Objects for parameterization

Index 8pp0 AI Acc Settings / AI Gyro Settings

  • Measuring axis "Acc X": Index 8000
  • Measuring axis "Acc Y": Index 8010
  • Measuring axis "Acc Z": Index 8020
  • Measuring axis "Gyro X": Index 8030
  • Measuring axis "Gyro Y": Index 8040
  • Measuring axis "Gyro Z": Index 8050

Subindex (hex)

Name

Meaning

Data type

Flags

Default

0

AI Acc/Gyro Settings

 

UINT8

RO

0x1E (30dec)

0A

Enable user calibration

Enables user calibration.

See chapter User calibration.

BOOLEAN

RW

0x00 (0dec)

0B

Enable vendor calibration

Enables vendor calibration.

BOOLEAN

RW

0x01 (1dec)

15

Filter settings

Filter type.

See chapter Measured value filter.

UINT16

RW

0x0000 (0dec)

1E

Slope detection sensitivity

Sensitivity of the status display (LEDs).

See chapter Status display.

UINT16

RW

0x0002 (2dec)

Index 8pp1 AI Acc Filter 1 Settings

Filter coefficients for the filter types "User Defined FIR Filter", "User Defined IIR Filter" and "User Defined Average Filter". For more information, see chapter Measured value filter.

  • Measuring axis "Acc X": Index 8001
  • Measuring axis "Acc Y": Index 8011
  • Measuring axis "Acc Z": Index 8021
  • Measuring axis "Gyro X": Index 8031
  • Measuring axis "Gyro Y": Index 8041
  • Measuring axis "Gyro Z": Index 8051

Subindex (hex)

Name

Meaning

Data type

Flags

Default

0

AI Acc Filter 1 Settings

 

UINT8

RO

0x28 (40dec)

01

Filter Coefficient 1

 

INT32

RW

0x00000000 (0dec)

02

Filter Coefficient 2

 

INT32

RW

0x00000000 (0dec)

03

Filter Coefficient 3

 

INT32

RW

0x00000000 (0dec)

…

…

…

…

…

…

26

Filter Coefficient 38

 

INT32

RW

0x00000000 (0dec)

27

Filter Coefficient 39

 

INT32

RW

0x00000000 (0dec)

28

Filter Coefficient 40

 

INT32

RW

0x00000000 (0dec)

Index 8ppB AI Acc Settings Information

Subindex (hex)

Name

Meaning

Data type

Flags

Default

0

AI Acc Settings Information

 

UINT8

RO

0x01 (1dec)

01

Info 1

 

STRING

RW

 

Index 8ppC AI Acc User Calibration Data

Parameters for user calibration. For more information, see chapter User calibration.

  • Measuring axis "Acc X": Index 800C
  • Measuring axis "Acc Y": Index 801C
  • Measuring axis "Acc Z": Index 802C
  • Measuring axis "Gyro X": Index 803C
  • Measuring axis "Gyro Y": Index 804C
  • Measuring axis "Gyro Z": Index 805C

Subindex (hex)

Name

Meaning

Data type

Flags

Default

0

AI Acc User Calibration Data

 

UINT8

RO

0x04 (4dec)

01

Calibration Date

Date of the user calibration.

OCTET-STRING[4]

RW

{0}

03

S0

Offset

REAL32

RW

0x00000000 (0dec)

04

S1

Gain

REAL32

RW

0x3F800000 (1065353216dec)

Index 8ppF AI Acc Vendor data

Subindex (hex)

Name

Meaning

Data type

Flags

Default

0

AI Acc Vendor data

 

UINT8

RO

0x02 (2dec)

01

Offset

 

INT16

RW

0x0000 (0dec)

02

Gain

 

INT16

RW

0x4000 (16384dec)

Index 806F AI Temp Vendor data

Index (hex)

Name

Meaning

Data type

Flags

Default

806F:0

AI Temp Vendor data

 

UINT8

RO

0x08 (8dec)

806F:01

Offset

 

INT16

RW

0x0000 (0dec)

806F:02

Gain

 

INT16

RW

0x0000 (0dec)

806F:03

shd0

 

UINT8

RW

0x00 (0dec)

806F:04

shd1

 

UINT8

RW

0x00 (0dec)

806F:05

shd2

 

UINT8

RW

0x00 (0dec)

806F:06

shd3

 

UINT8

RW

0x00 (0dec)

806F:07

shd4

 

UINT8

RW

0x00 (0dec)

806F:08

shd5

 

UINT8

RW

0x00 (0dec)

Index F800 AI Settings

Index (hex)

Name

Meaning

Data type

Flags

Default

F800:0

AI Settings

 

UINT8

RO

0x11 (17dec)

F800:0D

Sampling Rate

Selection of sampling rate (ODR) for all measuring axes.

  • 0: 4000 Hz
  • 1: 2000 Hz
  • 2: 1000 Hz
  • 3: 200 Hz
  • 4: 100 Hz

See chapter Sampling rate (ODR).

UINT16

RW

0x0000 (0dec)

F800:11

Range

Setting the measuring ranges.

See chapter Measuring ranges.

UINT16

RW

0x0000 (0dec)