Oversampling

Basics

When operating without oversampling, process data is transferred exactly once per EtherCAT cycle. Conversely, the temporal resolution of a process record directly depends on the communication cycle time. Higher temporal resolution is only possible through a reduction in cycle time - with associated practical limits.

Oversampling enables multiple sampling of an input variable within an EtherCAT cycle and subsequent transmission of the measured values in an array. The oversampling factor describes the number of samples within an EtherCAT cycle and is therefore an integer.

Requirements

Selecting the oversampling factor

The following table shows the oversampling factors for all permissible combinations of EtherCAT cycle time and sampling rate (ODR) in accordance with the above requirements. Set the oversampling factor by selecting the corresponding Predefined PDO Assignment. See chapter Setting a Predefined PDO Assignment.

EtherCAT
cycle time

Sampling rate (ODR)

4000 Hz

2000 Hz

1000 Hz

200 Hz

100 Hz

0.5 ms

2

--

--

--

--

1 ms

4

2

--

--

--

2 ms

8

4

2

--

--

2.5 ms

10

--

--

--

--

4 ms

16

--

4

--

--

5 ms

20

8

--

--

--

8 ms

--

16

8

--

--

10 ms

40

20

10

2

--