Measuring range 4 … 20 mA
Technical data | Measuring range 4...20 mA |
|---|---|
Measuring range, nominal | 4…20 mA |
Measuring range, end value (full scale value) | 20 mA |
Measuring range, technically usable | 0…+21.179 mA, overcurrent-protected |
Fuse protection | Internal overload limiting, continuous current resistant |
PDO resolution | 16-bit, including sign |
PDO LSB (Extended Range) | 524.28 nA |
PDO LSB (Legacy Range) | 488.30 nA |