Output signal range

The output signal range can be selected individually for each analog output.

Set the output signal ranges in the following CoE parameters:

Connection

CoE object

Parameter

X01

814Dhex

AO Advanced Settings Ch.1

11hex

Output Type

X02

815Dhex

AO Advanced Settings Ch.2

11hex

Output Type

X05

816Dhex

AO Advanced Settings Ch.3

11hex

Output Type

X06

817Dhex

AO Advanced Settings Ch.4

11hex

Output Type

Possible values

Value

Output signal range

2dec (factory setting)

-10 … +10 V

14dec

0 … 10 V

18dec

0 … 20 mA

19dec

4 … 20 mA

Example

Output signal range 1:
"Output Type" CoE parameter for the analog output at connection X01