Objects for digital inputs
These objects are only available in products that have a digital input at pin 2 of their IO-Link ports:
- EP6224-0002
- EP6224-0092
- EP6228-0042
- EP6228-3132
- EP6228-3142
Index 1A20 Digital TxPDO-Map Inputs
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1A20:0 | DeviceState TxPDO-Map Inputs | PDO Mapping | UINT8 | RW | 0x04 (4dec) |
1A20:01 | SubIndex 001 | 1. PDO Mapping entry (object 0xF100 (Diagnosis Status data), entry 0x01 (State Ch1)) | UINT32 | RW | 0xF102:01, 1 |
1A20:02 | SubIndex 002 | 2. PDO Mapping entry (object 0xF100 (Diagnosis Status data), entry 0x02 (State Ch2)) | UINT32 | RW | 0xF102:02, 1 |
1A20:03 | SubIndex 003 | 3. PDO Mapping entry (object 0xF100 (Diagnosis Status data), entry 0x03 (State Ch3)) | UINT32 | RW | 0xF102:03, 1 |
… | … | … | … | … | … |