Output signal range

The output signal range can be selected individually for each analog output.

Set the output signal ranges in the CoE parameters "Input Type":

Channel

"Output Type"

1

0x803D:11

2

0x804D:11

Possible values for EP4304-1002

Value

Output signal range

2dec (factory setting)

U ±10V

14dec

U 0-10V

65535dec

Disabled

Possible values for EP4314-1002

Value

Output signal range

16dec

I ±10 mA

17dec (factory setting)

I ±20 mA

18dec

I 0-20 mA

19dec

I 4-20 mA

65535dec

Disabled

Example

Output signal range 1: