ZS2001: pluggable spring-loaded terminals
Notice  | |
Incorrect signal levels due to electromagnetic interference Digital inputs with a 10 µs input filter are optimized for fast signal transmission and are therefore susceptible to electromagnetic interference. Under the influence of electromagnetic interference, a false signal level can be detected. 
  | 
                
            
Pin assignment
Contact  | Function  | 
|---|---|
0  | Input 1  | 
1  | Input 2  | 
2  | Input 3  | 
3  | Input 4  | 
4  | Input 5  | 
5  | Input 6  | 
6  | Input 7  | 
7  | Input 8  | 
"24"  | US  | 
"0V"  | GNDS  | 
ZS2001-0004 has three rows with ten terminal contacts each. The first row is occupied as shown in the table. The second and third rows are designed to distribute the supply voltage and ground. See connection examples:
Connection examples
  | 
  | ||
ZS2001-0001 ZS2001-0002  | 
  | ZS2001-0004  | 
  | 
The diagram shows the connection of 8 sensors in single-wire technology and one sensor each in two-wire and three-wire technology.
Please note for connector ZS2001-0004: two bridges (24 V and 0 V) are required to supply the terminal points for two-wire and three-wire connection technology.
Status LEDs
ZS2001-0002 and ZS2001-0004 have a green status LED for each digital input. An LED lights up when a high level is detected at the corresponding input.