Technical data
All values are typical values over the entire temperature range, unless stated otherwise.
EtherCAT | |
|---|---|
Connection | 2 x M8 socket, 4-pin, A-coded, shielded |
Electrical isolation | 500 V |
Distributed Clocks | yes |
Supply voltages | |
|---|---|
Connection | Input: 7/8" plug, 5-pin, 16-UN thread Downstream connection: 7/8" socket, 5-pin, 16-UN thread |
|
US nominal voltage |
24 VDC (-15 % / +20 %) |
US sum current | max. 16 A at 40 °C |
Current consumption from US | 120 mA + Encoder supply + Digital output currents + Current for the holding brake |
UP rated voltage | 8…48 VDC |
UP sum current | max. 16 A at 40 °C |
Current consumption from UP | = Current consumption of the motor output stage |
Motor | |
|---|---|
Number of channels | 1 |
Motor type | 2-phase stepper motor, unipolar or bipolar |
Connection | M12 socket, 5-pin, A-coded |
Motor supply | 8…48 VDC from UP |
Rated current | 3.5 A per phase |
Peak current | 5 A per phase |
Overload- and short-circuit proof | Yes |
Step frequency | max. 8,000 full steps/s |
Current controller frequency | Dynamic |
Microstepping | max. 256 intermediate steps per full step |
Encoder interface | |
|---|---|
Number of channels | 1 |
Protocols |
|
Connection | 1 x M12 socket, 8-pin, A-coded |
Resolution | max. 64 bit position value, 2 bit status, 16 bit CRC |
Encoder supply | Configurable: 5 VDC (default) or 9 VDC from US max. 0.5 A |
Digital outputs for control signals | Zero, Direction |
Holding brake | |
|---|---|
Number of channels | 1 |
Connection | 1 x M12 socket, 5-pin, A-coded |
Rated voltage | 24 VDC from US |
Output current | max 0.5 A |
Digital outputs | |
|---|---|
Number | 2 |
Connection | Each digital output is available on two connections in parallel:
|
Cable length | max. 30 m |
Load type | Ohmic, inductive, lamp load |
Output voltage | Corresponds to the configured encoder supply |
Output current | max. 0.5 A per channel, individually short-circuit proof |
Auxiliary voltage output | 24 VDC from US,max. 0.5 A in total, short-circuit proof |
Digital inputs | |
|---|---|
Number | 2 |
Application options |
|
Connection | 2 x M12 socket, 5-pin, A-coded |
Cable length | max. 30 m |
Sensor power supply | 24 VDC from US max. 0.5 A in total, short-circuit proof |
Environmental conditions | |
|---|---|
Ambient temperature during operation | -25 … +60 °C |
Ambient temperature during storage | -40 … +85 °C |
Vibration / shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 |
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 |
Protection class | IP65, IP66, IP67 conforms to EN 60529 |
Approvals/markings | |
|---|---|
Approvals/markings *) | CE, cURus |
*) Real applicable approvals/markings see type plate on the side (product marking).
Additional tests
The devices have undergone the following additional tests:
Test | Explanation |
|---|---|
Vibration | 10 frequency sweeps in 3 axes |
5 Hz < f < 60 Hz displacement 0.35 mm, constant amplitude | |
60.1 Hz < f < 500 Hz acceleration 5 g, constant amplitude | |
Shocks | 1000 shocks in each direction, in 3 axes |
35 g, 11 ms |