Flow control
EP6002 supports a software flow control for send data and for receive data.
The flow control is disabled in the factory setting. Enable the flow control by setting the following CoE parameters to TRUE:
Channel | Cable | CoE object | Parameter | ||
|---|---|---|---|---|---|
1 | send data | 8000hex | COM Settings Ch.1 | 02hex | Enable XON/XOFF supported tx data |
receive data | 8000hex | COM Settings Ch.1 | 03hex | Enable XON/XOFF supported rx data | |
2 | send data | 8010hex | COM Settings Ch.2 | 02hex | Enable XON/XOFF supported tx data |
receive data | 8010hex | COM Settings Ch.2 | 03hex | Enable XON/XOFF supported rx data | |