M12 sockets of EP2028-0032
Pin assignment
Pin | Function | Core color 1) |
|---|---|---|
1 | +24 VDC UP | brown |
2 | (output of an adjacent socket) | white |
3 | GNDP | blue |
4 | Output | black |
5 | FE | gray |
1) The core colors apply to sensor cables from Beckhoff. See chapter Accessories.
Pins 2 and 4 of the following sockets are each internally connected:
- X01 and X02
- X03 and X04
- X05 and X06
- X07 and X08
Taking the example of X01 and X02:
See connection examples.
Status LEDs
There is a green LED next to each M12 socket. The LED lights up when the digital output is switched on.