Digital I/O X01, X02
The connections for the digital I/O are two 5-pin M12 sockets, A-coded.
X01
Pin | Function | Description |
|---|---|---|
1 | 24 V US | Supply voltage output US = 24 VDC |
2 | SET | Digital output, intended for zeroing the encoder counter reading. This pin is directly connected to X05, pin 7 "SET". The high level of this digital output corresponds to the configured encoder supply voltage, 5 V or 9 V. See chapter Setting the encoder supply voltage. |
3 | GND | Ground |
4 | DI1 | Digital input 1 |
5 | ⏚ | Functional earth |
X02
Pin | Function | Description |
|---|---|---|
1 | 24 V US | Supply voltage output US = 24 VDC |
2 | DIR | Digital output, intended for changing the counting direction of the encoder. This pin is directly connected to X05, pin 8 "DIR". The high level of this digital output corresponds to the configured encoder supply voltage, 5 V or 9 V. See chapter Setting the encoder supply voltage. |
3 | GND | Ground |
4 | DI2 | Digital input 2 |
5 | ⏚ | Functional earth |