 13dec: 26 µs
  • 14dec: 28 µs
  • 15dec: 30 µs

USINT

RW

0x5 (5dec)

8014:07

Chopper: Comparator disabled

 

BOOL

RW

00

8014:08

Chopper: Fast decay time

Possible values:

  • 0dec: Slow decay only
  • 1dec: 2 µs
  • 2dec: 4 µs
  • 3dec: 6 µs
  • 4dec: 8 µs
  • 5dec: 10 µs
  • 6dec: 12 µs
  • 7dec: 14 µs
  • 8dec: 16 µs
  • 9dec: 18 µs
  • 10dec: 20 µs
  • 11dec: 22 µs
  • 12dec: 24 µs
  • 13dec: 26 µs
  • 14dec: 28 µs
  • 15dec: 30 µs

USINT

RW

0x3 (3dec)

Index (hex)

Name

Meaning

Data type

Flags

Default

8014:0C

Chopper: Sine wave offset

Possible values:

  • 0dec: -3
  • 1dec: -2
  • 2dec: -1
  • 3dec: 0
  • 4dec: 1
  • 5dec: 2
  • 6dec: 3
  • 7dec: 4
  • 8dec: 5
  • 9dec: 6
  • 10dec: 7
  • 11dec: 8
  • 12dec: 9
  • 13dec: 10
  • 14dec: 11
  • 15dec: 12

USINT

RW

0x3 (3dec)

8014:11

Chopper: Hysteresis start value

Possible values:

  • 0dec: 1
  • 1dec: 2
  • 2dec: 3
  • 3dec: 4
  • 4dec: 5
  • 5dec: 6
  • 6dec: 7
  • 7dec: 8

USINT

RW

0x2 (2dec)

8014:14

Chopper: Hysteresis end value

Possible values:

  • 0dec: -3
  • 1dec: -2
  • 2dec: -1
  • 3dec: 0
  • 4dec: 1
  • 5dec: 2
  • 6dec: 3
  • 7dec: 4
  • 8dec: 5
  • 9dec: 6
  • 10dec: 7
  • 11dec: 8
  • 12dec: 9
  • 13dec: 10
  • 14dec: 11
  • 15dec: 12

USINT

RW

0x6 (6dec)

8014:18

Chopper: Hysteresis decrement time

Possible values:

  • 0dec: 1 µs
  • 1dec: 2 µs
  • 2dec: 3 µs
  • 3dec: 4 µs

USINT

RW

0x0 (0dec)

8014:1A

Stall guard: Filter enable

 

BOOL

RW

01

8014:1B

Stall guard: Current up step width

Possible values:

  • 0dec: 1
  • 1dec: 2
  • 2dec: 4
  • 3dec: 8

USINT

RW

0x0 (0dec)

8014:1D

Stall guard: Current down step speed

Possible values:

  • 0dec: 1/32
  • 1dec: 1/8
  • 2dec: 1/2
  • 3dec: 1

USINT

RW

0x0 (0dec)

8014:1F

Stall guard: Minimum current

Possible values:

  • 0dec: 1/2 max. current
  • 1dec: 1/4 max. current

BOOL

RW

00

8014:21

Stall guard: Minimum value

Possible values:

  • 0dec: Stall guard off
  • 1dec: 1
  • 2dec: 2
  • 3dec: 3
  • 4dec: 4
  • 5dec: 5
  • 6dec: 6
  • 7dec: 7
  • 8dec: 8
  • 9dec: 9
  • 10dec: 10
  • 11dec: 11
  • 12dec: 12
  • 13dec: 13
  • 14dec: 14
  • 15dec: 15

USINT

RW

0x0 (0dec)

8014:25

Stall guard: Hysteresis value

Possible values:

  • 0dec: 0
  • 1dec: 1
  • 2dec: 2
  • 3dec: 3
  • 4dec: 4
  • 5dec: 5
  • 6dec: 6
  • 7dec: 7
  • 8dec: 8
  • 9dec: 9
  • 10dec: 10
  • 11dec: 11
  • 12dec: 12
  • 13dec: 13
  • 14dec: 14
  • 15dec: 15

USINT

RW

0x0 (0dec)

8014:31

Stall guard: Threshold value

 

SINT

RW

0x1 (1dec)

8020 POS Settings Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

8020:0

POS Settings Ch.1

 

USINT

RO

0x11 (17dec)

8020:01

Velocity min.

Settings for the Positioning Interface; see chapter Parameter set

INT

RW

0x64 (100dec)

8020:02

Velocity max.

INT

RW

0x2710 (10000dec)

8020:03

Acceleration pos.

UINT

RW

0x3E8 (1000dec)

8020:04

Acceleration neg.

UINT

RW

0x3E8 (1000dec)

8020:05

Deceleration pos.

UINT

RW

0x3E8 (1000dec)

8020:06

Deceleration neg.

UINT

RW

0x3E8 (1000dec)

8020:07

Emergency deceleration

UINT

RW

0x64 (100dec)

8020:08

Calibration position

UDINT

RW

0x0 (0dec)

8020:09

Calibration velocity (towards plc cam)

INT

RW

0x64 (100dec)

8020:0A

Calibration Velocity (off plc cam)

INT

RW

0xA (10dec)

8020:0B

Target window

UINT

RW

0xA (10dec)

8020:0C

In-Target timeout

UINT

RW

0x3E8 (1000dec)

8020:0D

Dead time compensation

INT

RW

0x32 (50dec)

8020:0E

Modulo factor

UDINT

RW

0x0 (0dec)

8020:0F

Modulo tolerance window

UDINT

RW

0x0 (0dec)

8020:10

Position lag max.

UINT

RW

0x0 (0dec)

8020:11

Calibration acceleration (around plc cam)

UINT

RW

0x0 (0dec)

8021 POS Features Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

8021:0

POS Features Ch.1

 

USINT

RO

0x16 (22dec)

8021:01

Start type

Settings for the Positioning Interface; see chapter Parameter set

UINT

RW

0x1 (1dec)

8021:11

Time information

USINT

RW

0x0 (0dec)

8021:13

Invert calibration cam search direction

BOOL

RW

01

8021:14

Invert sync impulse search direction

BOOL

RW

00

8021:15

Emergency stop on position lag error

BOOL

RW

00

8021:16

Enhanced diag history

BOOL

RW

00

F80F STM Vendor data

Index (hex)

Name

Meaning

Data type

Flags

Default

F80F:0

STM Vendor data

 

USINT

RO

0x9 (9dec)

F80F:04

Warning temperature

Temperature threshold value in [°C] for reporting an overtemperature warning.

SINT

RW

0x50 (80dec)

F80F:05

Switch off temperature

Temperature threshold value in [°C] for shutdown of the output stage.

SINT

RW

0x64 (100dec)

F80F:09

Maximum current

 

UINT

RW

0x1DC9 (7625dec)

F81F STM Vendor data 2

Index (hex)

Name

Meaning

Data type

Flags

Default

F81F:0

STM Vendor data 2

 

USINT

RO

0x8 (8dec)

F81F:01

Slope control low side

Possible values:

  • 0dec: min.
  • 2dec: med.
  • 3dec: max.

USINT

RW

0x3 (3dec)

F81F:03

Slope control high side

Possible values:

  • 0dec: min.
  • 1dec: min. + tc
  • 2dec: med. + tc
  • 3dec: max.

USINT

RW

0x3 (3dec)

F81F:05

Sense voltage

Possible values:

  • 0dec: 305 mV
  • 1dec: 165 mV

BOOL

RW

00

F81F:08

Blank time

Possible values:

  • 0dec: 1,0 µs
  • 1dec: 1,5 µs
  • 2dec: 2,3 µs
  • 3dec: 3,4 µs

USINT

RW

0x2 (2dec)