Measuring range 4 … 20 mA
Technical data  | Measuring range 4...20 mA  | 
|---|---|
Measuring range, nominal  | 4…20 mA  | 
Measuring range, end value (full scale value)  | 20 mA  | 
Measuring range, technically usable  | 0…+21.179 mA, overcurrent-protected  | 
Fuse protection  | Internal overload limiting, continuous current resistant  | 
PDO resolution  | 16-bit, including sign  | 
PDO LSB (Extended Range)  | 524.28 nA  | 
PDO LSB (Legacy Range)  | 488.30 nA  |