Setting a Predefined PDO Assignment

Predefined PDO Assignments are useful combinations of process data objects.

You can set the desired Predefined PDO Assignment in the "Process Data" tab.

Setting a Predefined PDO Assignment 1:
Setting a Predefined PDO Assignment 2:

Recommendation: Only use REAL32

Predefined PDO Assignments whose names contain the character string "DINT" switch the output format for the measured values from REAL32 (floating point) to DINT (integer).
These Predefined PDO Assignments only exist to ensure backward compatibility; DINT does not have a higher resolution than REAL32. Their use is generally not recommended.

  • Recommendation: Do not set a Predefined PDO Assignment whose designation contains the string "DINT".

The following table only shows the recommended Predefined PDO Assignments (REAL32):

Predefined PDO Assignment

Use

REAL32 (Default)

Operation without oversampling

REAL32 with Input Cycle Counter

Operation without oversampling with additional process data object "AI Acc X Input Cycle Counter"

DC Oversampling 2 REAL32

Oversampling operation with oversampling factor 2

DC Oversampling 4 REAL32

Oversampling operation with oversampling factor 4

DC Oversampling 8 REAL32

Oversampling operation with oversampling factor 8

DC Oversampling 10 REAL32

Oversampling operation with oversampling factor 10

DC Oversampling 16 REAL32

Oversampling operation with oversampling factor 16

DC Oversampling 20 REAL32

Oversampling operation with oversampling factor 20

DC Oversampling 40 REAL32

Oversampling operation with oversampling factor 40